Communications [56]
Galaxy Flex Installer Manual
126
On selecting the SIA format, you are prompted for the required SIA level. There are five
SIA levels available:
0 (default) – Basic event information with 4 digit account number.
1 – as level 0 plus 6 digit accounts.
2 – as level 1 but with event modifiers.
3 – as level 2 but with text descriptions.
4 – as level 3 but allows control commands to be received by the control panel.
SIA Trigger Events [56.1.01.2.level.1]
When you select the option, the first trigger event and its
On/Off
status is displayed (see
Table 10 for a list of available triggers). These are the events and alarms that are transmitted
to the ARC or computer. If the trigger status is set to
On
, an event activation results in
transmission of the event details to the receiver.
The table below shows the list of signalling triggers that are available to the Telecom
module, the USB module, the ISDN module and the Ethernet module.
No.
Trigger Event
No.
Trigger Event
1
PA/Duress
12
Modules/Comms
2
Intruder
13
Elec Status
4
Security
14
Menu Access
5
Custom Zones
15
Trouble
6
Fire
16
Log Zone
7
Set Fault
17
Max Tag
8
Omit
18
Zone Restoral
9
Tamper
19
RF Supervision
10
Setting
20
Fault
11
Reset/Cancel
Table 10 Trigger Events
1=Status
To modify the trigger, select the required trigger type using
A
and
B
and press
ent
. To
program the status to On press
1
, to set it to Off press
0
. Press
ent
to save the programming
and return to the previous menu level.
Programming the SIA Format with Groups Enabled
If groups have been enabled on the system (refer to
Options [63]
) the SIA format option
alters, and an additional level is added.
1=Trigger Events
Press
ent
to display the first trigger event. The keypad shows the trigger, the trigger status
and the groups assigned.
1=Status
As described above.