Messages and Diagnostic Codes
Release 3
34-ST-25-20 MC Toolkit User Manual
67
9/06
MC TOOLKIT/SDC 625 ERROR MESSAGES
Serial Port is not Available
SetCommMask Error!
SetCommState Error!
SetCommTimeouts Error!
Make sure ActiveSync is not running.
If Several programs are active, try closing one or more open programs.
Stop the MC Toolkit application by doing File | Exit and restart the
program.
Use the Pocket PC hardware reset. See your Pocket PC documentation
reset the unit. Caution: If the Symbol PPT 2800 computer is reset, it will
lose all its installed programs and data. The program will have to be
installed again.
Make sure you are using a Honeywell approved Pocket PC.
Suspend monitor Thread Failed!
Upload Cannot Continue.
System failed to suspend the monitor function
Too Many bytes received on ComPort!
Repeat the command. If the problem persist contact Honeywell TAC.
Transmitter-Modem Receive Buffer
overflow!
This could indicate a software problem with the MC Toolkit Software.
Repeat the command again. If the problem persist contact Honeywell
TAC.
Unknown Error!
MCT101 Users: This could indicate a defective modem. Repeat the
command again. If the problem persist contact Honeywell TAC.
COM Port Initialization Failed
MCT101 Users: Please check the COM Port of the PPC to which
HARTDE Modem is connected. Some other application may be using the
same.
No HARTDE Modem Present
MCT101 Users: HART/DE Modem is not detected. Please check the
Modem connection to PPC & Modem battery.
HARTDE Modem Protocol set failed
MCT101 Users: Unable to set the HART Protocol in Modem. Please
check the Modem. Remove the Modem battery and re-install.
Failed to create Burst Message
Handler thread
Too many applications may be running. Please close some of the
application and restart SDC.
Error In Communication with Device,
Closing the Device.
MCT101 Users: This could be a problem with device connection. Please
check the Modem connection with PPC, Modem connection with Device,
Modem battery and Device power.
No Device found, Do You want to Retry
MCT101 Users: Device is not detected. Please check the Modem
connection with PPC & Device, Modem battery and Device power.
If the above things are perfect, try to change different device detection
options from Preference dialog box under Device/Preferences menu,
restart the SDC.
Could not find XXXX.fms, Loading
Generic DD...
Unable to find the connected Device DD in the DD Library of PPC. You
can still perform Generic operations with the device with Generic DD
loaded. For utilizing full functionalities of the device, update the Device
DD in the DD Library of PPC (in the memory card) and try again.
Unable to Load Generic DD
(0x268005XX)..
Generic DD not available in the DD Library of PPC. Please update your
DD Library of PPC. If the problem persist contact Honeywell TAC