background image

 

 

 

 

FCC STATEMENT 

Note:

 This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 

15 of the FCC Rules.  These limits are designed to provide reasonable protection against harmful interference when 
the equipment is operated in a commercial environment.  
This equipment generates, uses, and can radiates radio frequency energy and, if not installed and used in accordance 
with the instruction manual, may cause harmful interference to radio communications.  Operation of this equipment in a 
residential area is likely to cause harmful interference in which case the user will be required to correct the interference 
at his own expense. 

 

 

FCC STATEMENT 

This device complies with Part 15 of the FCC Rules, and RSS 210 of IC.  Operation is subject to the following two 
conditions: (1) This device may not cause harmful interference (2) This device must accept any interference received, 
including interference that may cause undesired operation. 
 

 

The user shall not make any changes or modifications to the equipment unless authorized by the Installation 
Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the 
equipment. 
 

 
 

 
 

 

 

DOCUMENTATION AND ONLINE SUPPORT 

For the latest documentation and online support information, please go to: 

http://www.security.honeywell.com/hsc/resources/MyWebTech/

 

WARRANTY 

For the latest warranty information, please go to: 

http://www.security.honeywell.com/hsc/resources/wa/ 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

 

Ê800-04433V1"Š 

800-04433V1  12/10  Rev. A  

 

 

2 Corporate Center Drive, Suite 100,  

P.O. Box 9040, Melville, NY  11747 

Copyright 

 2010 Honeywell International Inc. 

www.honeywell.com/security 

 

Содержание 800-04433V1

Страница 1: ... rc ci ia al l F Fi ir re e C Co om mm mu un ni ic ca at to or r I In ns st ta al ll la at ti io on n a an nd d S Se et tu up p G Gu ui id de e iPGSM COM Commercial Fire Communicator RADIO TROUBLE LOW BATT AC ON AC LOSS 800 04433V1 12 10 Rev A ...

Страница 2: ...t 2 STEP 3 Determine the Signal Strength and Select a Location 3 STEP 4 Mount and Wire 3 STEP 5 Program the Communications Module 6 STEP 6 Configure the Fire Panel 7 STEP 7 Test the System 7 iPGSM COM Trouble Detection Information 7 Dialer Capture Module Information 8 LED Board Information 8 PowerBoost1 Module Information 9 iGSM Communications Module Information 10 iPGSM COM Specifications 11 Wiri...

Страница 3: ...is reported as 04 The installer must inform the central station of this condition Operation The iPGSM COM replaces the fire panel s POTS communications path When an event occurs the fire panel goes off hook to dial the central station The iPGSM COM detects the off hook condition and provides the fire panel with a dial tone When the fire panel detects the dial tone it begins dialing the central sta...

Страница 4: ...nitoring station Communication Module s MAC ID and MAC CRC number located on outside of box and inside of the module Note The iPGSM COM comes with a SIM Subscriber Identity Module that needs to be activated 1 To activate the SIM log into the AlarmNet Direct website and choose SIM Activation Status then enter the required information Click Activate SIM 2 Setup the customer account by choosing Progr...

Страница 5: ...ute for the module to initialize 4 Position the assembly near a suitable mounting position and observe the RSSI display 5 Look for a mounting position that yields at least 3 bars lit solid Four or five bars are better 6 Verify the signal strength remains steady for a few minutes then mark that mounting position Disconnect the battery STEP 4 Mount and Wire For UL compliant installations refer to th...

Страница 6: ...ity power ground typically a cold water pipe to the cabinet s ground post Ensure all ground connections are tight 8 Connect the Ethernet cable and the Telco 1 and Telco 2 lines If you choose to use an optional Cabinet Tamper Switch if the control panel supports it mount and wire it Note The Ethernet cable Telco 1 Telco 2 lines and the optional cabinet Tamper Switch if used must be run through cond...

Страница 7: ...RSSI M0 M1 GPRS IBS 7720P PROGRAMMER PORT NOT FOR TELEPHONE SERVICE USE BATTERY ANTENNA MOUNTING ADAPTER CONDUIT WALL OUTLET BOX K14358 CABINET DOOR PowerBoost1 TO FACILITY GROUND ANTENNA NUT WASHER 50 OHM CABLE LED Display TRANSFORMER N8167 1 5 ON 2 3 4 CONDUIT FUSE not supplied BATTERY 7AH Dialer Capture Module Telco 1 Telco 2 ECP Tip 2 Ring 2 ZN EOL EOL ZN PWR GND Tip 1 Ring 1 Data Out Data In ...

Страница 8: ...Then press Y to the Exit Prog Mode prompt Upon exiting the root file is updated to log the changes made A message is displayed telling the user that this step is being executed When complete the message DONE is displayed to indicate the file was successfully uploaded Note If critical configuration changes were made such as the mode of operation the communications module will reset to ensure that t...

Страница 9: ...x then close and lock the cabinet cover 2 Refer to the fire panel s installation operation guide the testing procedure 3 Notify the monitoring station that a test will be conducted Test the system to ensure it is operating iPGSM COM Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the iPGSM COM and Telco 2 is used by the iPGSM COM to report faults t...

Страница 10: ...is lost iPGSM COM 004 V0 Dialer Capture Module Telco 1 Telco 2 ECP Tip 2 Ring 2 ZN EOL EOL ZN PWR GND Tip 1 Ring 1 Data Out Data In 12V In GND RED GREEN LED Board Information Panel Status LED Indicator RADIO TROUBLE Yellow ON when radio trouble is present Buzzer Upon loss of AC power this will beep once every 10 seconds LOW BATTERY Yellow ON when battery is low Yellow not used AC LOSS Yellow ON wh...

Страница 11: ...r more trouble conditions exist such as overload output supervision ground fault or charger failure Notes If AC power is lost and the battery voltage falls below 10v the module s output voltage will be turned off The output power is turned back on when AC power is restored You must use the DIP switch settings shown below iPGSM COM 003 V0 TROUBLE LED INDICATOR PowerBoost 1 1 5 ON 2 3 4 Confiure DIP...

Страница 12: ...per Switch GRN YEL RED ECP OFF OFF Zone NOT USED ON OFF 4204 NOT USED OFF ON 2 4204 NOT USED ON ON MODULE S RECEIVED SIGNAL STRENGTH RSSI When the Mode Switch is NOT depressed LED 1 will illuminate red The remaining LEDs indicate RSSI Received Signal Strength MODULE S OPERATION MODE When the Mode Switch IS depressed LED 1 will be OFF LEDs 2 and 3 indicate the module s communication mode with the D...

Страница 13: ... 3 4 inches Height 14 7 8 inches Depth 3 inches Transformer N8167 Primary 120VAC 60Hz 0 50A Secondary 18VAC 50VA Battery 12V 7Ah sealed lead acid type not supplied Use a Honeywell 712BNP Yuasa NP7 12 or equivalent Battery Charging Current maximum 1A Supervision The AC power backup battery IP communications and GSM communications are monitored ...

Страница 14: ...iPGSM COM Commercial Fire Communicator Installation and Setup Guide 12 NOTES ...

Страница 15: ...ROUBLE ACTIVE AC PowerBoost1 DC DC OUT DC OUT N U DC OUT OUT RX TX GND RED WHT LO BATT VIO OUTPUT 1 OUTPUT 2 N U RADIO TROUBLE 1 5 ON 2 3 4 Buzzer Buzzer AC LOSS not used CONDUIT WALL OUTLET BOX K14358 ANTENNA GRN YEL STATUS MESSAGE FAULT 7720P PROGRAMMER PORT RED BLK YEL GRN BLK RED CABINET DOOR FUSE GRA OPTIONAL CABINET TAMPER SWITCH BLK BATTERY BATTERY 7AH CONDUIT GRA AC ON To Facility Ground n...

Страница 16: ...of the FCC Rules and RSS 210 of IC Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User s Manual Unauthorized ch...

Отзывы: