| 49
Document 800-26311_ A - April 2020
3. Select
Input Modes
.
4. Configure Shunt and Debounce times.
5. Configure Scheduling.
6. Click
Save
.
Configuration
Description
Normally
Closed
means that the input’s normal state is closed. (Default
setting).
Open
means that the input’s normal state is open.
State
Unsupervised
means that the input’s electrical circuit is wired in
one path without alternative paths supervised by resistors.
(Default setting)
Supervised
means that the input’s electrical circuit is wired in one
path with alternative paths supervised by resistors. If you select
Supervised, then you must select a Resistor value.
Resistor Value
Specifies the resistor values being used in the supervised modes.
The only available resistor value in supervised mode is 2.2K.
Auto-Relock
Causes the door to re-lock immediately when the door status
switch closes after entry. The output relay that controls the door
strike de-energizes when the associated input returns to normal
state instead of remaining energized for the duration of the pulse
time. To enable Auto-Relock, de-select the Disable check box, and
select the associated output from the drop-down list.
Output
Select an Output value for Auto-Relock.
Configuration
Description
Shunt Time
(h:m:s)
Specifies the amount of time for which the inputs are shunted, or
de-activated. The maximum length of time is 1 hour, 45 minutes,
59 seconds.
You can express seconds in tenths of a second.
Debounce Time
(sec)
Specifies the period of time (MIN = 0 second, MAX = 6553.5
seconds) the input must remain in a new state before generating
an alarm. For example, with a 5-second debounce time selected,
if a Normal state is changed to Alarm, the state must remain in
Alarm for five consecutive seconds before an alarm is generated.
Configuration
Description
Shunt
Specifies the time period during which the input will be ignored.
Disable
Interlocks
Specifies the time period during which the programmed action on
this input from another point will be disabled.
Disable Alarm
Messages
Specifies the time period during which Alarm and Normal will not
be reported, but Short and Cut will be reported.
Short
alarms are
triggered when a short occurs in the system.
Cut
alarms are
triggered when a wire is cut.
Содержание MPA1
Страница 1: ...Document 800 26311_Rev B July 2020 Access Control Unit MPA1 User Guide ...
Страница 2: ...Revisions Rev Date Revisions A 02 2020 Document created B 07 2020 Document updated with ULC Features ...
Страница 14: ... 13 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Страница 72: ... 75 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Страница 100: ...www honeywell com security 104 MPA1 User Guide This page is intentionally left blank ...
Страница 109: ... 113 Document 800 26311_ A February 2020 Click Open to load the file Confirm Yes when this warning comes up Success ...
Страница 119: ... 125 Document 800 26311_Rev B July 2020 ...