| 51
Document 800-26311_ A - April 2020
1. Select Discrete or Group and specify the available number
•
Default number is Discrete (single) output 1. This is the Switched Ground Door Lock
output on the MPA1
2. Select General Settings
3. Select Scheduling
Configuration
Description
Name
Enter a unique name to identify the lock output
Pulse Time
configure how long a device assume to be normal status such as a
hours, minutes and seconds, Maximum time is 1:45:59
Latch
Toggle the start of the outputs between energized and de-energized
upon every activation (code use, interlock, or manual pulse)
Interlocks
Disable/ enable interlocks. See
Configuring Interlocks, page 63
for
more about Interlocks
TZ Card Toggles
Requires like the First Card Rule, a valid card read within the time
zone to enable the time zone (periods in which the doors are
unlocked) to take effect. Unlike the First Card Rule, however the user
can swipe the card a second time to return the doors to a locked
state.
Effective only if the output has a valid schedule for
Energized
in the
Section
Scheduling.
Both TZ Card Toggle and First Card Rule can
not be enable the same time
First Card Rule
First Card Rule requires a valid card read within the time zone to
enable the time zone (period in which the doors are unlocked) to take
effect.
Note
Effectively only if the output has a valid schedule for
Energized
in the section
Scheduling.
Both TZ Card Toggle
and First Card Rule cant be enabled at the same time.
Lock Operations
Specifies the output to function in Fail Secure, or Fail Safe mode in
(default) Fail Secure mode output in normal state is not active. A lock
that needs to be powered to unlock a door will use the Fail Secure
mode. If the MPA1 is not powered the output and lock remains in it
normal state.
In Fail Safe mode the output in the normal state is activated. A lock
that needs to be Powered to lock the door (e.g a magnetic lock) will
use the Fail safe mode. If the MPA 1 is not powered the output and
lock remains in its abnormal state and releases the lock.
Note
The MPA1 does not have the jumpers to provide Fail Safe
operation of the lock
Configuration
Description
Energized
Specifies the period during which the output relay is
automatically energized (Door is unlocked), Select Schedule
Entering a Panel Name, page 28
) from the
drop down list. The Energized state of the output can be
affected by the Enabled setting for the
TZ Card Toggle
or
First
Card Rule
.
Disable Interlocks
Specifies the period during which the Interlock that control
the output will be disabled, Select a Schedule (that you
Entering a Panel Name, page 28
) from the drop-
down list.
Содержание MPA1
Страница 1: ...Document 800 26311_Rev B July 2020 Access Control Unit MPA1 User Guide ...
Страница 2: ...Revisions Rev Date Revisions A 02 2020 Document created B 07 2020 Document updated with ULC Features ...
Страница 14: ... 13 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Страница 72: ... 75 Document 800 26311_ A April 2020 This page is intentionally left blank ...
Страница 100: ...www honeywell com security 104 MPA1 User Guide This page is intentionally left blank ...
Страница 109: ... 113 Document 800 26311_ A February 2020 Click Open to load the file Confirm Yes when this warning comes up Success ...
Страница 119: ... 125 Document 800 26311_Rev B July 2020 ...