iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide

 

 

– 

10

 – 

iGSM Communications Module Information 

 

TB 1

6
7
8

5

10
11

9

2
3
4

1

PRIMARY POWER: 9 - 16.5 VAC
CURRENT: 900mA PEAK, 70mA STANDBY
BATTERY: 8V. 3.1 AHr FOR 24 Hr BACKUP

FCC:XXXXXXXXXX    IC: YYYYYYYYYY

RSSI

M0

M1

GPRS

IBS

iPGSM-COM-002-V0

RSSI / Mode
and
status LEDs

ON – Message transmission pending.
QUICK PERIODIC BLINK – Normal.
FAST BLINK – Message waiting for network ACK.
SLOW BLINK – Idle power abnormal.
SLOW BLINK – In unison with green LED,
                          registratration in progress.

Ethernet Link/Activity
GREEN 

ON  –  Ethernet Link detected.
OFF – No link detected.
FAST BLINK – Transmitting/Receiving Data.

Link Speed
GREEN 

Network Collision
YELLOW

Note:

 If all LEDs FAST BLINK in unison with

          the RSSI LEDs this indicates a Hardware Error.

ON – No contact with network.
OFF – Normal.
SLOW BLINK – Loss of communication with the

                       Dialer Capture Module

 (ECP fault).

ON – NOT registered with AlarmNet.
OFF – Registered with AlarmNet.
FAST BLINK – Download session with Compass
                         in progress.
SLOW BLINK – In unison with yellow LED,
                          registration in progress.

Mode
Switch

Tamper

Switch

GRN

YEL

RED

ECP                                                          OFF                                           OFF

Zone  (NOT USED)                                   ON                                            OFF

4204  (NOT USED)                                  OFF                                            ON

2 - 4204  (NOT USED)                              ON                                             ON

MODULE'S RECEIVED SIGNAL STRENGTH (RSSI)

When the 

Mode Switch

 is NOT depressed, LED 1 will illuminate red.

The remaining LEDs indicate RSSI (Received Signal Strength).

MODULE'S OPERATION MODE

When the 

Mode Switch

 IS depressed, LED 1 will be OFF.

   LEDs 2 and 3 indicate the  module's communication mode with the Dialer Capture Module.

Mode                                LED 2 (yellow)                           LED 3 (yellow

)

MODULE'S STATUS

When the 

Mode Switch

 IS depressed, LED 1 will be OFF.  

  LEDs 4, 5, and 6 indicate the module's Status.

FAST BLINK - Module registered, second

site available, excellent signal strength.

LED 4 (green)                     LED 5 (green)                                  LED 6 (green)

ON - Connected to

Internet.

ON - Module registered, no second

site available.

ON - GPRS service

available.

OFF - No GPRS service

available

OFF - Module not registered with

network carrier.

FAST BLINK - GPRS in

use.

SLOW BLINK - Module registered, second

site available, and low signal strength.

NORMAL BLINK - Module registered, second
site available, acceptable signal strength.

OFF - Not connected

to Internet.

7720P
Programmer
Port

BLINKING – Network collision detected.
OFF – Normal.

ON – 100 MB/S link to Internet.
OFF – 10 MB/S link to Internet.

FAST BLINK – No network contact AND loss of communi-
                        cation with the 

Dialer Capture Module

.

 

 

Содержание 800-04433V1

Страница 1: ... rc ci ia al l F Fi ir re e C Co om mm mu un ni ic ca at to or r I In ns st ta al ll la at ti io on n a an nd d S Se et tu up p G Gu ui id de e iPGSM COM Commercial Fire Communicator RADIO TROUBLE LOW BATT AC ON AC LOSS 800 04433V1 12 10 Rev A ...

Страница 2: ...t 2 STEP 3 Determine the Signal Strength and Select a Location 3 STEP 4 Mount and Wire 3 STEP 5 Program the Communications Module 6 STEP 6 Configure the Fire Panel 7 STEP 7 Test the System 7 iPGSM COM Trouble Detection Information 7 Dialer Capture Module Information 8 LED Board Information 8 PowerBoost1 Module Information 9 iGSM Communications Module Information 10 iPGSM COM Specifications 11 Wiri...

Страница 3: ...is reported as 04 The installer must inform the central station of this condition Operation The iPGSM COM replaces the fire panel s POTS communications path When an event occurs the fire panel goes off hook to dial the central station The iPGSM COM detects the off hook condition and provides the fire panel with a dial tone When the fire panel detects the dial tone it begins dialing the central sta...

Страница 4: ...nitoring station Communication Module s MAC ID and MAC CRC number located on outside of box and inside of the module Note The iPGSM COM comes with a SIM Subscriber Identity Module that needs to be activated 1 To activate the SIM log into the AlarmNet Direct website and choose SIM Activation Status then enter the required information Click Activate SIM 2 Setup the customer account by choosing Progr...

Страница 5: ...ute for the module to initialize 4 Position the assembly near a suitable mounting position and observe the RSSI display 5 Look for a mounting position that yields at least 3 bars lit solid Four or five bars are better 6 Verify the signal strength remains steady for a few minutes then mark that mounting position Disconnect the battery STEP 4 Mount and Wire For UL compliant installations refer to th...

Страница 6: ...ity power ground typically a cold water pipe to the cabinet s ground post Ensure all ground connections are tight 8 Connect the Ethernet cable and the Telco 1 and Telco 2 lines If you choose to use an optional Cabinet Tamper Switch if the control panel supports it mount and wire it Note The Ethernet cable Telco 1 Telco 2 lines and the optional cabinet Tamper Switch if used must be run through cond...

Страница 7: ...RSSI M0 M1 GPRS IBS 7720P PROGRAMMER PORT NOT FOR TELEPHONE SERVICE USE BATTERY ANTENNA MOUNTING ADAPTER CONDUIT WALL OUTLET BOX K14358 CABINET DOOR PowerBoost1 TO FACILITY GROUND ANTENNA NUT WASHER 50 OHM CABLE LED Display TRANSFORMER N8167 1 5 ON 2 3 4 CONDUIT FUSE not supplied BATTERY 7AH Dialer Capture Module Telco 1 Telco 2 ECP Tip 2 Ring 2 ZN EOL EOL ZN PWR GND Tip 1 Ring 1 Data Out Data In ...

Страница 8: ...Then press Y to the Exit Prog Mode prompt Upon exiting the root file is updated to log the changes made A message is displayed telling the user that this step is being executed When complete the message DONE is displayed to indicate the file was successfully uploaded Note If critical configuration changes were made such as the mode of operation the communications module will reset to ensure that t...

Страница 9: ...x then close and lock the cabinet cover 2 Refer to the fire panel s installation operation guide the testing procedure 3 Notify the monitoring station that a test will be conducted Test the system to ensure it is operating iPGSM COM Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the iPGSM COM and Telco 2 is used by the iPGSM COM to report faults t...

Страница 10: ...is lost iPGSM COM 004 V0 Dialer Capture Module Telco 1 Telco 2 ECP Tip 2 Ring 2 ZN EOL EOL ZN PWR GND Tip 1 Ring 1 Data Out Data In 12V In GND RED GREEN LED Board Information Panel Status LED Indicator RADIO TROUBLE Yellow ON when radio trouble is present Buzzer Upon loss of AC power this will beep once every 10 seconds LOW BATTERY Yellow ON when battery is low Yellow not used AC LOSS Yellow ON wh...

Страница 11: ...r more trouble conditions exist such as overload output supervision ground fault or charger failure Notes If AC power is lost and the battery voltage falls below 10v the module s output voltage will be turned off The output power is turned back on when AC power is restored You must use the DIP switch settings shown below iPGSM COM 003 V0 TROUBLE LED INDICATOR PowerBoost 1 1 5 ON 2 3 4 Confiure DIP...

Страница 12: ...per Switch GRN YEL RED ECP OFF OFF Zone NOT USED ON OFF 4204 NOT USED OFF ON 2 4204 NOT USED ON ON MODULE S RECEIVED SIGNAL STRENGTH RSSI When the Mode Switch is NOT depressed LED 1 will illuminate red The remaining LEDs indicate RSSI Received Signal Strength MODULE S OPERATION MODE When the Mode Switch IS depressed LED 1 will be OFF LEDs 2 and 3 indicate the module s communication mode with the D...

Страница 13: ... 3 4 inches Height 14 7 8 inches Depth 3 inches Transformer N8167 Primary 120VAC 60Hz 0 50A Secondary 18VAC 50VA Battery 12V 7Ah sealed lead acid type not supplied Use a Honeywell 712BNP Yuasa NP7 12 or equivalent Battery Charging Current maximum 1A Supervision The AC power backup battery IP communications and GSM communications are monitored ...

Страница 14: ...iPGSM COM Commercial Fire Communicator Installation and Setup Guide 12 NOTES ...

Страница 15: ...ROUBLE ACTIVE AC PowerBoost1 DC DC OUT DC OUT N U DC OUT OUT RX TX GND RED WHT LO BATT VIO OUTPUT 1 OUTPUT 2 N U RADIO TROUBLE 1 5 ON 2 3 4 Buzzer Buzzer AC LOSS not used CONDUIT WALL OUTLET BOX K14358 ANTENNA GRN YEL STATUS MESSAGE FAULT 7720P PROGRAMMER PORT RED BLK YEL GRN BLK RED CABINET DOOR FUSE GRA OPTIONAL CABINET TAMPER SWITCH BLK BATTERY BATTERY 7AH CONDUIT GRA AC ON To Facility Ground n...

Страница 16: ...of the FCC Rules and RSS 210 of IC Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User s Manual Unauthorized ch...

Отзывы: