![Honeywell RedLINK Скачать руководство пользователя страница 18](http://html.mh-extra.com/html/honeywell/redlink/redlink_installation-manual_150903018.webp)
RedLINK
TM
Installation Guide (EIM)
69-2091EFS—07 18
Specifications & replacement parts
Operating Ambient Temperature
Thermostat:
32 to 120° F (0 to 48.9° C)
Remote control:
32 to 120° F (0 to 48.9° C)
EIM:
-40 to 165° F (-40 to 73.9° C)
Outdoor air sensor:
-40 to 140° F (-40 to 60° C)
Return air sensor:
0 to 200° F (-17.8 to 93.3° C)
Operating Relative Humidity
Thermostat:
5% to 90% (non-condensing)
Remote control:
5% to 90% (non-condensing)
EIM:
5% to 95% (non-condensing)
Outdoor air sensor:
0% to 100% (condensing)
Physical Dimensions
(height, width, depth)
Thermostat:
3-9/16 x 5-13/16 x 1-1/2 inches (91 x 147 x 38 mm)
EIM:
8-1/8 x 8 x 1-7/8 inches (206 x 203 x 47 mm)
Outdoor air sensor:
5 x 3-1/2 x 1-11/16 inches (127 x 89 x 43 mm)
Return air sensor:
3-7/8 x 4-1/8 x 1-1/4 inches (77 x 102 x 25 mm)
Sensor probe is 3-3/4 inches long (77 mm)
Terminal
Voltage (50/60Hz)
Running Current
W
(heating)
18-30 VAC
1.00A
Y
(cooling)
18-30 VAC
1.00A
G
(fan)
18-30 VAC
0.60A
O/B
(changeover)
18-30 V
AC
0.60A
W2
(heating)
18-30 VAC
0.60A
Y2
(cooling)
18-30 VAC
0.60A
Aux/E
(auxiliary)
18-30 VAC
1.00A
L
(output)
18-30 VAC
0.60A
I
tem
Part Number
Equipment Interface Module (EIM)
THM5320R1000
Wireless adapter
THM4000R1000
FocusPRO
®
wireless thermostat (programmable)
TH6320R1004
FocusPRO
®
wireless thermostat (non-programmable)
TH5320R1002
Remote control
REM5000R1001
Outdoor air sensor
C7089R1013
Return air sensor (for backup control)
C7735A1000
Remote indoor sensor
C7189U1005
(alternative sensor for backup control in hydronic applications)
Battery holder
50007072-001
Cover plate (covers marks left by old thermostats)
50002883-001
Electrical Ratings
(EIM)
Accessories & Replacement Parts