6.
After registering, fill in the device’s Settings tab (and other tabs if
applicable) to fully configure the device. For a summary of settings, see
on page 124. For details, see the
MAXPRO Cloud online help.
5.4.8
LED Indicators
LED Colour
Indication
Function
Green
Steady blink
(0.1s on, 0.9s off)
Power and IB2 communication good
Red
Steady
Powered but not communicating on IB2
–
Off
No power or communication
5.5
MPI Relay Module MPIEOP4
5.5.1
About the MPI Relay Module
The MAXPRO Intrusion (MPI) Relay Module provides four additional
programmable, unsupervised relays for use with MPI Control Panels. The
module may be mounted remotely in its own enclosure, or together with an
MPI Control Panel or MPI Remote Power Supply in a cabinet.
5.5.2
Features
l
Provides four non-supervised relays
l
Status LEDs
l
Lid and off-wall tamper protection, bypassable through MAXPRO Cloud
programming.
5.5.3
Mounting
You can install the Relay Module against a wall in its own enclosure, or:
l
You can install up to two Relay Modules in a cabinet on top of and/or next to
an MPI Remote Power Supply.
l
You can install one Relay Module in a cabinet on top of the MPI Control
Panel.
The procedure below is for mounting the device on the wall in its own
enclosure. For installing in a cabinet, see
Cabinet Mounting with Control Panel or
76
800-23044 Rev. A draft_11
Installation and Setup Guide
Honeywell MAXPRO Intrusion MPIP2000U/3000U Series
Содержание MAXPRO MPIP2000U Series