RedLINK
TM
Installation Guide (EIM)
69-2091EFS—07 10
15
Compressor off time
(minimum)
5
5 minutes
(Heat On/Cool On flashes during off time)
[Options: 0 to 4 minutes]
16
Schedule format
Applies only to Model TH6320
0
Weekday/weekend program schedule
1
Weekday/Saturday/Sunday program schedule
17
External fossil fuel kit 1
External fossil fuel kit controls backup heat
0
Thermostat controls backup heat (outdoor sensor required)
18
Dual fuel heat pump
control
1
Droop control
**
0
No droop control
**
2
Droop control with Aux Heat Lockout
**
20
Droop temperature
(dual fuel)
2
Auto temperature droop 2° F (1° C)
[Options: 2 to 5 (2 to 5° F / 1 to 2.5° C)]
21
Dual fuel upstage to
furnace timer
1
1 hour
**
[Options: 0 (off) to 16 hours]
22
Outdoor air sensor?
0 No
1 Yes
24
Heat pump
compressor lockout
(balance point)
0
No heat pump compressor lockout
**
1
5
° F (-15° C)
7
35
° F (1.5° C)
2
10
° F (-12° C)
8
40° F (4.5° C)
3
15
° F (-9.5° C)
9
45° F (7° C)
4
20
° F (-6.5° C)
10
50
° F (10° C)
5
25
° F (-4° C)
11
55
° F (13° C)
6
30
° F (-1° C)
12
60° F (15.5° C)
25
Heat pump
auxiliary lockout
0
No heat pump auxiliary lockout
**
1
5
° F (-15° C)
8
40° F (4.5° C)
2
10
° F (-12° C)
9
45° F (7° C)
3
15
° F (-9.5° C)
10
50
° F (10° C)
4
20
° F (-6.5° C)
11
55
° F (13° C)
5
25
° F (-4° C)
12
60° F (15.5° C)
6
30
° F (-1° C)
13
65° F (18.5° C)
7
35
° F (1.5° C)
26
Auxiliary heat control
Applies only to Model TH5320
0 Comfort
**
1 Economy
27
Maximum heat
setpoint
90 Max. heat temperature setting is 90° F (32° C)
[Options: 40 °F to 90 °F (4.5 °
C to 32
°C)]
28
Minimum cool
setpoint
50 Min. cool temperature setting is 50° F (10° C)
[Options: 50 °F to 99 °F (10 °C to 37 °C)]
32
Temp. display offset
(indoor)
0
Thermostat displays actual temperature
[Options: -3 to +3 °F offset (-1.5 to +1.5 °C)]
33
Temp. display offset
(outdoor)
0
Thermostat displays actual temperature
[Options: -5 to +5 °F offset (-2.5 to +2.5 °C)]
35
Humidity display
offset (outdoor)
3
Thermostat displays actual humidity
[Other options: 0 = -15%, 1 = -10%, 2 = -5%, 4 = +5%, 5 = +10%,
6 = +15% offset]
Setup function
Settings & options (factory default in bold)
** See page 11
Installer setup tables