# Item
Terminal or
connector
Connect to
L
IB2 BUS
+12V
12 VDC supply terminal
–
0 VDC supply terminal
C
IB2 bus C
D
IB2 bus D
M Request to
exit (RTE),
optional
RTE
To request to exit button
–
To request to exit button [–] terminal.
Default supervision: EOLR (2K). For details and more
options, see
on page 39. Terminate
using resistors if not used.
N EXIT Reader
(Reader 2),
optional
+12V
Exit reader power input [+].
–
Exit reader power input [–]
D0
Exit reader data 0
D1
Exit reader data 1
T
Exit reader tamper.
–
Exit reader tamper [–]
Minimum Connections
The DCM simply needs wiring to the IB2 data bus, and the following minimum
connections:
1. Attach a Wiegand reader to the ENTRY Reader terminals.
2. Attach the door lock to the Door Strike/Lock terminals.
3. Attach a request to exit button to the RTE terminals.
4. Attach a door contact to the DSM terminals.
5. Optionally, you can connect the reader buzzer and red LED control lines
to the appropriate terminals on the DCM to give extra feedback.
Relay Jumper
NC
C
NO
12V
3
2
1
A
3
2
1
B
NC
C
NO
12V
A: jumper in position 2–3 (default). Normal relay operation.
74
800-23044 Rev. A draft_11
Installation and Setup Guide
Honeywell MAXPRO Intrusion MPIP2000U/3000U Series