Installation
AutoSet 1500 User Manual
16
Ch 2
1088500
Connecting AC wires to power source
Connect AC wires from the AutoSet control to your AC power source only when you're
finished connecting all wiring inside the control box. If you need to install a zero cam or
plan to make other optional connections to AutoSet (remote reset switch and chart
recorder), go to the sections that follow and do this wiring first. Then connect AC power.
WARNING
PREVENT SHOCK
Make sure main power is off when you connect AutoSet to
main power source.
WARNING
Make sure power supply cover is in place
Make sure you replaced the power supply cover (which fits
over the power supply near the top of the enclosure). The
power supply cover helps prevent shock if you're working
inside the box with power on.
What you should see when power is turned on
After connecting AutoSet to a power source, set switch S2 to "zero", close the cover, and
turn power on. The top LOAD displays should show 0's or other numbers. The bottom
setpoint displays should show either numbers, dashes (- - -) or the numbers "HI" or "LO".
It does not matter what at this point.
If the displays are not active,
turn off power to AutoSet.
Re-check connections for power
and strain links. Make sure the voltage selector switch is set correctly . Then turn power
on again. Make sure that the displays are active as noted above. If not, and AutoSet has
power, call Data Instruments or your sales representative.
Once all connections are made
Once you've made all connections and AutoSet has power, you are ready to begin
calibration. Calibration is covered in Chapter 3. Go to Chapter 3 and begin the calibration
procedure.