Страница 1: ...Honeywell Security Galaxy Flex Installer Manual ...
Страница 2: ......
Страница 3: ...15 Wire detectors to zones 16 Zone addressing 16 Zone configuration 17 Detector connection 17 Additional zone configuration information 17 Wire keyswitches 18 Wire terminator buttons 19 Connect outputs 19 Secure tampers 20 Learn wireless detectors 20 Additional programming 20 Users and access templates 22 Additional services 23 Connection to a local computer via USB 23 Connection to a remote servi...
Страница 4: ...ection 4 System programming 31 Setting Options 31 Set using a PIN 31 Cancel setting 32 Unset using a PIN 32 Engineer unsetting 32 Keyswitch setting options 32 Set with cards tags fobs 33 Cancel and reset alarms and alerts 34 Event recording 34 Override faults and tampers 35 Setting features 35 Menu Options 11 19 38 Omit Zones 11 Quick Menu 0 38 Timed Set 12 38 Part Set 13 39 Forced Set 14 39 Chime...
Страница 5: ...Quick Menu 8 59 Trace 44 59 Timer Control 45 60 Group Omit 46 61 Remote Access 47 63 Engineer Access 48 Quick Menu 9 69 Engineer 1 options 70 Parameters 51 70 Program Zones 52 89 Program Outputs 53 102 Links 54 116 Soak 55 118 Communications 56 119 System Print 57 153 Keypad 58 154 Quick Menu 59 157 Engineer 2 158 Diagnostics 61 158 Full Test 62 161 Options 63 162 Assemble Zone 64 166 Timers 65 17...
Страница 6: ...urrent consumption 208 Appendix E Declaration of conformity 209 Compliance and Approvals 209 Appendix F Parts list 211 Appendix G Peripherals 213 MK8 Keypad 213 RF Portal 216 RIO wired zone output expander 219 GSM GPRS module 221 Ethernet module 223 TouchCenter Keypad KeyProx 224 MAX 4 reader 228 Power Supply Unit and Power RIO 232 ISDN module 236 Audio interface module 237 Door control module 240...
Страница 7: ... housed in an ABS plastic housing with swing down lid that is designed for wall mounting The housing can accommodate the following optional modules GSM GPRS module If using GPRS do not fit an Ethernet module RF Portal for use with RF detectors and devices ISDN or Ethernet module in place of the GSM module Figure 1 Flex panel internal layout ...
Страница 8: ...anual 8 System architecture Figure 2 shows the full range of peripheral devices that can be connected to the system via the RS485 data bus or to other specific connection points on the control panel PCB see page 10 Figure 2 System configuration ...
Страница 9: ...50 Flex 100 RS485 Lines 1 1 1 Zones onboard 12 12 12 Zones maximum 20 52 100 Outputs onboard 3 3 3 Outputs maximum 7 23 47 PSU overall 1A 1A 1A PSTN onboard Yes Yes Yes USB port onboard Yes Yes Yes User Codes 23 48 98 Groups 3 4 8 Event Log 500 500 1000 Access Log 500 500 1000 Schedules Timers 2 4 4 GSM GPRS module Optional Optional Optional Ethernet module Optional Optional Optional ISDN module O...
Страница 10: ...PCB layout and connections Galaxy Flex Installer Manual 10 PCB layout and connections Figure 3 shows the control panel PCB layout and detailed connection information Figure 3 PCB layout and connections ...
Страница 11: ...groups Groups are completely independent sub systems and are also known as wards partitions or areas The system can be split into a maximum of 8 groups that can be programmed to operate independently from each other Install the panel and a keypad 1 Mount the panel to the wall using the mounting holes shown allowing 340 mm of free space away from the panel for the lid to swing down 2 Connect at lea...
Страница 12: ...n switch near to the unit to allow disconnection when necessary General Safety The power supply is supplied with a standard plug In the UK if you need to change the fuse in this plug use a 3 A fuse to BS1362 Always refit the plastic fuse carrier when replacing the fuse Units supplied with a European plug do not have a fuse internal to the plug If replacing the plug follow any instructions that are...
Страница 13: ...ecure the cord to the panel with a cable tie 2 DO NOT apply mains power Hard wired option 2 1 Cut the a c power cord 15 cm from the figure 8 connector and discard the part of the cord with the mains plug 2 Connect the remaining cord to the mains terminal block 3 Connect the terminal block to a fused mains outlet and secure the cable to the panel with a cable tie 4 DO NOT apply mains power ...
Страница 14: ...k of explosion if the battery is replaced by an incorrect type Dispose of used batteries according to the instructions 1 Connect the battery as shown Control panel Battery BAT ve terminal BAT ve terminal 2 Connect mains power to the panel Initial programming For instructions on how to use the keypad see Keypad KeyProx operation on page 214 After power is applied wait 1 minute and the keypad displa...
Страница 15: ...and date 41 ent 6 If you are splitting your system into groups enable groups now before performing any other programming 63 ent 1 ent 1 ent 7 Select Auto Detect 72 ent In this mode the system automatically recognises any additional peripheral devices you add to the system Install peripheral devices 1 Before applying power select a valid and unique address on each device The address on most devices...
Страница 16: ...ot connect 12 V terminals between the control panel and remote power supplies However connect the 0 V negatives of all power supplies at a common reference point Wire detectors to zones Note Learning wireless detectors is covered on page 20 Zones are the individual input circuits that are fully programmable using the Zones menu 52 ent This section describes how to change zone default settings how ...
Страница 17: ...hem as SPARE 18 2 If required reprogram zone configurations and the resistance preset values using the Zone Resistance menu 51 ent 46 ent 3 If required customise each zone to a specific preset using the Resistance Select menu 52 ent 9 ent 4 Limit the cable run on each zone to no more than 500 m For presets 11 and 12 limit the cable run to no more than 100 m Detector connection Wire detectors to zo...
Страница 18: ... detectors can be wired into a single zone when using preset 1 as shown in Figure 6 The maximum number of detectors that can be connected to a single zone is ten Figure 6 Zone to multiple detector wiring Wire keyswitches Latching or spring loaded keyswitches can be used to set and unset the panel To program keyswitches refer to Program Zones 52 If the keyswitch latches the transition from 1 kΩ to ...
Страница 19: ...he initialisation routine If the system continues setting push the button again The system will set on the second push This initialisation only occurs on the first setting All subsequent setting routines set on the first push of the terminator The wiring of the terminator and keyswitch zone type is shown in the following figure Figure 7 Terminator and keyswitch zone wiring Connect outputs Outputs ...
Страница 20: ...s If there is already an identical serial number on the system the message zone already allocated is displayed followed by the zone details Either accept the situation and learn the next wireless device from step 5 or delete the serial number from this zone and repeat the learn procedure If the detector is a multi loop device select the 2 Loop No menu option and then enter a loop number 1 6 or 0 f...
Страница 21: ...et Group 10 ent assign zone to a group if enabled Resistance Select 09 ent change pre defined resistance for the selected zone Activity Monitor 08 ent check zone activity RF Options 11 ent access these options Serial No 1 ent manual or self learn entry of wireless device serial number Loop No 2 ent loop number of multiple input wireless devices Supervision 3 ent enable for periodic device supervis...
Страница 22: ...sers and access templates If full time controlled access control is required allocate an access template to every user An access template is a list of groups and time schedules that provides access to multiple areas and at many set times with only one programming step This reduces programming time and complexity The Access Template to be used for each user is chosen within each user s options in t...
Страница 23: ...0 Crveate a new Site in the RSS softare database 11 In the set up for the site select Direct connection and select the USB comm Port 12 Select the Dial option and the Software will connect to the control panel No Settings need to be altered on the control panel Connection to a remote service computer Follow this procedure if you need to connect to a remote service centre 1 Select Remote Access 47 ...
Страница 24: ......
Страница 25: ... for 20 minutes the test will stop automatically 3 To end the test press esc Walk test results To view the results of your walk test select Display Log 22 ent Test outputs Outputs are tested by function for example Bells or Strobe 1 Select Outputs 32 ent 01 Bells is displayed on the keypad 2 Press A or B to move to the output you wish to test or type its number 3 Press ent to test the selected out...
Страница 26: ...add a second zone to the test press A Yes and then follow any further prompts to start the test To end the test Unset the system Program codes Modify PIN 42 ent 1 ent 1 ent change user PIN codes Modify level 42 ent 1 ent 2 ent control the options a user can access Modify name 42 ent 1 ent 3 ent name the user Modify groups 42 ent 1 ent 5 ent control which groups the user can access Card number 42 e...
Страница 27: ...iew or access options for which they are not authorized This includes options in the Quick Menu Note Menu options 51 to 72 Engineer 1 Engineer 2 and Engineer 3 can be assigned additional access to user type 3 to 6 by the engineer To access the menus 1 On a keypad enter your user code 2 Press ent You will now have access to one of the menu structures outlined below If you are using an engineer code...
Страница 28: ... Print 25 Access Doors 31 Walk Test 32 Outputs 41 Time Date 42 Codes 43 Summer 44 Trace 45 Timer Control 46 Group Omit 47 Remote Access 48 Eng Access 51 Parameters 52 Program Zones 53 Program Outputs 54 Links 55 Soak 56 Communication 57 System Print 58 Keypad 59 Quick Menu 61 Diagnostics 62 Full Test 63 Options 64 Assemble Zone 65 Timers 66 Pre Check 67 Remote Reset 68 Menu Access 69 Access Contro...
Страница 29: ...5 minutes to carry out the next step 3 Enter the default engineer code and then press ent After handover the codes should have been changed and you will need to get a manager or other type 6 user to carry out steps 1 and 2 See Engineer Access 48 for more details On accessing engineering mode any group that is set becomes inaccessible Set groups cannot be assigned to zones outputs and any other fun...
Страница 30: ...stem prompts the engineer to press to remove them If the engineer does not remove the missing modules the escape procedure is aborted That there are no power failures on the system such as a failure of the a c or battery Multi user access The system allows a maximum of 4 users to carry out tasks at the same time via separate user interfaces ...
Страница 31: ...to the user Pressing a group number toggles the R ready to an S set flashing If groups are not enabled or your user code does not have group choice the setting procedure starts immediately The exit time countdown is displayed At the end of the exit time or when the setting procedure is terminated by a final or push set zone closing the entry exit horn and keypad buzzers become silent for four seco...
Страница 32: ...status of the remaining groups and prompts for the required groups to be unset To unset the required groups press the relevant number keys the S or P Set or Part Set changes to flashing U and then press ent When the system group is unset three short beeps are emitted to advise you that the system group is unset Engineer unsetting An engineer can only unset a system that was set using the engineer ...
Страница 33: ...ssigned keypad If the card user has no keypad assigned then all keypads in the group assigned to the card user display Press any Key If a key is pressed the keypad containing the key to be pressed shows the card held function If no keys are pressed all keypads in the group s allocated to the card show the held menu function If the card user has group choice all groups available to the user are dis...
Страница 34: ...alid user code assigned to the group that has alarmed Reset levels can be programmed using System 51 6 Tamper Reset 51 7 PA Reset 51 22 Reset Levels 51 65 Note If a tamper alarm has activated zone or module the system cannot be reset until the tamper condition is restored The next time you attempt to set the system if any of the zones that were opened during the previous alarm have not closed sinc...
Страница 35: ... an overridden fault or tamper condition the display indicates the overridden function in place of the set mode by showing the omit message as detailed in the omit menu function The Override condition is logged and will last for one set period only When all the groups that are affected by the override condition become unset the override status is cleared An override restore is logged at unset If d...
Страница 36: ...ng Outputs programmed as Entry Exit Horn begin to pulse rapidly during the last 25 of the programmed exit time System set indication At the end of the exit time the entry exit horns become silent for four seconds This allows the door to be locked and secured and gives the detectors time to settle before the system finally sets Two long tones are emitted to confirm that the system has set If all gr...
Страница 37: ... allow time for the user to abort the remote signalling The Abort Time parameter can also be programmed so that an Intruder alarm is activated when the entry time expires or a zone is activated but entry of any valid code cancels the alarm and deactivates the Intruder outputs without the need for a system reset Abort setting message Zones that are open or opened during the exit period are indicate...
Страница 38: ...ng routine On returning to the banner normal or engineer the keypad displays the message ZONES OMITTED Outputs programmed as Zone Omit mode programmed as reflex are activated as soon as the zone is omitted and remain active until the zone is reinstated Manually reintroduce omitted zones Select the OMIT ZONES option Select the omitted zone to be reinstated and then press to toggle the omit status o...
Страница 39: ...ed by the engineer to perform another function or to start the part setting routine without a code being entered Forced Set 14 Option not available Chime 15 Quick Menu 1 The Chime option allows the user to switch the chime facility on and off Any zones that have the chime attribute enabled refer to Program Zones 52 momentarily operate entry exit horns when opened and two long tones are emitted Ins...
Страница 40: ...ice is offered The groups that are set when this option is selected are set by the keypad group restriction refer to Keypad Groups 58 7 If there is no keypad group restriction then all of the groups assigned to the user are set as long as there is at least one common group assigned to the keypad If there is a group restriction on the setting keypad then only the groups that are common to both the ...
Страница 41: ...out of all the zones Press esc to abort the printout Note A printer must be connected to the panel via a printer interface module Display Log 22 Quick Menu 3 Use this option to view the event log Flex panels can store 1000 events The alarm log uses a FIFO First In First Out method to log and store alarms The control panel differentiates between mandatory and non mandatory events All events are log...
Страница 42: ...roup involved in the event Alarm events reveal the zone descriptor if programmed Walk tested RF zones reveal the measured signal strength of each RF device REM CALL event displays the Remote Station ID for the Remote Servicing Software which has made the connection with the panel Notes 1 Where two identical events occur within 1 second only one is logged 2 Only the first occurrences of high resist...
Страница 43: ...on up to 16 characters of text entered in System Text parameter option 51 15 2 Default Set gives the default settings set up in option 51 17 The number or RF Portals on the system The number of MUX Modules on the system The number of keypads on the system Print 24 Quick Menu 4 Note A serial printer must be connected to the panel via a printer interface module Only information corresponding to the ...
Страница 44: ...ar Access Reader If there are no MAX DCM modules connected to the system the message None Detected is displayed If there is more than one device on the system press A or B to view the details of each device Additional function for MAX reader address display MAX modules unlike other peripherals do no have rotary switches to set their addresses Pressing in this option displays the address on each mo...
Страница 45: ...ed but rejected for some reason DK 422 MAX TAGS Yes Yes Access log information The access log contains one of these reasons for the door not operating Not Grp Match Reject Grp Set Illegal Time The access log also shows user information Press to view the reason for rejection Note MAX or prox readers addresses are different to DCM addresses For example 0013 where 00 not required 1 line number 1 3 ad...
Страница 46: ...M30 MAX Log The Flex 100 system has a 1000 event log for recording MAX activations This log is shared by all readers on the system and operates on a FIFO First In First Out basis when full To display the events in the MAX log select Access Doors 25 select the required MAX address and then press ent The first event that occurred on the selected MAX is displayed along with details of the time date a...
Страница 47: ...rogram Zones 52 Non omittable zones are not included and remain active throughout the test If all zones are non omittable NO ENTRIES is displayed Activate silent test on selected zones 31 2 1 2 Activate audible test on selected zones 31 2 2 2 Use these options to select specific zones to test 1 Navigate to a zone you want to test use A or B or type a zone number 2 Press to toggle the test status t...
Страница 48: ...urn to the walk test press again Note RF zones also record the signal strength in reduced gain mode End the walk test To end the walk test press esc The test ends automatically if no zones are activated for 20 minutes To view the results of the test access the event log refer to Display Log 22 The start of the walk test is indicated by the WALK TEST message Each tested zone is recorded the activat...
Страница 49: ...time must be a valid four digit number in 24 hour format hh mm Your entry if valid is accepted immediately and the selection screen is displayed The date must be a valid 6 digit number in day month and year format dd mm yy Your entry if valid is accepted immediately and the selection screen is displayed Note The time and date can be modified when groups are set Adjusting the clock speed You can va...
Страница 50: ... DCM Rdr 7 Template User Use the Codes option to assign modify and delete the codes that allow users to operate and access the system The Codes option is divided into two sub menus User Codes sub divided into 10 menus that determine all of the access information for users who require PINs depending on panel used and whether the group Option 63 and Acess mode Options 69 options are enabled This opt...
Страница 51: ...Codes 42 1 Details of the first user User 001 are displayed The following typical information is displayed on the keypad no pin assigned pin assigned You can scroll to the specific user or enter a user s number for example 023 or 069 When the required code is displayed press ent to select the modification options 1 Modify PIN is displayed first Scroll to the required option or type an option numbe...
Страница 52: ... When a PIN has been assigned as a dual code two solid boxes are displayed on the top line of the user number details screen Note You can t assign the Master manager code as dual Dual codes operation If you enter a single dual code the message NO ACCESS ADDITIONAL CODE is displayed A second dual code must be entered within 60 seconds of the first dual code to access the menu and set or unset the s...
Страница 53: ... fixed and cannot be assigned to user codes 8 is assigned to the remote code This is fixed and cannot be assigned to the engineer or user codes The remote code can only be used via keypads addressed as E To assign a level to a user 1 Type the level to be assigned 2 Press ent EN50131 1 Level Level Access Availability 1 0 Guard Entered into event memory no other option 2 1 Guard Can only set the sys...
Страница 54: ...t possible to access both menus at the same time To reprogram the options contained in the quick menu refer to Quick Menu 59 Note The master manager code defaults to the full menu To control the menu options available to each user level refer to Menu Access 68 You can allow users to access menu options that their code types are not by default authorized to access Modify Name 42 1 User code 3 Use t...
Страница 55: ...2 and 3 assigns groups 2 and 3 to the user Pressing 1 when group 1 is already assigned removes group 1 from the user code To assign group choice to the user press When the required groups have been assigned to the user press ent to accept the programming and return to the previous menu level Group options Single Group A user can be assigned to any single group In this case type 2 and above users c...
Страница 56: ...ing and return to the previous menu level Notes 1 A card number can be assigned to a user code that does not have a PIN allocated to it All other options assigned to this user are valid for the card fob tag button programmed 2 For access control cards when the serial number is not printed on the card the card number can be learned using the Add Batch 42 2 1 option MAX Function 42 1 User code 7 The...
Страница 57: ...ess This means that it will not open the door without another PIN or card see Codes 42 for programming Template 42 1 User code 9 An Access Template controls the areas to which a user has access and also the access times Once a template is created in Access Template 45 6 it can be assigned to multiple users This eliminates repetitive programming of common door access rights for multiple users If no...
Страница 58: ... Enable 51 60 2 before selecting this option 1 Select 2 Fob PA and then press ent 2 Select 1 Enabled Card Users 42 2 This option determines the tags cards on the system for various users There are seven options Add Batch 42 2 1 Use this option to start enrolment and display the user tag for each presentation When batch enrolling auto assigning of tags to users the panel increments the user number ...
Страница 59: ...urs GMT Note The time always changes with reference to GMT For example Italy which is 1 hour would be Last Sunday in March 02 00 to 03 00 Last Sunday in October 03 00 to 02 00 The start and end dates can be reprogrammed by authorized user codes Press A to modify the start date or press the B key to modify the end date The new date must be a valid four digit number in the day month dd mm format Tra...
Страница 60: ...s displayed Timer Control 45 Timer control menu 45 Timer Control 1 View 1 Weekly Sched 2 Timer Outputs 3 Autoset 2 Holidays 1 Modify Dates 2 Assign Groups 3 Timers Status 0 Off 1 On if Timer Access 51 43 is disabled 1 Name if Timer Access 51 43 is enabled 2 Status 0 Off 1 On 3 Events 4 Hol Period 5 Hol Sched 6 Pattern Day 4 Late Work 5 Weekend Work 6 Acc Template View Weekly Schedule 45 1 1 Use th...
Страница 61: ...onal extensions can be authorized by entry of a valid code during the subsequent autoset pre warning periods Weekend Work 45 5 The Weekend Work option allows a valid user code to authorize the system to unset at the weekend Access Template 45 6 An access template defines when and where a user is allowed access For each access template a schedule is given to each group area to define when access to...
Страница 62: ... 1 The type 6 user must have group choice to enter Group Omit 2 The zones in the selected groups are omitted from the system as soon as the group is selected and ZONES OMITTED is displayed Omitted zones remain omitted for one set period only or until they are manually reinstated to the system Outputs programmed as Zone Omit mode programmed as reflex are activated as soon as the zone is omitted and...
Страница 63: ...to 5 Call back 5 2 Ethernet GPRS 0 Direct Access 1 Call back 1 to 5 Call back 5 3 GSM 0 Direct Access 1 Call back 1 to 5 Call back 5 4 Auto service 1 Mode 0 Off 1 Timed 2 Instant 3 Confirm 2 Timers 1 Start Time 2 End Time 3 Sync Schedule 000 0 365 days 4 Schedule Reset 0 Off 1 Auto Reset 2 Manual Reset 3 Terminate Idle Idle Time 10 0 60 mins 4 Conn Retry 1 Retry Interval 30 0 60 mins 2 Retry Durat...
Страница 64: ...7 1 Use this option to control the access mode of the remote servicing package You need type 6 status to use this option INT Telecoms 47 1 0 Use this option to select the onboard telecoms as the communication device INT Telecoms Direct Access 47 1 0 0 ISDN Direct Access 47 1 1 0 Ethernet Direct Access 47 1 2 0 GSM Direct Access 47 1 3 0 When you select one of these options a 40 minute remote acces...
Страница 65: ... activate an automatic periodic upload On a predetermined schedule activate an automatic remote routine inspection Note The Auto Service function works for both the Internal Telecoms and the Ethernet module Use the following sub options to select the mode of the automatic communication in each of the three situations Auto Service Mode Off 47 4 1 0 In this mode the panel will not automatically init...
Страница 66: ...latest panel programming during the off peak window The period of time between connections can be set from 0 to 365 days The default setting is 0 which disables the option The off peak time window is programmed in menus 47 4 2 1 and 47 4 2 2 Auto Service Timers Schedule Reset Off 47 4 2 4 0 The panel never initiates a remote servicing connection This is the default setting Auto Service Timers Sche...
Страница 67: ...s a connection when engineer or user programming has been modified Remote Maint 47 4 6 Use this option to control the mode for automatically initiating communications for remote routine inspection and maintenance The panel uploads only the most recent information available from Diagnostics 61 No other panel programming is uploaded There are two sub options that control this Remote Maintenance Sche...
Страница 68: ...sent to the panel via the Send Remote Access Start Code The Service PIN code cannot be the same as any other user codes in the system This option is only available when the Schedule 47 4 6 1 option is greater than 0 and when the Code Only 47 4 6 2 1 option is enabled Delay Time 47 4 9 This is the time that the panel delays for incoming information from the remote servicing package The delay time c...
Страница 69: ... and hold esc to return to the banner This provides a five minute period during which the engineer can access engineering mode without causing a tamper alarm Once in engineering mode there is no time limit on the access period User authorization is limited to one visit only When you return the system to user mode the authorization is still valid for five minutes After this time it must be granted ...
Страница 70: ...se the values assigned to the parameter Press ent to accept a new value and return to the previous menu level Any parameters that differ from this procedure are indicated in the following paragraphs Assigning Parameters to Groups Some parameters allow separate values to be assigned to system groups If groups have been enabled the relevant parameters prompt for a group to be selected When selected ...
Страница 71: ...ot available 14 KEY SW Level not available 61 Activity Mon not available 15 System Text not available 62 Lockout not available 16 Soak Time not available 63 Banner alerts not available 17 Restart not available 64 Set Override not available 18 Stop Set not available 65 Reset Levels not available 19 Part Alarm 66 Min Pin Size not available 20 Power Delay 68 Line Fail not available 21 Reset Mgr not a...
Страница 72: ...ime 51 03 The abort function delays the activation of a full intruder alarm condition following an entry alarm This parameter has 2 sub options Abort Time 51 03 1 Range 0 to 300 seconds You can assign a different value to each group The abort time is initiated Whenever a zone that is not on the entry route Final Entry and Exit zones is activated for example when a user strays from the entry route ...
Страница 73: ...g the entry time or abort time no alarm condition is signalled Adding alters the standard operation so that if a user strays from the entry route within the entry time the intruder is signalled as soon as the entry deviation occurs Notes 1 To comply with PD6662 2010 the abort operation must be used with Abort Time set to 30 seconds 2 To comply with EN50131 2004 and DD243 2004 the abort operation m...
Страница 74: ...ect the user type that can reset the system following an intruder alarm A remote code can also change this option The default type is 3 and the range is 3 to 5 for the user 6 for the manager 7 for the engineer You can assign a different value to each group Note This option is affected by Reduced Resets 51 55 3 The panel only requests Engineer Level Reset if alarms have been signalled via the Commu...
Страница 75: ... This option determines if activated zones can be omitted at re arm as described above 0 Disabled 1 Omit All Omits any omittable zones that are open at re arm The complete zone circuit including tamper is omitted 2 Force As Omit All but omits zones whether omittable or not Refer to Program Zones 52 for details on enabling the zone omit attribute Key 0 51 10 Key 0 on the keypad can be assigned to o...
Страница 76: ...epts the programming and returns to the previous level The banner is displayed when the system is in the normal mode set unset PA Delay 51 13 Use this option to set the delay between the activation of a PA Delay or PA Delay Silent zone and the alarm sounding and signalling a PA via the communicator The default is 60 seconds and the range is 1 to 60 seconds You can assign a different value to each ...
Страница 77: ...ings before programming in Soak 55 Restart 51 17 1 Use this option to re configure the system without the need to remove and reconnect the power The system displays WARNING ent RESET SYSTEM Press ent to reconfigure the system The keypad display becomes blank for a few seconds then displays the message Configuring Please Wait When configuration is complete the banner returns to the normal display d...
Страница 78: ... setting Part Alarm 51 19 Use this parameter to enable the Bells and Strobe outputs to activate if an alarm condition occurs when the system is part set Select 1 to enable and 0 the disable Note The Horn Entry Exit and Intruder outputs are not affected by this parameter You can assign a different value to each group Power Delay 51 20 Use this parameter to delay activation of the AC Fail signal fol...
Страница 79: ...Alarm parameter is enabled any zone that is open when the Autoset begins at the end of the pre warning period causes an immediate full alarm condition to be activated If the Exit Alarm parameter is disabled any zone open when the Autoset begins at the end of the pre warning period results in an urgent bleeping from the entry exit horns If the open zones are not closed by the end the time assigned ...
Страница 80: ...t on the period between activations The Video parameter is programmable within the range 1 to 9 activations and the default value is 2 The video output occurs on every activation but a full alarm does not occur until the programmed number of activations is reached The Video zones activation counter is reset when the system is unset Note The activations of the Video zones are cumulative the counter...
Страница 81: ...ow for the setting period to expire You can assign a different value to each group Weekend Work 51 41 Use this parameter to enable or disable the Weekend Work 45 5 option If the parameter is set to 0 disabled default setting the message Option not available is displayed on selecting Weekend Work 45 5 Timer Access 51 43 If enabled a type 6 user can change all the Weekly Schedule information name st...
Страница 82: ...1800 0 3700 0 1400 0 2600 0 800 Low Res 800 900 1800 2000 3700 4200 1400 2800 2600 3000 800 900 Normal 900 1200 2000 2500 4200 5500 2800 8400 3000 4000 900 1200 1200 infinity High Res 1200 1300 2500 2700 5500 6500 8400 9800 4000 4400 1200 1300 Fault 1300 4500 Masked 1300 19000 2700 19000 6500 22000 9800 25000 4400 19000 4500 19000 Open 19000 infinity 19000 infinity 22000 infinity 25000 infinity 19...
Страница 83: ...ete set period with a default of 30 minutes Keypad Access 51 54 Use this option to select how the keypad unsets the system There are two options 1 Always Keypad always unset the system 2 Except Entry Except when entry time is running This ensures that users are unsetting using a fob or MAX tag portable device Confirm Operation 51 55 1 Use this option to control when confirmed alarms can be trigger...
Страница 84: ...eset 51 57 Not used Power Alarm 51 58 Enable this parameter to allow the Bells Strobe and Horn outputs to activate when there is an a c failure and the system is set The default is 0 Part Tone 51 59 Enable this parameter to change the setting tone for a part set The new tone is on for 2 seconds and off for 0 1 seconds RF Address 51 60 1 Use this option to specify the number of virtual RIO addresse...
Страница 85: ...0 7 This option controls whether and how an RF fault prevents the panel from being set There are three options 0 Disabled An RF fault will not prevent setting 1 Warning If there is a failure the user will get a warning but can continue to set 2 Auto Check If there is a failure the system cannot be set until the zone s have been activated Activity Mon 51 61 Use this option to check zone activity If...
Страница 86: ...anner Alerts 51 63 Use this option to program whether system alerts are displayed on the keypad banner If enabled system events are indicated on the display The default setting is disabled Set Override 51 64 Use this option to change the type of user that can override specific fault events to set the system A different value can be programmed for each group Reset levels 51 65 This parameter determ...
Страница 87: ...A event if the battery is low and there is a mains power failure When the event is sent the Power Delay time set in parameter 51 20 stops immediately Max Alm Cause 51 72 Use this option to define the range of valid cause codes agreed with the Alarm Receiving Centre When this function is enabled a cause code must be entered by the user to perform a system reset To disable set the alarm cause code t...
Страница 88: ...he default is 90 seconds and the range is 0 to 300 seconds MAX LEDs off 51 76 0 Disabled LEDs are on regardless of group set state 1 Enabled Turns the MAX LEDs off in the set state on a MAX4 LED 1 remains on in the Set state Duress User 51 77 Use this option to allow duress to be added to a user s attributes 0 Disabled 1 Enabled ...
Страница 89: ...em enabled 6 TimeResp Modify circuit debounce time 7 Custom SIA Select SIA event 8 Activity Mon Selects criteria for zone activity checking 9 SelectRes Selects resistance range for zone 10 Group Assign zone to a single group on the system 11 RF options Setup learn and test RF devices 12 Zone Restoral Send the restoral event of a zone to the ARC 13 Audio Channel Allocate a zone to an audio channel ...
Страница 90: ...urrent descriptor blank by default is displayed on the top line and an underscore shows where the next character will be positioned A selection of the alphabet is shown on the bottom line and the cursor flashes on the letter L Press to erase the characters already assigned to the descriptor Use A or B to move the alphabet left or right until the required character is positioned underneath the flas...
Страница 91: ...5 Part Disable the Part attribute to ensure the zone is excluded from the setting procedure when the part setting options is used to set the system 13 PART SET The Part attribute defaults to 1 enabled for all zone functions except zones programmed as 09 Keyswitch Use A or B to toggle the status of the Part attribute and then press ent to accept the programming 6 Resp Time This function is only app...
Страница 92: ...R Assist Emergency Alarm Emergency Restoral QA QR QB QU QT QJ BX TA 13 RO C Relay Relay Open Relay Closed RO RC BB BU BT BJ BX TA 14 SA R Sprinklr Sprinkler Alarm Sprinkler Restoral SA SR SB SU ST SJ BX TA 15 TA R Tamper Tamper Alarm Tamper Restoral TA TR TB TU BT BJ TX TA 16 WA R Water Water Alarm Water Restoral WA WR WB WU WT WJ BX TA 17 YT R Battery Battery Alarm Battery Restoral YT YR BB BU BT...
Страница 93: ...nes If the star group feature is assigned a zone programmed as Final Secure Final Part Final or Push Set then closing the zone when setting multiple groups terminates the setting procedure for all groups assigned to the zone Refer to the zone functions for further information on the operation of this feature Exit Zones The star group feature can be assigned to a zone programmed as Exit This allows...
Страница 94: ...he 2 Loop No option is displayed Enter the loop number Note If the RF device does not learn remove the battery short circuit the battery terminals replace the battery and repeat the above procedure 2 Loop No If the wireless device has multiple inputs loops use this option to enter a loop number from 1 to 6 or 0 if it is a single input device 3 Supervision Provides periodic supervision 0 Disabled o...
Страница 95: ...amming a Final zone doubles the entry time of the group Opening a Final zone during the exit time is reported on the keypad as an open zone the entry exit horns bleep rapidly to indicate that the zone is open Note The termination feature of a Final zone can be extended to terminate the setting of multiple groups by pressing when assigning a group to the zone Refer to the Star Group Function 02 Exi...
Страница 96: ... conjunction with a Push Set zone which acts as the exit terminator for the setting procedure Pressing when programming an Entry zone doubles the entry time of the group Opening an Entry zone during the exit time is reported on the keypad as an open zone and the entry exit horns bleep rapidly to indicate that the zone is open 08 Push Set This zone function is used to terminate the setting routine ...
Страница 97: ...system is set operating a Keyswitch immediately unsets the assigned groups and there is no entry time countdown The Part attribute of the Keyswitch function defaults to 0 disabled and the standard Keyswitch function full sets the system To part set the system using the Keyswitch enable the Part attribute Note The operation of a Keyswitch zone can be extended to the setting and unsetting of multipl...
Страница 98: ...ctionality When the system is full set operation is identical to the Exit zone function When the system is part set operation is identical to the Entry zone function Pressing when programming a Part Entry zone doubles the entry time of the group 13 PA The PA Personal Attack function is continuously operational Activation of this zone type overrides the Bell Delay parameter and causes an instant fu...
Страница 99: ...ows any unused zones to be ignored The resistance readings from the circuit including the tamper conditions do not activate an alarm condition Note We recommend that all unused zones are programmed as Spare and that a 1 kΩ 1 resistor is connected across each of these zones 19 Fire The Fire function is continuously operational When activated a Fire zone overrides the Bell Delay parameter and activa...
Страница 100: ...ystem setting if the Line Fail is active by enabling the Stop Set parameter option 51 18 25 AC Fail This function is used to monitor a remote power supply In the event of a power failure the AC Fail zone is activated the activation and de activation of the zone is recorded in the event log 26 Log This zone type has no operational function It is designed to record the activation of a zone in both t...
Страница 101: ...espectively This function is designed to permit a remote signal for example REDCare s Return Path Signalling feature to reset the system following an alarm condition 40 Bell Fail This zone type is for bells that have diagnostic capabilities and failure outputs If activated it causes fault for any bell failure condition 41 Intr Low This zone type assigns a low priority to a zone in the event of an ...
Страница 102: ...if the Group option is enabled refer to Groups 63 1 Table 6 Output Attributes Selecting Outputs RIO Outputs When you enter the option the first output on the system is displayed with the output address and function on the top line and the polarity and assigned groups on the bottom line Use A or B to scroll through the outputs or enter the address of a specific output Press ent to programme an outp...
Страница 103: ...ever the output mode of each function can be modified to meet special requirements when reprogrammed the new mode applies to all outputs assigned to that function The output modes are 1 Latch the output remains active until a valid code is entered 2 Reflex the output follows the activity of the triggering event for example the Set output follows the setting and unsetting of the group 3 Pulse the o...
Страница 104: ... than one group All outputs default to all groups on the system When you select the attribute the groups that the output is currently assigned to are displayed Press the relevant number keys to toggle the status of the group and press ent If the group number is displayed on the top line the group is assigned to the output If a dash is displayed in place of the group number the group has been remov...
Страница 105: ...e the status of the groups and then press ent to accept the programming The available group status conditions are S Set group must be set to allow output to activate U Unset group must be unset to allow output to activate Set or unset output activation is independent of the group status ...
Страница 106: ...t A T A 15 PA Delay A A A T A 16 PA Delay Silent A T A 18 Spare T 19 Fire A A T 20 Tamper S S S A A 22 Beam Pair S S S T A 23 Battery Low T U 24 Line Fail T 25 AC Fail T A 26 Log T A 28 Video S S S T A 29 Video Exit S S S T A 32 Set Log T 33 Custom A T 34 Custom B T 39 Keyswitch Reset T X 40 Bell fail 41 Intr Low S S S T A 42 Intr High S S S T A 43 PSU Fault T 44 Fault T Key S Activates when syste...
Страница 107: ... Fire A A A V A A 20 Tamper A A S S 22 Beam Pair S SXE S S 23 Battery Low 24 Line Fail U A 25 AC Fail 26 Log 28 Video S SXE S S S 29 Video Exit S SXE S S S 32 Set Log 33 Custom A 34 Custom B 39 Keyswitch Reset 40 Bell fail 41 Intr Low S SXE S S S 42 Intr High S SXE S S S 43 PSU Fault 44 Fault Key S Activates when system is Set Activation dependant on system programming P Activates when system is P...
Страница 108: ...pare 19 Fire O A 20 Tamper O A 22 Beam Pair O 23 Battery Low O 24 Line Fail O 25 AC Fail O 26 Log O 28 Video O S 29 Video Exit O S 32 Set Log O 33 Custom A O 34 Custom B O 39 Keyswitch Reset O 40 Bell Fail 41 Intr Low O S 42 Intr High O S 43 PSU Fault O 44 Fault O Key S Activates when system is Set Activation dependant on system programming P Activates when system is Part Set X Activates during Ex...
Страница 109: ... A 24 Line Fail A 25 AC Fail A 26 Log 28 Video 29 Video Exit 32 Set Log 33 Custom A 34 Custom B 39 Keyswitch Reset 40 Bell Fail A A 41 Intr Low 42 Intr High 43 PSU Fault A 44 Fault A Key S Activates when system is Set Activation dependant on system programming P Activates when system is Part Set X Activates during Exit Time U Unset E Activates during Entry Time A Activated in any condition L Switc...
Страница 110: ...is activated whenever a circuit tamper or lid tamper occurs The output is not subject to the Re arm parameter It latches on and remains active until a valid code with the appropriate Tamper Reset level is entered The output is also activated on the first entry of the engineer code when accessing engineer mode Note The Tamper output is not activated when engineer access is authorized by the user 07...
Страница 111: ...ed subject to the time entered in 20 Power Delay 15 Battery Low Reflex This output activates whenever the control unit stand by battery falls below 10 5 V or a Battery Low zone is activated It is restored when the voltage rises above 10 5 V or the Battery Low zone is closed 16 Fire Latch This output is activated whenever a Fire zone is activated The output is not subject to the Re arm parameter It...
Страница 112: ...ssigned to the Confirm output to allow activation Cross group confirmation is controlled by the Communications programming in Internal Telecoms 56 1 or GSM 56 5 If signalling is by DTMF format cross group confirmation occurs on groups that share the same confirm channel In all other signalling formats cross group confirmation occurs on groups that share the same account number Note The Confirm out...
Страница 113: ...h the programmed on and off times assigned to the function Note If the Timer A or B outputs are programmed as Latch mode then they can only be reset by a user code with access to all of the groups assigned to the relevant timer 32 Zone Omit This output is activated by 11 OMIT ZONES or by 54 LINKS as soon as a zone is omitted from the system If the Output Mode attribute is assigned as Reflex defaul...
Страница 114: ...the system has been unset before the programmed Monitor time refer to Status 65 3 1 48 Prewarn Reflex This output is active during the programmed pre warning period of the autoset function The mode is Reflex The Prewarn emits a constant tone if the auto setting of the system can be extended If an extension is not possible Prewarn outputs pulses 49 Autoset Reflex This output is activated when the s...
Страница 115: ...resent on the panel and clears when all the fault conditions have cleared The following fault types activate the fault output Line Fail any module ARC Comms Fail any module RF Jam RF Low Battery RF Supervision Failure Bell Fail from a bell fail zone AC Fail panel AC zone or power supply Battery Fail panel battery zone or power supply Mask SMS signalling faults will not activate the fault outputs 7...
Страница 116: ...ress A or B to select the actual link source for example the zone address or the user code number 3 If the source is required to toggle the destination on and off press The source is prefixed by a on the display Note The link destination is activated by the first operation of the source and then deactivated by the second operation 4 Press ent The source of the link is assigned and the keypad promp...
Страница 117: ...ard the link activates momentarily only This option is only practical to trigger a destination event for example an output pulse On 01 When the MAX is swiped with a card the link is activated When the MAX is swiped a second time the link deactivates f Weekly Schedule On WK01 On time activates the link Off time deactivates the link Off WK01 The first on time activates the link The next on time deac...
Страница 118: ...ivation on any of the selected zones The Soak Time starts when the first zone is put onto soak test Subsequent additions are only tested for the period remaining in the Soak Time Activation of an Exit or Video Exit zone during the Entry Time does not reset the soak test and period To program Soak Zones When you select the Soak option the address and function of the first zone on the system is disp...
Страница 119: ...mm 1 Use this option to program the onboard telecom module for alarm signalling and remote servicing over the PSTN 3 ISDN Comm 3 Use this option to program the ISDN module for alarm signalling and remote servicing over ISDN B and D channels 4 Ethernet or GPRS Comm 4 Use this option to program the Ethernet module for alarm signalling and remote servicing over an Ethernet LAN WAN using both TCP IP a...
Страница 120: ...riptor not available 6 Control not available 7 Output Groups 2 Acct Channel 2 SIA 0 0 4 1 Trigger Events 1 Status 2 Groups 2 Group Settings 1 Telephone No 2 Account No 3 Microtech 1 Trigger Events 1 Status 2 Groups 2 Group Settings 1 Telephone No 2 Account No 4 Contact ID 1 Trigger Events 1 Status 2 Groups 2 Ack Timeout 1 30 seconds 2 60 seconds 3 Group Settings 1 Telephone No 2 Account No Continu...
Страница 121: ...Autotest 1 Start Time 2 Intervals 0 99 hours 3 Int Test 0 Disabled 1 Enabled 08 Engineer Test 09 No of Rings 10 1 20 10 Line Fail 1 Line Volts 0 Disabled 1 Enabled 2 Dial Tone 0 Disabled 1 Enabled 3 Incoming Call 0 Disabled 1 Enabled 11 Fail to Comm 1 60 2 120 3 180 4 240 5 300 12 Remote Access 1 Access Period 1 Off 2 All Unset 3 Any Set 4 Any Time 2 Mode 1 Direct Access 2 Manager Authorize 3 Call...
Страница 122: ...o 3 2 Centre No 3 Format 1 TAP 1 Status 2 Groups 1 Status 2 Groups 2 UCP SMS 1 Status 2 Groups 1 Status 2 Groups 3 UCP Minicall 1 Status 2 Groups 1 Status 2 Groups 4 UCP Numeric 1 Status 2 Groups 1 Status 2 Groups 4 Site ID 5 Password 18 No Tel 3 Int Telecoms Format 56 1 01 The Telecom module provides four signalling formats DTMF SIA Microtech Contact ID Select a format and program the alarm and e...
Страница 123: ...the first channel are displayed Select the required channel or enter the channel number directly DTMF Channels 1 16 56 1 01 1 1 Each channel can be programmed with the following attributes 1 Output Function 2 Output Mode 3 Output Polarity 4 Diag Recording option not available 5 Descriptor option not available 6 Control option not available 7 Output Groups DTMF Channel Output Function 56 1 01 1 1 1...
Страница 124: ...etting of the group 3 Pulse the output remains active for the programmed pulse time 1 to 3000 seconds To program the Output Mode 1 Select the required mode 2 Press ent to accept the programming 3 If assigning the Pulse output mode enter the pulse time and then press ent Note The Output Mode status determines the operation of the channel restore Press to modify the status when the channel details a...
Страница 125: ...ng the groups An arrow is displayed on the bottom line with the current status Press the relevant number keys to toggle the status of the groups and then press ent to accept the programming The available group status conditions are S Set group must be set to allow channel to activate U Unset group must be unset to allow channel to activate Set or unset channel activation is independent of the grou...
Страница 126: ...w shows the list of signalling triggers that are available to the Telecom module the USB module the ISDN module and the Ethernet module No Trigger Event No Trigger Event 1 PA Duress 12 Modules Comms 2 Intruder 13 Elec Status 4 Security 14 Menu Access 5 Custom Zones 15 Trouble 6 Fire 16 Log Zone 7 Set Fault 17 Max Tag 8 Omit 18 Zone Restoral 9 Tamper 19 RF Supervision 10 Setting 20 Fault 11 Reset C...
Страница 127: ...played if groups have been enabled refer to Options 63 Event triggers are signalled with the account number to the telephone number programmed in the Account Number 56 1 03 and Telephone Number 1 56 1 02 options However each group can be assigned a separate account number and programmed to transmit event details to a unique telephone number Select the required group and then press ent SIA Group Se...
Страница 128: ...seconds before dialling the next digit Multiple entries can be made for example entering gives a six second pause Dial tone detect wait for new dial tone Each dial tone detect lasts for 15 seconds Multiple entries can be made for example entering gives a 30 second dial tone detect If a new dial tone is not detected in this time then the dialling attempt is aborted This is counted as a fail to comm...
Страница 129: ...ed in the Intervals option 2 Intervals Sets the period between engineer test transmissions following the Start Time The range is 0 to 99 hours Notes 1 If the Test Interval is 0 default the Autotest is disabled even if a Start Time has been assigned 2 To disable Autotest enter 00 00 default no transmissions of test signals can be sent at midnight 3 Intelligent Test Stops the transmission of an auto...
Страница 130: ...is restored within this period no event is stored If an attempt is made to set the system or part of the system within this period the message ALERT LINE FAIL 1 ENT CONTINUE SET is displayed If ent is pressed the set continues if esc is pressed a line fail is logged immediately If the system is unset the COMM LINE FAIL message is displayed on the keypad display and a local alarm is sounded The key...
Страница 131: ... transmission must be made to both telephone numbers Remote Access Period 56 1 12 1 Use this option to control how the remote site is accessed by the Remote operator There are four modes 1 Off Remote Servicing access to the panel is disabled 2 All Unset Access only when all the groups are unset If groups are not enabled access is available at any time 3 Any Set Remote Servicing access will only be...
Страница 132: ...y made If a new alarm event occurs while the system is transmitting in the Alarm Monitoring mode the transmission is terminated and the alarms are sent to the ARC using the primary format selected The menu structure and programming of the Alarm Monitoring options are identical to the SIA format Refer to SIA 56 1 01 2 SMS 56 1 17 Use this option to generate and transmit SMS text messages in respons...
Страница 133: ...vailable to support alternate dialling to a third destination receiver The programming is identical to Telephone No 1 56 1 02 The No TEL 3 option can also be used as a primary destination receiver for audio events when option 56 7 1 is set to No TEL 3 irrespective of the receiver mode 56 2 Not used ...
Страница 134: ...Rate 1 None 2 90 secs 3 15 mins 4 60 mins 5 Programmable 0 999 minutes 5 CUG Index 4 RAM not available 4 Format 1 DTMF 2 SIA 3 Microtech 4 Contact ID 5 Robofon 6 X 25 Protocol 1 7 X 25 Protocol 2 02 Secondary 1 Default Tel No 2 Default Acc No 3 Dial Type 4 Format 5 Copy Primary 6 Alternate 1 Disable 2 Enable 03 ISDN Type 1 Point to Multipoint 2 Point to Point Continued on next page ...
Страница 135: ...1 Start Time 2 Intervals 0 99 hours 3 Int Test 0 Disabled 1 Enabled 4 Group Condition 06 Engineer Test 07 Line Fail 1 None 2 Line Vols Only 3 Layer 1 Only 4 Volts and Layer 1 5 Volts or Layer 1 08 Fail to Comm 09 Remote Access 1 Access Time 1 Off 2 All Unset 3 Any Set 4 Any Time 2 Mode 1 Direct Access 2 Manager Authorize 3 Call Back 10 Alarm Monitoring 1 Trigger 1 20 2 Phone Number 3 Account Numbe...
Страница 136: ...he telecom provider Values can be 00 to 63 2 LCGN Logical Channel Group Number 3 LCN Logical Channel Number The X 25 data network uses the LCGN and LCN to identify the users that are connected Normally users are connected directly to the X 25 network To allow for a high number of users the LCN can be set from 000 to 255 The LCGN can multiply this number of users by 15 The LCGN can vary from 00 to ...
Страница 137: ... values programmed for the primary number 1 Default Telephone Number The programming is identical to Telephone Number 1 56 1 02 2 Default Account Number Refer to Primary 56 3 01 2 3 Dial Type Refer to Primary Dial Type except X 25 should be option not available 4 Format Refer to Primary Format It is possible to assign different formats to both the Primary and Secondary numbers however when using t...
Страница 138: ...functionality of the PABX and the ISDN module always connect the PABX to the ISDN out ports The phone numbers that are available on a Point to Point line often only vary in the last 2 digits e g 123401 123409 To handle incoming calls from Remote Servicing one phone number need to programmed into the ISDN module This specific phone number cannot be used by the PABX because the ISDN module will seiz...
Страница 139: ...y 40 seconds and monitors the activation response from the ISDN network This activation remains for about 20 seconds When X 25 is used the layer 1 check is not performed because the ISDN line is already activated continuously The module can be configured using these options 1 None No line monitoring 2 Line Volts D C volts monitored only 3 Layer 1 Layer 1 monitored only 4 Volts and Layer 1 Volts an...
Страница 140: ...ansmitted are erased from the buffer Remote Access 56 3 09 See Remote Access 56 1 12 for details Alarm Monitoring 56 3 10 Use this option to allow events to be dialled to a computer with Alarm Monitoring software Alarm events information is only transmitted when all of the alarms have been sent to the ARC or all communication attempts have been unsuccessfully made If a new alarm event occurs while...
Страница 141: ...econdary IP 1 IP Address 2 Port No 4 Account No 5 Receiver 1 Single 2 Dual 6 Alarm Mon 1 Trigger 1 Status 2 Groups 2 Account No 3 IP Address 4 Port No 7 Heartbeat 1 Interval 8 Protocol 0 UDP 1 TCP 03 Remote Access 1 Access Period 1 Off 2 All Unset 3 Any Set 4 Any Time 2 Mode 1 Direct Access 2 Manager Authorize 1 Call Back IP1 1 IP Address 2 Port No 2 Call Back IP2 1 IP Address 2 Port No 3 Call Bac...
Страница 142: ... remote servicing including data encryption and path supervision between the module and alarm receiving applications Note Use the programming functions in this section if you plan to transmit data with the GPRS element of the module Module Config 56 4 01 Each Ethernet module is pre programmed with a unique MAC address that identifies it on the network However to communicate with other applications...
Страница 143: ...able of transmitting the panel events indicated in Appendix B Refer to Appendix C for the detailed breakdown of the SIA event structure for each level On selecting the SIA format you are prompted for the required SIA level 0 default basic event information with 4 digit account numbers 1 as level 0 plus 6 digit account numbers 2 as level 1 but with event modifiers 3 as level 2 but with text descrip...
Страница 144: ... of the following options 1 Account No By default the account number programmed in option 56 4 02 4 is displayed Erase the old number enter a new number 4 to 6 digits and then press ent 2 IP Address By default the IP address programmed in option 56 4 02 2 1 is displayed Erase the old address enter a new address and then press ent 3 Port No By default the port number programmed in option 56 4 02 2 ...
Страница 145: ...er you enter in this field is automatically copied to all groups Alarm Reporting Receiver 56 4 02 5 Use this option to select the paths used for alarm signalling 1 Single If this option is selected and a Secondary IP is programmed the Secondary IP destination is used in the event of a failure to the Primary IP A Fail to Comm is logged against the Primary alarm transmission path 2 Dual If this opti...
Страница 146: ...not received within the programmed interval a line fail condition is activated The Line Fail event indicates which path has failed Primary Secondary or Alarm Monitoring Alarm Reporting Protocol 56 4 02 8 The Ethernet module can signal using either TCP Transmission Control Protocol or UDP Universal Datagram Protocol 0 UDP and 1 TCP If communicating with V3 26 Alarm Monitoring or V6 26 Remote Servic...
Страница 147: ... the Call back IP addresses programmed into the system 1 Call Back IP 1 5 There are 5 possible IP address Port number destinations that can be programmed allowing communication with up to five different Remote Servicing locations 1 IP Address Enter the IP address of the PC running the Remote Servicing application 2 Port No Enter the port number allocated to Remote Servicing on the PC default is 10...
Страница 148: ... 68 delay period the line fail will immediately be logged and indicated Line Fail Network 56 4 07 1 Use this option to monitor the connection between the Ethernet module and the local network 0 OFF and 1 Available When set to 1 Available a Line Fail event is activated if the Ethernet module is disconnected from the network or the local network is not available at the panel Line Fail Signal Path 56...
Страница 149: ...he Ethernet module and remote computer using the SIA control command protocol 4 Alarm Mon Controls encryption for the Alarm Monitoring alarm transmission paths GPRS Network 56 4 10 To enable GPRS operation you need to setup Format 56 4 02 1 Primary IP 56 4 02 2 and Account No 56 4 02 4 as well as the following options 1 APN The Access Point Name for the GPRS provider a maximum of 30 characters 2 L...
Страница 150: ...t 56 1 01 2 Microtech Format 56 6 1 2 For details see Int Telecom Microtech Format 56 1 01 3 Account No 56 6 2 This is the site identifier Enter a unique account number 6 digits maximum Audio 56 7 Use this option to setup Audio Transmission to allow audio verification of an alarm Each system zone can be assigned one audio channel each with a maximum of three microphones Following an alarm transmis...
Страница 151: ...rd sound in the event of an alarm 1 Path PSTN This option selects PSTN as the communication line between the panel and ARC when set to 1 Enabled 2 Audio Channels This option controls the audio channels status It can be enabled or disabled The channel is in a four digit format For example Channel 9024 9 Line number fixed 0 Audio Interface number fixed 2 Mux Module number 4 Audio channel Press ent t...
Страница 152: ...laxy Flex Installer Manual 152 Pre Listen Time The alarm delay listen time can be set from 0 to 10 seconds Setting the time to 5 seconds default means that 5 seconds of pre alarm and 5 seconds of post alarm audio is saved ...
Страница 153: ...tions 01 to 12 When printing option 12 EVENT LOG the system prompts for Groups to be selected The print shows only those events logged for the groups selected To abort the print at any time press esc Note Connect a printer before selecting the print option If the printer is off line or is not connected the PRINTER off line ESC to abort message is displayed Press esc and correct the problem Printin...
Страница 154: ...ed 1 WITH CODE A key requires code to be entered prior to operation 2 NO CODE A key is a single touch operation no code is required Select the required Code Status and then press ent Note The Code Status assigned to the key is displayed when selecting the keypad address for example A 12 which indicates that the A key does not require a user code Menu Option To assign one of the options to the A ke...
Страница 155: ...ystem is unset Off when the system is set On when keys are pressed 3 On during setting and unsetting On when keys are pressed Off after keypad timeout and menu exit 4 On when keys are pressed Off after keypad timeout and menu exit Keypad Mute 58 5 Use this option to improve security and reduce tampering with the keypad when it is located in a public place 0 Off default 1 On The keypad remains sile...
Страница 156: ...group allows access to all of the user s groups The user is not restricted by the groups that are assigned to the keypad as long as there is one group common to both This means that a keypad assigned to group 1 only for example can be used to set groups 1 2 3 and 4 by using a code with all of these groups allocated Keypad Group Restriction To restrict access only to groups that are common to both ...
Страница 157: ...menu location the assigned menu option the full menu option number and the assigned user type To modify the quick menu 1 Type or navigate to a quick menu number and then press ent 2 Type or navigate to a full menu number 11 to 72 and then press ent To delete a quick menu option Press instead of a full menu number NOT USED is displayed The system arranges the quick menu in order of lowest user type...
Страница 158: ...tion level between the panel and the keypads 3 RIO COMMS the voltage and version at each RIO as well as the communication level between the panel and the RIO 4 PSU COMMS the voltage at each Power Supply Unit and the communication level between the panel and the SPSUs It is identical to the RIO COMMS diagnostic with the exception that it also indicates the fuse status and battery status A number to...
Страница 159: ...y a list of RF zones Select a zone and press ent Select sub option 2 Reset lowest to reset the lowest recorded signal strength of the current zone only Select 2 Reset lowest directly to reset the lowest recorded signal strength of all RF zones Historical 61 2 The following options allow a full diagnostic baseline to be performed on the complete system including power supplies and peripherals View ...
Страница 160: ...ones in the system For RF zones signal strength and time since supervision are displayed 6 Communication Type of device address and the percentage level with all peripherals in the system 7 Panel Memory A check of the panel memory 9 Batt Volts Voltage level of the battery connected to the control panel Record 61 2 3 Use this option to start a baseline check of areas 1 to 7 in the table above You a...
Страница 161: ... generates the appropriate local or full alarm depending on the zone To start the full test 1 Select the Full Test option The address and function of the first zone on the system is displayed 2 Navigate to the required zone and then press ent 3 An option is then given to choose a second confirm zone If you press A YES select a second required zone by pressing ent If you press B NO the system begin...
Страница 162: ...p Mode enable option and then press ent to accept the programming 2 Return to the Engineer Mode banner to enable groups completely To disable Groups 1 Select the Group Mode disable option and then do one of the following Press 1 Reset Groups and then press ent All group programming for all the panel features is reset to A1 The message ATT GRPS OFF SYS OP IMPACT is displayed on exit from engineerin...
Страница 163: ... the group The current Setting Logic details are displayed for each of the other groups S below a group means that it must be set to allow the selected group to set below a group indicates that the group does not need to be set 3 To toggle the status of a group press its number 4 When you have defined the setting logic pattern press ent to save the programming Setting Logic Operation If Setting Lo...
Страница 164: ... the letter L 3 Press to erase the characters already assigned to the name 4 Use A or B to move the alphabet left or right until the required character is positioned underneath the flashing cursor and then press ent to copy the character to the descriptor in the top line 5 Repeat step 4 until the group name is complete Text Case Library On entering the Group Name option the alpha numeric character...
Страница 165: ...ed groups will set and unset even though they are not programmed 4 Final Keyswitch and Exit can be programmed to function with regard to other groups during the setting and unsetting procedures refer to option Program Zones 52 5 Outputs can be assigned to any selection of groups Output activation can be made dependent on the set or unset status of the assigned groups refer to Program Outputs 53 6 ...
Страница 166: ... to toggle between Disabled and Alarm 2 Entry Exit Press to toggle between Disabled and Alarm 3 Part Set Press to toggle between Disabled and Alarm 4 Full Set Press to toggle between Disabled and Alarm 3 Setting 1 Begin Set Press to toggle between Disabled and Enabled 2 Begin Entry Press to toggle between Disabled and Enabled 3 Sets System Press to toggle between Disabled and Enabled 4 Log Press t...
Страница 167: ...led To enable the zone to activate an alarm select the required Status attribute using the A or B keys and press The display indicates that a custom zone activation while the system is in the selected Status will create an Alarm condition and switch on the assigned outputs Note The custom zone can be operational in all four status conditions if required Setting 64 3 The Setting attribute determine...
Страница 168: ...e system is set Activates Link A outputs when the system is unset Generates an alarm condition when the system is part and full set Does not generate an alarm condition during the setting and unsetting procedure Acts as a terminator when the system is setting Logs all activation in both set and unset states To program Assemble Zone Assuming factory default settings 1 Select option 64 ASSEMBLE ZONE...
Страница 169: ...ress ent to select this option Begin Set Disabled is displayed 18 Press B Sets System Disabled is displayed 19 Press Sets System Enabled is displayed 20 Press esc Setting is displayed 21 Press A Log is displayed 22 Press ent to select this option Log Disabled is displayed 23 Press Log Entry Exit is displayed 24 Press Log 24 Hours is displayed 25 Press esc three times to return to 64 ASSEMBLE ZONES...
Страница 170: ...ramming 4 Holiday Period 00 40 00 None 5 Holiday Schedule 1 4 schedules 6 Pattern day 1 Mon 2 Tue 3 Wed 4 Thu 5 Fri 2 Timer Outputs 1 Timer A 1 Status 0 Off 1 On 2 Weekly Schedule 1 4 schedules 2 Timer B 1 Status 0 Off 1 On 2 Weekly Schedule 1 4 schedules 3 Autoset groups Use A or B to select groups then press ent 1 Status 0 Off 1 On 2 Monitor 2 Prewarning 1 Period 30 0 50 mins 2 Audible 0 Off 1 O...
Страница 171: ...e programs for each day of the week The state of the weekly schedule is ON or OFF depending on the last event that was reached Up to 4 weekly schedules with 28 time slots are available for programming depending on panel variant The weekly schedules are used to control these panel functions Auto setting Lockout times User access times Timer Outputs Name 65 1 1 A maximum 12 character alpha numeric n...
Страница 172: ...tched On and Off by users via option Timer Control 45 Holiday Period 65 1 4 This is the holiday period programmed in Modify Dates 45 2 1 Up to 40 holiday periods can be viewed with this option Holiday Schedule 65 1 5 This is an alternative schedule that is used if the Holidays 45 2 option is activated The system defines a selection of holiday dates 65 1 4 and then a schedule of times can be used o...
Страница 173: ... is to be allocated to Press A or B to step through the groups until the required number is displayed and press ent Account Group Autosetting Account Group autosetting is allowed This means that several groups can be bound together into one account group and instead of a sending a normal CA closed automatically event the panel sends a CL closed late event Refer to Account No 56 1 2 2 2 There are f...
Страница 174: ... factory preset any zone that is open at the start of the setting procedure except Final Exit Entry or Push Set or Secure Final or Part Final when acting as a Final is omitted by the autoset routine whether or not it is omittable If one of the above listed zones is open and is non omittable on expiry of the time programmed in the Fail to Set parameter the Fail to Set outputs are activated along wi...
Страница 175: ...tem was unset Press A or B to view the zones Press ent to continue the setting routine The zones that have not been activated do not have to be tested Autocheck when the setting routine is started the user is informed of the number of selected pre check zones that have not been activated since the system was unset and a warning is sounded press the A or B keys to view the zones These zones must be...
Страница 176: ...onditions that require to be reset remotely must have the appropriate System Reset Tamper Reset or PA Reset parameters programmed for engineer reset type 7 Each alarm activation generates a random number therefore the number required to reset the panel changes each activation As ARCs have different decoding equipment the appropriate reset system must be selected from the following Remote Mode opti...
Страница 177: ...es appear displayed on the top line of the display The type maps default to the standard access To modify the types press the required number keys this toggles the access type numbers on the bottom line of the display on and off Press ent to save the programming and return to the previous menu level If the level is assigned to the option the number is displayed if it has been removed a dash is dis...
Страница 178: ... graphic ent to select 1 Descriptor toggle upper case lower case or library text delete last character A B move to character word ent assign character word esc save programming 2 Relay Duration 1 60 seconds default 05 3 Open Timeout 0 60 seconds default 10 4 Groups 1 Alarm Group 2 Group Restrict 3 Exit group 5 Emergencies Enable or disable option If group mode is enabled a separate enable is avail...
Страница 179: ...trict 3 Exit Group 05 Emergencies 0 Disabled 1 Enabled 06 Security 1 Nightlock 0 4 weekly schedules 2 Unlock Time 0 4 weekly schedules 3 Dual Mode 1 Disabled 2 Card and Card 3 Card and Pin 4 Dual Time Option not available 07 Menu Recall 1 Menu Function 11 72 not used 2 Menu Mode 1 Triple Repeat 2 Recall Button 3 Keypad Keypad Enable 2 Card Format 0 26bit 1 Crp 1K 35bit 2 37bit no FC 3 Northern 34 ...
Страница 180: ...odules are assigned and modified using this option On selecting MAX Address the system searches for the MAX with the highest address Select the line and press ent On locating the MAX the keypad prompts for the type of MAX to be assigned 0 Online The MAX is fully integrated with the system and communicates via the AB line sharing system resources and facilities 1 Standalone The MAX operates as an e...
Страница 181: ... swipe If the door remains open longer than the period assigned to the Open Timeout then an alarm occurs Note If the Open Timeout is programmed as 0 seconds then the door can remain open indefinitely without resulting in an alarm being activated The range is 00 to 60 seconds and the default time is 10 seconds Press A or B to increase or decrease the time in one second increments Alarm Group 69 2 2...
Страница 182: ...ups which are common to both the MAX and the card Refer to the following table for examples of how the readers respond to different situations with the Common Group Restriction on and off The card held function used in the example is Timed Set Action on card held Situation at time of card swipe No on Group Restriction All groups unset All groups on card start to set All common groups start to set ...
Страница 183: ... to 4 weekly time schedules can be programmed Setting the schedule to 00 disables the function Security Dual Mode 69 2 2 6 3 Use this option enable dual authority via the assigned keypad The options are 0 Disabled A card or a PIN is required to gain access 1 Card and Card Two cards are required to gain access 2 Card and Pin A card and a PIN from the same user are required to gain access Menu Recal...
Страница 184: ... Use this option to assign a name of up to 9 characters to each of the DCMs This name is assembled from the character set and or library options On selecting the Descriptor parameter the currently assigned name is displayed on the top line an underscore shows where the next character will be positioned and a selection of the alphabet is shown on the bottom line the cursor flashes on the letter L P...
Страница 185: ...pe If the door remains open longer than the period assigned to the Open Timeout an alarm occurs Note If the Open Timeout is programmed as 0 seconds then the door can remain open indefinitely without resulting in an alarm being activated The range is 0 to 60 seconds and the default time is 10 seconds Press A or B to increase or decrease the time in one second increments DCM Reader Alarm Group 69 3 ...
Страница 186: ...CM LED lights and the buzzer sounds Closing the fire zone has no effect the DCM readers are treated as latched outputs and an appropriate reset is required A second group map is allocated to each DCM reader in order to facilitate this function This permits the existing door control features to be separate from the fire escape features The default setting for each DCM reader is all groups selected ...
Страница 187: ...d from the available list 11 72 To assign a new option press A or B until the required option is displayed or enter the option number directly and then press ent to accept the selection Assign a double asterisk to make the menu function not used DCM Menu Recall Menu Mode 69 3 1 5 07 2 Use this option to control the menu function There are two options 1 Triple Repeat The card is presented to the re...
Страница 188: ...options can be selected 1 Start point If the card structure is unknown a start number can be chosen that is a numeric value less than the maximum length of the card 2 Field Length This is the length of the card number The maximum field length is from the start of the card number to the maximum length of the card ...
Страница 189: ...al is valid When a module is added the now count is increased To view all the added or missing modules 1 Press esc 2 Press A or B to scroll through the list To confirm module removal Press Modules added and removed are recorded in the event log To program or configure a new module exit the Auto Detect option Engineering Exit operation and Auto Detect operation are mutually exclusive when one opera...
Страница 190: ......
Страница 191: ...M 056 BROWN 057 BUILDING 058 BUNKER 059 BY 060 CABINET 061 CAFE 062 CALL 063 CANTEEN 064 CAR 065 CARGO 066 CARPENTER 067 CARPET 068 CASH 069 CASHIER 070 CEILING 071 CELL 072 CELLAR 073 CENTRAL 074 CENTRE 075 CHAIR 076 CHANGING 077 CHEMISTRY 078 CHICKEN 079 CHURCH 080 CLASSROOM 081 CLEANER 082 CLEANERS 083 CLEANING 084 CLERK 085 CLERKS 086 COAL 087 COAT 088 COIN 089 COLD 090 COLLECTION 091 COMMUNIC...
Страница 192: ...255 LINE 256 LITTLE 257 LOADING 258 LOBBY 259 LOCK 260 LOFT 261 LORRY 262 LOUNGE 263 LOW 264 LUNCH 265 MACHINE 266 MAGNETIC 267 MAIN 268 MAJOR 269 MALE 270 MAN 271 MANAGER 272 MANAGERS 273 MASTER 274 MAT 275 MATHS 276 MEDICAL 277 MEN 278 MESS 279 METAL 280 METER 281 MEZZANINE 282 MICROWAVE 283 MIDDLE 284 MILK 285 MINOR 286 MOBILE 287 MODEL 288 MONITOR 289 MOULDING 290 MOVEMENT 291 NEAR 292 NEW 293...
Страница 193: ...TATION 445 STOP 446 STORE 447 STORES 448 STROBE 449 STRONG 450 STUDY 451 SUITE 452 SUMMER 453 SUNDAY 454 SUPPLY 455 SURGERY 456 SWIMMING 457 SWITCH 458 SYSTEM 459 TABLE 460 TALL 461 TAMPER 462 TEA 463 TEACHER 464 TECHNICAL 465 TECHNICIAN 466 TELLER 467 TEN 468 TENNIS 469 TEST 470 THE 471 THEATRE 472 THEN 473 THIRTEEN 474 THIRTY 475 THREE 476 TICKET 477 TILL 478 TO 479 TOILET 480 TOOL 481 TOP 482 T...
Страница 194: ......
Страница 195: ...NONE 150 EXIT Exit zone alarm ZONE 2 INTRUDE 134 INTRUDER Intruder zone alarm ZONE 2 INTRUDE 130 SECURITY Security zone alarm ZONE 4 SECURITY 135 DUAL Dual zone alarm ZONE 2 INTRUDE 130 FINAL Final zone alarm ZONE NONE 150 SEC FINAL Secure final zone alarm ZONE 4 SECURITY 134 PRT FINAL Part final zone alarm ZONE 2 INTRUDE 134 PRT ENTRY Part entry zone alarm ZONE 2 INTRUDE 134 BEAM PAIR Beam pair z...
Страница 196: ... BEAM PAIR Beam pair zone rest ZONE 2 INTRUDE 130 18 ZN RESTO VIDEO Video zone restored ZONE 2 INTRUDE 130 18 ZN RESTO VIDEO EXT Video exit zone rest ZONE 2 INTRUDE 130 18 ZN RESTO CUSTOM A Custom A zone rest ZONE 5 CUS ZON 130 18 ZN RESTO CUSTOM B Custom B zone rest ZONE 5 CUS ZON 130 18 ZN RESTO MASK Mask zone restored ZONE 4 SECURITY 135 18 ZN RESTO INT ALARM Intruder Delay restored ZONE 2 INTR...
Страница 197: ...zone tested ZONE NOT SENT 611 LOG Log zone tested ZONE NOT SENT 611 RM ACCESS Rem acc zone tested ZONE NOT SENT 611 VIDEO Video zone tested ZONE NOT SENT 611 VIDEO EXT Video exit zone tested ZONE NOT SENT 611 INT DELAY Intrud delay zone tested ZONE NOT SENT 611 SEC DELAY Security del zone tested ZONE NOT SENT 611 SET LOG Set Log zone tested ZONE NOT SENT 611 CUSTOM A Custom A zone tested ZONE NOT ...
Страница 198: ...pen MOD 4 SECURITY 426 E System Trouble ER Mod Removed REMOVED Module Removed MOD TAMPER 532 ET RF NVM Fail RF MEM RF NVM RAM Fail MOD TAMPER 333 F Fire FA Fire Alarm FIRE Fire zone alarm ZONE 6 FIRE 110 FB Fire Bypass OMITTED Fire zone omitted ZONE 8 OMIT 573 FORCEOMT Force omit after rearm ZONE 8 OMIT 573 FJ Fire Troub rest LOW RES Restor zone resistance ZONE 15 TROUBL 380 HIGH RES Restor zone r...
Страница 199: ...c condition reported ZONE 20 FAULT 330 IR Equipment Fail Rest FAULT Condition restored to normal ZONE 20 FAULT 330 J Wrong code Time changed JA Code Tamper WRONG CD Wrong code alarm act MOD 9 TAMPER 461 Invalid Code INVALID CD Invalid Code entered MOD ALWAYS TR None JL LOG 90 MISC ALWAYS TR 632 JR TIMER A MISC NONE 0 TIMER B MISC NONE 0 AUTOTIMER MISC NONE 0 LOCKTIMER MISC NONE 0 JT Time changed N...
Страница 200: ... 15 TROUBL 380 HIGH RES High resistance on zone ZONE 15 TROUBL 380 MU Unbypass FORCE OMT Unomitted after rearm ZONE 8 OMIT 573 O Opening OA Open Report UNSET Automatic Unset EVENT 10 SETTING 401 OG Open Area UNSET Part Unset USER 10 SETTING 401 KSW UNSET Keyswitch part unset ZONE 10 SETTING 409 OK Early Open U S EARLY Unset Early EVENT 10 SETTING 451 OP Open Report UNSET Unset USER 10 SETTING 401 ...
Страница 201: ...K Link zone closed ZONE 16 LOG 150 LOG Log zone closed ZONE 16 LOG 150 LOG DELAY Log delay zone closed ZONE 16 LOG 150 CUSTOM A Zone closed Non alarm ZONE 16 LOG 150 CUSTOM B Zone closed Non alarm ZONE 16 LOG 150 EXITGUARD Exitguard zone closed ZONE 16 LOG 150 RD Prog denied RMACCESS Zone denied rem acc ZONE 14 MEN AC 553 RO Relay open BELL FAIL Bell fail zone opened ZONE 16 LOG 150 KEYSWITCH KS N...
Страница 202: ...ne ZONE 9 TAMPER 383 MAX TAMP MAX Module Tamper MOD 9 TAMPER 145 WALL TAMP Wall tamper zone alarm ZONE 9 TAMPER 137 MASK TAMP ZONE 9 TAMPER 383 DCM EVENT Invalid Card Tamper alarm MOD 9 TAMPER None ADDED Module Added MOD 9 TAMPER 531 ENG TAMP Engineering Tamper MISC 9 TAMPER None TE Test End WALK TEST Walk test finished USER 14 MEN AC 607 TR Tamper Restor TAMPER Tamper zone restored ZONE 9 TAMPER ...
Страница 203: ...Cold Start MEM RESET Power Up Panel MISC 13 ELEC ST None YK Comm Restoral internal to tel Tel module rest RS485 EVENT ALWAYS TR 350 YL AC Batt Fail AC BATT Mains fail and batt low EVENT 13 ELEC ST None YP PSU fail PSU FLT Power Supply Unit fault EVENT 13 ELEC ST 314 YR Sys Batt Rest BATT LOW Battery Low restored ZONE 13 ELEC ST 302 CU BATT Control unit batt restore ZONE 13 ELEC ST 302 BATT LOW Mod...
Страница 204: ...IAG REC LIST NONE 0 00 LOC WRITE LIST NONE 0 00 REM WR RD LIST NONE 0 00 DIAG CHK LIST NONE 0 00 DISCHARGE ZONE 13 ELEC ST 0 00 ETST PASS USER NONE 0 00 ETST FAIL MISC NONE 0 00 OVERRIDE MISC NONE 0 00 R TIMESET MISC NONE 0 00 CU RIO SW MISC NONE 0 00 CLBK1 ERR USER NONE 0 00 REM TRY USER NONE 0 00 REM FIN USER NONE 0 00 REM ABORT USER NONE 0 00 REM FAIL USER NONE 0 Note 1 Dependent upon zone type...
Страница 205: ... pimmm EV 1 xxxxxx NEVmmm 0 xxxx NEVmmm Event 3 4 xxxxxx Ntixx xx rixx EV Aeeeeeeeeesiiiiiiii 1 With ri modifier Automatic set timer activated 2 Without ri modifier Automatic test engineer mode 2 xxxxxx Ntixx xx rixx EV 1 xxxxxx NEV 0 xxxx NEV000 Key Data Block ti Time modifier ri Group modifier not used if groups are disabled id User modifier u User number pi Peripheral modifier m Peripheral numb...
Страница 206: ......
Страница 207: ...mA maximum Power supply Type A Battery type Sealed lead acid plastic enclosure Max ripple voltage 150 mV pk pk Maximum auxiliary current rating 0 9 A EN grade 2 maximum auxiliary current rating 0 7 A Minimum standby battery capacity required for maximum load EN50131 PD6662 12 hrs 8 4 Ah Maximum Battery Size 10Ah Time to recharge Battery to 80 10Ah Battery 67 hrs Total PSU output 1 A Aux voltage ou...
Страница 208: ...ce Module C084 60 60 Speaker mic Unit TP2 800GY 10 10 Keypad CP050 xx 70 90 Keyprox CP051 xx 90 130 TouchCenter CP041 xx 105 110 MAX 4 Reader MX04 35 35 Door Control Module C080 65 65 Vplex Module C090 75 75 GPRS Module A070 xx 35 150 2 ISDN Module A211 40 50 2 Ethernet E080 2 155 165 2 Note 1 Measured with no detectors or sirens attached Note 2 Communication on and average current during normal a...
Страница 209: ...supplies grade 2 EN50136 1 1 Alarm systems Alarm transmission systems and equipment 1998 A2 2008 General requirements for alarm transmission systems EN50136 1 3 1998 Alarm systems Alarm transmission systems and equipment Requirements for systems with digital communicators using the public switched telephone network EN50136 2 1 1998 Alarm systems Alarm transmission systems and equipment General req...
Страница 210: ...n European single terminal connection to the Public Switched Telephone Network PSTN However due to differences between the individual PSTNs provided in different countries the approval does not of itself give an unconditional assurance of successful operation on every PSTN network termination point In the event of problems contact the equipment supplier in the first instance The product is designe...
Страница 211: ...Keypad CP041 00 Multi language TouchCenter Keyprox CP042 00 Multi language Remote Modules RIO PCB A158 B Expander module 8 zone 4 outputs RIO boxed C072 Expander module 8 zone 4 outputs Printer Interface A161 25 way sub D connector ISDN Module E077 Ethernet module E080 2 RF Portal boxed C079 2 Gateway for wireless peripherals RF Portal Kit For installation inside panel box Audio Controller C084 2 ...
Страница 212: ...alone installation on 1 PC Installer version Network R057 CD DG Installation CD plus 1 dongle for network installations Additional dongle for user version and installer network YY0 0010 Allow one more network operator User Management Suite UMS Installation kit 1 user R058 CD DG Installation CD plus 1 dongle Additional Dongle for 1 more user YY0 0010 Allow another user installation or one more netw...
Страница 213: ...r Power consumption The Mk 8 Keypad KeyProx needs 12 V d c supplied by the control panel or a remote power supply The current consumption of the Keypad KeyProx is Mode Mk8 Keypad Mk8 KeyProx Nominal backlight off 30 mA 50 mA Backlight on 60 mA 80 mA Maximum alarm mode 90 mA 110 mA Installation Setting the address Set a unique address for the keypad using the rotary switch on the PCB before applyin...
Страница 214: ...er functions Refer to Appendix F for keypad KeyProx part numbers with the volume control function Self diagnostics Use this feature to test the keypad inputs and outputs To start the test disconnect the power to the keypad Press and hold ent and then re apply the power The test routine starts immediately Each test last approximately four seconds To stop the test disconnect the power Keypad KeyProx...
Страница 215: ...ors in the TEXT option to start printing from the current event when viewing option Display Log 22 to display the set status of the groups When Show Status refer to option Show Status 58 6 is enabled pressing the and keys simultaneously when the normal banner is displayed indicates the group set status Power LED The power LED indicates the status of the a c power supply and the stand by battery Po...
Страница 216: ...rtable fobs and panic buttons will be used RF Portals will automatically communicate with RF detectors and fobs which give the highest received signal strength There is no link between individual RF Portals and zones or users The Panel will automatically switch to an alternate RF Portal if the signal path becomes blocked Adding an increased number of RF Portals around the building will increase th...
Страница 217: ...eption is likely 5 Mount RF Portals with the antenna in a vertical orientation for best reception Installation Setting the address Using the rotary switch on the PCB set each RF Portal address to a unique value before power is applied Any address in the range 0 to 15 can be used This address is independent of the addresses used by other types of modules For example an RF Portal can share the same ...
Страница 218: ...sses when an RF Portal is configured You can manually alter the number and addresses of the virtual RIO using the RF Address 51 60 1 menu option You can view the zones allocated to wireless detectors using the RF Zones 52 2 menu option Programming Program wireless zones using the RF Zones 52 2 menu option If required customise operation of the wireless system using the RF Parameters 51 60 menu opt...
Страница 219: ... on the line connect a 680 Ω EOL resistor across the A and B terminals Configuration To configure the RIO in the system exit from engineer mode If the message XX Mod Added To View is displayed the system has recognised the module Press A or B to confirm that the RIO has been added If the message is not displayed or the RIO is not on the list of added modules then it is not communicating with the c...
Страница 220: ...each output is 400 mA The default functions and pull up resistors are shown below Output Function Pull up resistor 1 Bells R1 2 Strobe R3 3 PA R5 4 Reset R7 Table 11 RIO output default functions Specification Width 160mm 6 Height 151mm 6 Depth 40mm 1 Weight approx 300g 11oz Humidity 0 85 Nominal Supply voltage 12V DC Current Nominal 30mA Current Maximum 590mA Max output current max combined load t...
Страница 221: ...e module and then plug the other end into the socket on the control panel PCB SIM holder GSM GPRS module B A C C 3 Locate the module on the three mounting pillars as shown B and secure it in position with the supplied screws C 4 Fit a suitable SIM card into the SIM holder on the top of the module see SIM cards below 5 Re connect the battery and mains power to the control panel SIM cards Any valid ...
Страница 222: ...ion over GSM will be significantly slower than PSTN Using the GPRS channel and an Ethernet link to the PC will allow faster communications Characteristics The following table shows the technical characteristics of the GSM module GSM fault detection Dedicated internal GSM fault code is triggered by the lack of a network Service temperature 0 deg to 40 deg C Storage temperature 20 deg to 70 deg C Du...
Страница 223: ...he Ethernet PCB may vary with different hardware revisions Configuring the module To configure the module in the system exit from engineer mode It is allocated keypad address 15 B If the message XX Mod Added To View is displayed the system has recognised the module Press A or B to confirm that comm 4 has been added If this message is not displayed or the Ethernet module is not on the list of added...
Страница 224: ...in the enclosure Keypad interface button EMERGENCY button Figure 10 Homepage screen Installation procedure 1 Remove the mounting plate from the TouchCenter by pushing it towards the bottom of the keypad 2 Locate the mounting plate over the mounting surface such that the opening of the mounting plate is aligned with the cable 3 Pass the cable through the opening of the mounting plate 4 Secure the m...
Страница 225: ...s On first power up the TouchCenter immediately prompts for a bus address This can be any valid address that is not shared with any other keypad KeyProx or MAX device The default address is usually acceptable Note A KeyProx needs two module addresses one for the keypad and one for the prox device The address used must be suitable for both a keypad and MAX device If the address has previously been ...
Страница 226: ...ree diagnostic tests are provided to verify correct operation of the TouchCenter and to check the connection to the control panel LCD Display Test Audio Test LED Test Address If required use the option SERVICE to change the RS485 address If changed reconfigure the TouchCenter with the control panel TouchCenter operation For general operation 1 On the homepage press the required function button Not...
Страница 227: ...urrent 203 mA maximum 287 mA maximum 175 mA display on 210 mA display on 107 mA standby 140 mA standby Note Ensure that sufficient power is available for the TouchCenter keypad A local power supply may be required Compliance This product is suitable for use in systems compliant to EN50131 1 2006 and PD6662 2006 This product has been tested for compliance to EN50131 3 2009 by BRE Global Ltd Securit...
Страница 228: ...d or erased Removing power from the MAX4 does not erase the programming memory Note The MAX4 defaults to standalone mode It can be configured to online mode directly from the control panel Online The MAX4 can operate in fully integrated online mode with the control panel communicating via the AB line to share system resources and facilities In this configuration the MAX4 can be used for both door ...
Страница 229: ... 6 Void Red 7 Program Red Figure 11 MAX4 LEDs Violet C NC NO Relay Module A060 Relay Out 12V Suppressor OR Violet Relay Out Door Lock Horn Door Contact I P RS485A In Extra Ground Power Input Ground White Grey Pink Green Blue Pink Yellow Brown Grey Red Blue Black Red Spare Horn O P Egress I P RS485B Out RS485A Out RS485B In Door Contact Egress 12V 12V Galaxy RS485 Data Bus only used in on line conf...
Страница 230: ...ng new readers with the lowest available number on the line When reprogramming is complete the MAX4 bleeps the LEDs on the MAX4 switch off and the keypad display returns to 1 MAX Address 6 Enter your engineer code and then press esc to exit from engineer mode The message 1 MOD ADDED esc CONTINUE is displayed on the keypad and LED 2 on the MAX4 reader switches on Press esc and the keypad returns to...
Страница 231: ... key on any of the keypads assigned to a common group displays the card held function Card Held system setting If the MAX4 or DCM card is assigned one of the setting options options 12 13 and 16 to 19 the card held functions starts the setting procedure for the groups assigned to the card Note If Group Restriction is assigned only the groups that are common to both the MAX4 reader and the MAX4 use...
Страница 232: ...y the number of RIOs that can be added to a panel 1 1 2 2 3 3 4 4 5 5 6 6 7 7 8 8 zones 1 to 8 heatsink COMs lines outputs rotary address switch AC BAT PWR 0 V OP1 OP2 OP3 OP4 LID TAMP OW TAMP 14 5 0 V 12V1 A DO B DI F1 F4 F3 F2 LK1 LK2 LK3 LK4 BAT BAT AC F BT 0 V 14 5 0 V 13 8 LED1 COMs LED2 AC Control Unit 12V2 0 V 0 V FAULT OP external tamper from Power Block Bell box connector LK5 LK10 SLAVE E...
Страница 233: ...the control panel in the PSU Comms 61 4 menu option Configuration Addressing for either variant is identical to that described for RIO Modules Set the address using the rotary switch before applying power The 4 outputs are switched 0 V 0 V active Without the jumper links LK1 4 fitted the outputs float in the OFF state They can apply a 12 V signal if required by fitting the appropriate pull up jump...
Страница 234: ... Block Off Wall Tamper Micro switch Lid Tamper Microswitch 6 way jumper lead from power block to control unit 2 Tie wrap the mains cable as shown 3 Using a three core cable that satisfies local regulations wire mains power to the mains terminal block as follows blue wire to the terminal marked N Neutral green yellow wire to the terminal marked E Earth brown wire to the terminal marked L Live Note ...
Страница 235: ...put French variant only Output voltage nominal Output current max 14 5 V 0 15 A when using this current the AUX1 AUX2 currents will be reduced by an equivalent amount Battery charge current max Maximum ripple voltage 1 4 A 100 mV Fuses F1 14 5 V F2 Battery F3 12 V Aux1 F4 12 V Aux2 500 mA 20 mm anti surge 1 6 A 20 mm anti surge 1 0 A 20 mm anti surge 1 0 A 20 mm anti surge EN50131 Compliance This ...
Страница 236: ...s in addition to two receiver specific X 25 protocols Hardware and software line snatch Comprehensive line fail detection and reporting Two way communication using B Channel and D Channel The ISDN Module is allocated keypad address C and reports itself as Comm Mod 3 As a result of the addition of the ISDN module keypad address C is not available If this keypad is required the ISDN Module should be...
Страница 237: ...ces such as the TP800 can be connected to each audio channel PHONE LINE A B A B Telecom Socket Telecom Connect SKT1 Debug Header LK4 LK3 GND 12V GND SPARE AUDIO A B A B PANEL PL3 PL6 CMD 2 TMP 2 SPK 2 MIC 3 GND 4 5V CMD 1 TMP 1 SPK 1 MIC 1 LK2 F1 PL2 Jumper lead RS485 termination Engineer Header Audio Bus RS485 Audio Bus Engineer Header RS485 line Control Panel RS485 line Off wall Tamper microswit...
Страница 238: ...hones with a pre amplifier that delivers audio at line level 3 V peak to peak The module can transmit audio to speakers that accept line level signals Please read any instructions that come with your microphone regarding the adjustment of sensitivity The module can be used with the following Honeywell audio devices TP800 TP2 800GY Speaker and microphone unit IS215TCE MIC PIR detector with built in...
Страница 239: ...Galaxy Flex Installer Manual Appendix G Peripherals 239 IS215TCE MIC DT7450 MIC connection Detector connections Audio Interface IS215TCE MIC DT7450 MIC GND 12 V MIC M GRD G ...
Страница 240: ... the DCM PCB from the box to allow access to the screw holes 2 Fix the base to the mounting surface using the screw holes provided 3 Bring all cables into the enclosure via the base cable entry points There are six cable entry holes 4 Attach the RIO box lid with the four thread forming screws provided Mounting the power RIO box The DCM is mounted above the control PCB on a mounting plate 1 Remove ...
Страница 241: ...lay activates only for the programmed duration but the door propped alarm is held off This can be achieved for example by using a keyswitch wired in parallel with the normal EC button request to exit Function Contact This uses normal 1 k 2 k double balanced zone wiring It initiates a pre programmed menu option following a valid card The normal use is to activate the setting procedure via the reade...
Страница 242: ... Common pin for connecting cable shield or drain wire 12 volt output 0 volt connect DO Data Out DI Data In LED 1 LED 2 LED 3 Buzzer output for reader 1 2 3 4 5 6 7 8 ON Not Used 0 volt connect RTE contact Door contact input 0 volt connect Function contact menu button Normally closed relay Common pin relay Normally open relay TC 0V Lid tamper switch Tamper connect Rotary address Switch DIP Switches...
Страница 243: ... ON OFF OFF 3 ON ON OFF OFF Connecting the DCM to the system Wire the DCM to the RS485 line The DCM requires 12 V d c which can be supplied from the control panel power supply or from the Power RIO when mounted inside the Power RIO box see Figure 17 Note If the DCM is the last module on the line connect a 680 Ω EOL resistor across the A and B terminals Configuring the DCM The DCM is configured int...
Страница 244: ... within a Power RIO enclosure please see the Power RIO documentation Electrical Operating voltage range 10 5 V to 15 V Current draw typical 40 mA Current draw maximum 2 readers 130 mA Compliance This product is suitable for use in systems compliant to EN50131 1 2006 EN50133 1 and PD6662 This product has been tested for compliance to EN50131 3 and EN50133 3 by CNPP Security Grade 3 Environmental cl...
Страница 245: ...nsions 13 E engineer mode 31 G GPRS setup 153 L learn wireless detectors 22 line monitoring 134 ISDN line 143 M MAX reader address 46 mounting holes 13 P parts list 213 pcb layout 11 peripherals compatible 10 R RS485 wiring recommendations 18 S specifications 10 electrical 209 mechanical 209 system architecture 8 T templates 24 Z zone addressing 18 configuration 19 ...