System Communication and Operation
6-11
Various System Trouble Displays
Alpha Display
Fixed Disp.
Meaning
ALARM CANCELED
CA
Appears if an exit or interior zone contained a fault during closing
at the time the Exit Delay ended (e.g., exit door left open and the
zone was not auto-bypassed), but the system was disarmed during
the Entry Delay time. The alarm sounder and keypad sounder
stop when the system is disarmed. No message will be transmitted
to the central station.
EXIT ALARM
EA
will appear when the Exit Delay ends if an exit or interior zone
contained a fault during closing and the zone was not auto-
bypassed. The alarm sounder and keypad sound continuously
until the system is disarmed (or timeout occurs). An “Exit Alarm”
message is sent to the central station if enabled in field *59. Also
results if an alarm from an exit or interior zone occurs within 2
minutes after the end of an Exit Delay if exit alarm is enabled in
field *59.
CHECK CHECK
indicates that a problem exists with the displayed zone(s) and
requires attention.
ALARM 1xx
1xx
indicates that communication between control and a zone
expander or wireless
FAULT 1xx
1xx
receiver is interrupted, where “xx” is the device address. Check the
wiring and
CHECK 1xx
1xx
DIP switch settings on the units.
91
If field *199 is set to “1,” all ECP module problems are displayed
as “91.”
If there are wireless sensors in the system, the Check condition
may also be caused by some change in the environment that
prevents the receiver from receiving signals from a particular
sensor.
TAMPER 1xx
1xx
Appears when a tamper switch at the device address shown has
been activated while system is disarmed.
TMPR_ARMD 1xx
Appears when a tamper switch at the device address shown has
been activated while system is armed.
SYSTEM LO BAT
BAT
with no zone number indicates that the system's main standby
battery is weak.
LO BAT
BAT
with a zone number and a once-per-minute beeping at the keypad
indicates that a low-battery condition exists in the wireless sensor
displayed (zone “00” indicates a wireless keypad). If the battery is
not replaced within 30 days, a “CHECK” display may occur.
Note: Some wireless sensors contain a non-replaceable long-life
battery which requires replacement of the entire unit at the end of
battery life (e.g., 5802 and 5802CP).
TELECOM FAULT
94
Telephone Line Failure, indicates that a monitored telephone line
(if programmed in field *92) has been cut or disconnected.
Depending on how the system was programmed, the keypad may
also produce a trouble sound, and the external sounder may be
activated. Silence by entering installer code + OFF.
Содержание ADEMCO VISTA-12A
Страница 2: ...ii ...
Страница 26: ...Installation and Setup Guide 2 20 ...
Страница 82: ...Installation and Setup Guide 5 26 ...
Страница 98: ...Installation and Setup Guide 7 4 ...
Страница 104: ...Installation and Setup Guide 8 6 ...
Страница 108: ...Installation and Setup Guide 9 4 ...