Mounting and Wiring the Control
2-9
Smoke Detectors
4-Wire Smoke Detectors
Connect 4-wire smoke detectors (up to 16,
depending on detector current drain) to any
zone from 2-8 as shown on the next page. This
control does not automatically reset power to
4-wire smoke detector zones, so you must use a
relay (e.g., 4204, 4229), or on-board trigger 17
to reset power (also required for fire
verification). Do this by programming the
designated relay/trigger as zone type 54 (fire
zone reset); see On-Board Trigger section for
other information.
Notes
••••
Fire
Verification
(zone type 16):
The control
panel will “verify” a fire alarm by resetting the
smoke detectors after the first alarm trigger,
and then waiting 90 seconds for a second
alarm trigger. If the smoke detector does not
trigger again, the control will disregard the
first trigger, and no alarm signal will occur.
This feature eliminates false alarms from
smoke detectors due to electrical or physical
transients.
•
Maximum
current for trigger 17 output for 4-
wire smoke detectors is 300mA.
Figure 6. 4-Wire Smoke Detector Connections
+
+
2000
OHMS
EOLR
HEAT
DETECTOR
RED
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
VIOLET
AUX PWR
OUTPUT
TERMINALS
5
4
_
_
+
_
BLK
_
+
4_wiresmk-007-V0
TO ZONE TERM. ( )
TO ZONE TERM. ( )
RELAY
CONTACT OPENS
MOMENTARILY UPON
FIRE ALARM RESET
PROGRAM
RELAY
AS ZONE
TYPE 54
(FIRE ZONE
RESET)
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
N.C.
N.O.
4-Wire Smoke Detector Using Relay for Power Reset
+
2000
OHMS
EOLR
HEAT
DETECTOR
RED
VIOLET
AUX PWR
5
_
+
_
BLK
_
+
4_wiresmk-008-V0
4-WIRE SMOKE
OR COMBUSTION
DETECTOR
( )
( )
+
_
TO ZONE TERM. ( )
TO ZONE TERM. ( )
TO OUTPUT 17
PROGRAM OUTPUT 17
FOR "OUT NORM
LOW" = YES IN 79 MENU
MODE AND AS ZONE
TYPE 54 IN
80 MENU MODE
EOL
POWER
SUPERVISION
RELAY MODULE
A77-716B.
USE N.O.
CONTACT,
WHICH CLOSES
WHEN POWER
IS APPLIED.
N.O.
4-Wire Smoke Detector Using Output 17 for Power Reset