www.honeywell.com/security
96 |
MPA1 User Guide
Replace a Secondary Panel (Web Mode)
Overview
Details the steps to replace a MPA1 "Secondary" panel in an existing loop of Ethernet
Virtual Loop (EVL) in Web Mode.
Secondary Panel Replacement and Synchronization
Step # 1.
Un-register the original Secondary panel in the Primary panel. Navigate to:
•
EVL Tab: Menu > Panel Configuration > Advanced > EVL Discovery.
Step # 2.
Install the replacement Secondary panel in the loop.
Step # 3.
Navigate to the "Advanced" Tab of the primary panel:
•
EVL Installations:
Requires Manual Registration of the Secondary Panels.
• Navigate to the EVL Discovery and "Register" the Secondary Panels.
IMPORTANT:
In order to proceed to Step #4 please wait for the Secondary panel to be
synchronized. Refer to the "System Detail Chart"
Step # 4.
Program and add the new Secondary panels doors into the “Spaces”.
Step # 5.
Program the custom settings for Readers, Input Points and Output Points.
Step # 6.
Perform a "System Wide Backup" when programming is complete.
Hard Default a Primary in an Existing Loop (Web Mode)
Overview
Details the synchronization process of a MPA1 "Primary | Secondary" panel after hard
defaulting an existing "Primary" Panel in Ethernet Virtual Loop (EVL) in Web Mode.
Primary | Secondary Panel Synchronization (Hard Default)
IMPORTANT:
Ensure a "System Wide Backup" is performed prior to Hard Default of the
Primary Panel.
Step # 1.
Perform a hard default and log into the Web Interface.
Step # 2.
Navigate to the "Advanced" Tab of the primary panel:
•
EVL Installations:
Requires Manual Registration of the Secondary Panels.
• Navigate to the EVL Discovery and "Register" the Secondary Panels.
Содержание MPA1
Страница 1: ...Document 800 26311_Rev B July 2020 Access Control Unit MPA1 User Guide ...
Страница 2: ...Revisions Rev Date Revisions A 02 2020 Document created B 07 2020 Document updated with ULC Features ...
Страница 14: ... 13 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Страница 72: ... 75 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Страница 100: ...www honeywell com security 104 MPA1 User Guide This page is intentionally left blank ...
Страница 109: ... 113 Document 800 26311_ A February 2020 Click Open to load the file Confirm Yes when this warning comes up Success ...
Страница 119: ... 125 Document 800 26311_Rev B July 2020 ...