
The default settings in MAXPRO Cloud are suitable for this SAB configuration:
Trigger Output 1 = Exterior Siren; and Trigger Output 2 = Strobe. If you
have wired up the SAB as shown, you do not need to change the settings.
3.10 Wiring Outputs
The control panel offers the following outputs:
l
Four programmable low-voltage trigger outputs (P on page 34): for arming
LEDs, smoke detector power reset, etc.
Wire the AUX1 +12V to the output device, and then use one of the trigger
terminals 1 to 4 to switch to ground. The outputs will switch to ground when
activated.
Max. current is 50 mA for each trigger.
For outputs that require a known state (logical 0/1), you can customise the
outputs to use a pull-up resistor by fitting jumpers on the outputs.
l
Two relay outputs, 28 VDC, 2.8 A max., resistive loads (N/O on page 34).
Wire the relays between the common C terminal and the normal closed NC
or normal open NO terminals.
48
800-23044 Rev. A draft_11
Installation and Setup Guide
Honeywell MAXPRO Intrusion MPIP2000U/3000U Series
Содержание MAXPRO MPIP2000U Series
Страница 2: ......