background image

 

 

 

Honeywell Emergency Notification Manager

 

EBI XLS MASS NOTIFICATION SYSTEM (MNS) 

 

 

  

                                                                  CONFIGURATION, PROGRAMMING AND OPERATION MANUAL 

 

WARNING

 

This  equipment  generates,  uses,  and  can  radiate

 

radio  frequency  energy,  and  if  not  installed  and 
used  in  accordance  with  the  Instructions  Manual, 
may cause interference with radio communication. 
It  has  been  tested  and  found  to  comply  with  the 
limits for a  Class  A computing device pursuant to 
Subpart  J  of  Part  15  of  FCC  Rules,  which  are 
designed to provide reasonable protection against 
such  interference  when  operated  in  a  commercial 
environment.  Operation  of  this  equipment  in  a 
residential  area  is  likely  to  cause  interference,  in 
which  case,  users  at  their  own  expense  will  be 
required  to  take  whatever  measures  may  be 
required 

to 

correct 

the 

interference. 

Any 

unauthorized  modification  of  this  equipment  may 
result in the revocation of the owner's authority to 
continue its operation.

 

 

FIRE ALARM & EMERGENCY 
COMMUNICATION SYSTEM 
LIMITATIONS

 

While a life safety system may lower insurance rates, it is not a 
substitute for life and property insurance 

An automatic fire alarm system

-typically made up of smoke 

detectors,  heat  detectors,  manual  pull  stations,  audible 
warning  devices,  and  a  fire  alarm  control  panel  (FACP)  with 
remote  notification  capability-can  provide  early  warning  of  a 
developing  fire.  Such  a  system,  however,  does  not  assure 
protection  against  property  damage  or  loss  of  life  resulting 
from a fire. 

An emergency communication system

-typically made up of 

an automatic fire alarm system (as described above) and a life 
safety 

communication 

system 

that 

may 

include 

an 

autonomous  control  unit  (ACU),  local  operating  console 
(LOC),  voice  communication,  and  other  various  interoperable 
communication  methods-can  broadcast  a  mass  notification 
message.  Such  a  system,  however,  does  not  assure 
protection  against  property  damage  or  loss  of  life  resulting 
from a fire or life safety event. 

The  Manufacturer  recommends  that  smoke  and/or  heat 
detectors  be  located  throughout  a  protected  premises 
following  the  recommendations  of  the  current  edition  of  the 

National  Fire  Protection  Association  Standard  72  (NFPA  72), 
manufacturer's recommendations, State and local codes,  and 
the  recommendations  contained  in  the  Guide  for  Proper  Use 
of  System  Smoke  Detectors,  which  is  made  available  at  no 
charge to all installing dealers. This document can be found at 
http://www.systemsensor.com/appguides..
  A  study  by  the 
Federal  Emergency  Management  Agency  (an  agency  of  the 
United  States  government)  indicated  that  smoke detectors 
may not go off in as many as 35% of all fires. While fire alarm 
systems  are  designed  to  provide  early  warning  against  fire, 
they do not guarantee warning or protection against fire. A fire 
alarm system may not provide timely or adequate warning, or 
simply may not function, for a variety of reasons: 

Smoke  detectors 

may  not  sense  fire  where  smoke  cannot 

reach  the  detectors  such  as  in  chimneys,  in  or  behind  walls, 
on  roofs,  or  on  the  other  side  of  closed  doors.  Smoke 
detectors also may not sense a fire on another level or floor of 
a  building.  A  second-floor  detector,  for  example,  may  not 
sense a first-floor or basement fire. 

Particles  of  combustion  or  "smoke" 

from  a  developing  fire 

may  not  reach  the  sensing  chambers  of  smoke  detectors 
because: 

—  Barriers  such  as  closed  or  partially  closed  doors, 

walls,  chimneys,  even  wet  or  humid  areas  may  inhibit 
particle or smoke flow. 

— 

Smoke  particles  may  become  "cold,"  stratify,  and  not 

reach  the  ceiling  or  upper  walls  where  detectors  are 
located. 

—  Smoke particles may be blown away from detectors by 

air outlets, such as air conditioning vents. 

—  Smoke  particles may  be  drawn  into  air  returns  before 

reaching the detector. 

 

The  amount  of  "smoke"  present  may  be  insufficient  to  alarm 
smoke  detectors.  Smoke  detectors  are  designed  to  alarm  at 
various levels of smoke  density.  If such density levels are not 
created  by  a  developing  fire  at  the  location  of  detectors,  the 
detectors will not go into alarm. 

Smoke  detectors,  even  when  working  properly,  have  sensing 
limitations.  Detectors  that  have  photoelectronic  sensing 
chambers  tend  to  detect  smoldering  fires  better  than  flaming 
fires,  which  have  little  visible  smoke.  Detectors  that  have 
ionizing-type  sensing  chambers  tend  to  detect  fast-flaming 
fires  better  than  smoldering  fires.  Because  fires  develop  in 
different  ways  and  are  often  unpredictable  in  their  growth, 
neither type of detector is necessarily best and a given type of 
detector may not provide adequate warning of a fire. 

 

 

39-00008-1 

 

Содержание EBI XLS MASS NOTIFICATION SYSTEM

Страница 1: ...rer s recommendations State and local codes and the recommendations contained in the Guide for Proper Use of System Smoke Detectors which is made available at no charge to all installing dealers This document can be found at http www systemsensor com appguides A study by the Federal Emergency Management Agency an agency of the United States government indicated that smoke detectors may not go off ...

Страница 2: ...mission systems are recommended The most common cause of life safety system malfunction is inadequate maintenance To keep the entire life safety system in excellent working order ongoing maintenance is required per the manufacturer s recommendations and UL and NFPA standards At a minimum the requirements of NFPA 72 shall be followed Environments with large amounts of dust dirt or high air velocity...

Страница 3: ...damage threads resulting in reduced terminal contact pressure and difficulty with screw terminal removal This system contains static sensitive components Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body Use static suppressive packaging to protect electronic assemblies removed from the unit Follow the instructions in the ...

Страница 4: ... 11 Programming Steps 11 ACU 11 CCS 12 LOC 12 Subsidiary Equipment 13 Programming 13 DCC Participation 13 Local Control 14 Mass Notification Control Settings for the XLS DVC 15 Set the Priority 15 MN Mapping 17 Type IDs 18 Special Function Zones 19 MN Active Tone 19 Fire Active Tone 22 DVC RPU 24 MN Annunciator Programming 25 XLS DVC General Zones 26 OPERATION 26 Mass Notification Events 26 MN Ala...

Страница 5: ...well products Fig 1 to create a system with mass notification capabilities It covers assembling the following key components of a mass notification system Autonomous Control Units ACU Local Operating Consoles LOC Central Control Stations CCS It also details the mass notification MN event priority and describes the system s operation when MN is part of its function The installation and functions co...

Страница 6: ...larms differently from fire alarms Fire alarms are indicated by the Fire Alarm LED and will be counted with the Fire Alarm counter MN alarms are indicated by the Other LED on the display and indicated on an annunciator with a dedicated LED and counted with an OTHER counter MN supervisory events and fire supervisory events share the Supervisory LED piezo sounding pattern and supervisory counter MN ...

Страница 7: ... general paging for prioritization based on site specific requirements A page at the MN level will create a latching MN alarm condition that requires acknowledgment and reset The LOC supports All Call when priority allows LOC pages must be ALL CALL pages MN events can be acknowledged silenced or reset only by an active MN command center When an LOC gains control of acknowledge silence and reset fu...

Страница 8: ... more ACUs in a mass notification system The priority of a CCS will be lower than that of an ACU or LOC in the MN fire system EBI WORKSTATION The EBI workstation displays events and status of the MN and fire systems from any ACU located on an XLS NET It provides two paging levels Level 1 and Level 2 which may be assigned to MN or fire for prioritization based on site specific requirements A page a...

Страница 9: ...vides the audio functions of the CCS It provides three paging levels Level 1 Level 2 and Level 3 which may be assigned to MN fire or general paging for prioritization based on site specific requirements A page at the MN level will create a latching MN alarm condition that requires acknowledgment and reset Multiple CCS locations can be prioritized in hierarchical levels by adjusting the priority le...

Страница 10: ...09A Monitor Module TC809B Mini Monitor Module TC809D Dual Monitor Module or XP10 M Monitor Module can be installed to monitor a UL approved switch or button device installed for initiating MN alarms A Listed UL2017 initiating switch device is required It will generate an MN alarm MN supervisory or MN trouble message when it is programmed with an MN EC type code Fig 8 Monitor Module and Input Devic...

Страница 11: ...To ensure that you are installing and programming the latest features we strongly recommend that you download the most current version of software for each product prior to commissioning any system Contact Technical Support with any questions about software and the appropriate version for a specific application PROGRAMMING Overview When a system is configured for both fire and MN protection progra...

Страница 12: ...input categories and priorities Fig 21 4 Create and program an MN Active Tone page 19 5 Create and program a Fire Active Tone when Fire is the highest priority page 21 ACU Programming Steps XLS3000 XLS NCA2 4 Program with MN type IDs page 18 5 Program with MN Special Function Zones page 19 XLS3000 must be in network display mode to function as part of an ACU XLS DVC 1 Set the MN mode enable paging...

Страница 13: ...articipation In a system with both MN and Fire support DCC must always be disabled for all XLS120s XLS140 2s XLS3000s XLS NCA2s and EBI Workstation XLS3000 XLS NCA2 Panel In the Panel Settings Menu Set DCC Participation to NO to disable DCC Participation Fig 9 Panel Settings Screen 2 XLS3000 Subsidiary Equipment Programming Steps XLS DVC 1 Set the MN Mode Fig 15 2 Set the Associated Node Number fi...

Страница 14: ...S140 2 XLS120 VeriFire Tools In the General II screen Fig 12 VeriFire Tools XLS140 2 XLS120 Leave the Display and Control Center box unchecked in the XLS140 2 and XLS120 service Local Control When the XLS3000 in network display mode or the XLS NCA2 is acting as a subsidiary device that is it is not part of an ACU LOC or CCS its local control setting must be disabled Panel Set Local Mode to NO Fig ...

Страница 15: ... consistent throughout a system XLS3000 XLS NCA2 This field allows the programmer to define the panel s relative fire and MN priority The priority may be set at the panel See Fig 17 or in VeriFire Tools See Fig 18 Panel Navigate through the PanelSettings menu pressing the More softkey until MN PRIORITY OVER FIRE appears Press the softkey next to this selection until the appropriate setting appears...

Страница 16: ...Second button Level 2 always pages Inputs 7 9 or 11 depending on whether the XLS DVC is an ACU LOC or CCS Third button Level 3 always pages Input 13 Input Categories are Fire MN General and MN Active Tone When ACU LOC CCS or Subsidiary is selected as a mode Level 1 inputs default to the MN category and Level 2 inputs default to the Fire category MN Active Tone is a category it is assigned to a seq...

Страница 17: ...prioritize a network XLS DVC over the local XLS DVC reassign the priority for the Network Paging rows to a lower number and therefore a higher priority than that of the Local Paging rows In systems that implement multiple network audio sources the priority of the network sources will be determined by the priority assigned to the active input on the network source For example an XLS DVC that is sen...

Страница 18: ...e Point Characteristics Latchi ng Y yes N no Activate s CBE Device Function ECS MN MONIT OR MN Alarm Y Y Mass Notification alarm monitoring device ECS MN SUPT MN Super visory N Y Indicates tracking supervisory condition ECS MN SUPL MN Super visory Y Y Indicates latching supervisory condition ECS MN TROU BLE MON Troubl e N N Generates a trouble for both short and open circuit conditions Monitor mod...

Страница 19: ...l be suppressed in the panel that made the match Logic equations will be activated ZF21 MN Supervisory Zone Activates for local events when there is an MN supervisory in the system ZF22 MN Trouble Zone MN Trouble Zone Activates for local events when an MN trouble occurs The MN Special Function Zones are available as indicated in Table 11 Table 11 MN Special Function Zone Availability MN Active Ton...

Страница 20: ...mple MN has the highest priority and the MN Active Tone Category has been assigned to Sequence 2 the MN Active Tone It has been assigned a priority of 8 just below the MN Category inputs and above the Fire Category inputs Fig 26 Assign Priority to the MN Active Tone Sequence Create a logic zone that will activate if a ZF20 MN alarm comes in from any MN mapped node 1 Select OR as the function 2 Sel...

Страница 21: ...ig 27 Map the MN Active Tone Sequence to a Logic Zone In the PAM Programming Service add the Logic Zone created in Fig 27 above to the entire MN Active Tone Input row Input 32 Sequence 2 in this example Fig 28 Map the MN Active Tone Sequence to a Logic Zone ...

Страница 22: ... sequences and pages that come below it in priority until a fire reset clears the MN Active Tone NOTE MN or OTHER sequences and pages will not be suppressed for fire alarms without the Fire Active Tone properly prioritized in the PAM In the Audio Message Prog Service of VeriFire Tools DVC programming build the Fire Active Tone audio sequence on the Message Sequences tab Fig 29 Creating a Fire Acti...

Страница 23: ...he Fire Category inputs and above the MN Category inputs Fig 30 Assign Priority to the Fire Active Tone Sequence Map a common general zone for example Z1 to all the PAM points designated as the Fire category 1 Select OR as the function 2 Select Zone Z1 3 Close the equation In this example ZL3 is the Logic Zone programmed for activation of the Fire Active Tone Fig 31 Map the Fire Active Tone Sequen...

Страница 24: ... Add the Fire Active Tone logic equation to fire PAM points DVC RPU SET THE PAGING LEVELS In the COMMON RPU Prog Service screen in DVC programming Select the Paging Levels to enable the ALL CALL buttons in the second column of the DVC KD Addressing DVC RPU address must equal the LCD 160 address See LCD 160 on page 25 Fig 33 Set Paging Levels VeriFire Tools ...

Страница 25: ...CD 160 must be address 5 CAUTION ADDRESSING IS CRITICAL TO COMMAND OPERATIONS THE DVC RPU ADDRESS ON THE DIGITAL AUDIO LOOP MUST EQUAL THE LCD 160 ADDRESS ON THE RDP BUS Fig 35 Block Diagram Illustrating Address Link MN Annunciator Programming DEDICATED MN ALARM ANNUNCIATOR A DVC KD LED annunciator programmed as a dedicated MN alarm annunciator is required for each XLS120 XLS140 2 XLS3000 and XLS ...

Страница 26: ...NCA2 Does not activate the alarm relays Displays MN ALARM in the upper left corner of the display of XLS3000 XLS NCA2 and LCD 160 as well as other information specific to the alarm Activates Special Function Zone ZF20 MN alarm zone Suppresses fire alarms if MN has the highest priority refer to Output Event Suppression on page 29 Activates General Pending type code at the XLS3000 Does not activate ...

Страница 27: ... will not resound Displays MN SUPERVISORY in the upper left corner of the display as well as other information specific to the supervisory message for the XLS3000 XLS NCA2 LCD 160 Is a latching or tracking event based on Type ID see Table 9 The control panel will not return to normal operation until the supervisory condition is corrected and the control panel is reset Resets require two presses of...

Страница 28: ... picked up by participating MN nodes and the MN event will automatically clear from their local systems The EBI Workstation MN and FIRE Reset operation is described in installation instruction 95 8548 MN AND FIRE EVENTS PRESENT IN SYSTEM MN is the highest priority When both MN and fire events are present in the system and MN events have the highest priority press the panel s reset button to Reset ...

Страница 29: ... and Z12 are dedicated fire zones Z2 is an MN alarm zone If Z10 Z11 or Z12 is active and Z2 is not ZL2 will go active If Z10 Z11 or Z12 and Z2 are active ZL2 will go inactive and any outputs mapped to it may be suppressed Outputs All outputs used for MN must be programmed as non silenceable This includes those outputs that are shared between MN and other events such as Fire Dedicated Fire outputs ...

Страница 30: ...it is wired to removing control when the panel does An MN page at an XLS DVC will Give control to its assigned XLS NCA2 or XLS3000 which will maintain its Controls Active LED on and maintain control functions as unblocked Turn off Control Active LEDs and block control functions at all other panels and annunciators An MN page at a DVC RPU will Give control to its assigned LCD 160 which will maintai...

Страница 31: ...mation and Control Solutions office as listed in the phone book or contact a regional office as shown at the end of this document It is recommended that the system test frequency is once per year HONEYWELL IS A REGISTERED TRADEMARK AND ENTERPRISE BUILDINGS INTEGRATOR IS A TRADEMARK OF HONEYWELL INC Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley ...

Отзывы: