For example, for R1 = R2 = 1K, the system will go in:
l
Tamper state if the resistance falls below 800 ohms.
l
Ready state if the resistance is between 800 and 1,500 ohms.
l
Alarm state if the resistance is between 1,500 and 12,000 ohms.
l
Tamper state if the resistance is above 12,000 ohms.
Note
l
Resistor tolerance 1% or better.
l
Capable of up to 100 ohms resistance.
3.8.2.3
Triple Balanced
R1
R2
R3
ALARM
N.C.
TROUBLE
N.C.
State at input terminals
Message to the system
Short circuit
Tamper
R1 ohms
Ready
R1 + R2 ohms
Alarm
R1 + R3 ohms
Trouble
R1 + R2 + R3 ohms
Mask condition (trouble when system is
disarmed; alarm when system is armed)
Open circuit
Tamper
Acceptable values for for R1, R2, and R3 are:
l
R1 = 1K
l
R2 = 1K
l
R3 = 3K.
The electrical bands are indicated below:
Ohm
0
Tamper
<
Ready
<
Alarm
<
Trouble
<
Mask
<
Tamper
800
Ω
1,800
Ω
2,500
Ω
4,500
Ω
10,000
Ω