With R1 = R2 = 1K and R3 = 3K, the system will go in:
l
Tamper state if the resistance falls below 800 ohms.
l
Ready state if the resistance is between 800 and 1,800 ohms.
l
Alarm state if the resistance is between 1,800 and 2,500 ohms.
l
Trouble state if the resistance is between 2,500 and 4,500 ohms.
l
Mask condition if the resistance is between 4,500 and 10,000 ohms.
l
Tamper state if the resistance is above 10,000 ohms.
Note
l
You cannot use triple balanced with the control panel's zones 9
and 10.
l
Resistor tolerance 1% or better.
l
Capable of up to 100 ohms resistance.
3.8.3
Using 2-Wire Smoke Detectors on Zone 9 and 10
3.8.3.1
About Zones 9 and 10
By default, zones 9 and 10 are configured as fire zones, using Supervised
EOLR with a 2K resistor. You can change the resistor value if needed; the
supervision type is fixed to Supervised EOLR.
Zones 9 and 10 can each support up to 16 two-wire smoke detectors if you
configure them as fire zones. The zones provide 12 VDC power to the sensors
(10–14.5 VDC).
You can also configure zones 9 and 10 with a security function for use with
standard sensors. In this case, you can use EOLR or double-balanced
supervision.
You cannot use triple-balanced supervision with zones 9 and 10.
Note
The alarm current on zones 9 and 10 supports only one smoke
detector in the alarmed state.