iPGSM-COM Commercial Fire Communicator – Installation and Setup Guide 

 

 3 

– 

STEP 3 – Determine the Signal Strength and Select a Location 

IMPORTANT - Do Not mount this device outdoors.  
When choosing a suitable mounting location, understand that signal strength is very important for proper 
operation.  For most installations using the supplied antenna, mounting the unit as high as practical, and 

avoiding large metal components provides adequate signal strength for proper operation.  
You will use the iGSM Communications Module to determine signal strength in order to find a suitable 
mounting location.  

Note:

 If the SIM is already activated, the RSSI signal strength indicators will indicate signal 

strength.  
If the SIM has not been activated, the firmware in the communications module enables it to 
communicate with the cellular network towers (without the SIM being activated) so that 

signal strength measurements can be determined.  In this case, you can display the signal 
strength by simultaneously pressing the MODE and TAMPER switches.  

1.

 

For this procedure you will need a fully charged 12V battery. 

2.

 

Attach the Antenna (see illustration on page 5).   

3.

 

Temporarily wire the battery's negative [–] terminal to TB1–4 on the iGSM communications module, 

then wire the battery's plus [+] terminal to TB1–2 on the communications module.  Wait about one 

minute for the module to initialize. 

4.

 

Position the assembly near a suitable mounting position and observe 

the RSSI display.   

5.

 

Look for a mounting position that yields at least 3 bars lit solid.  Four 

or five bars are better. 

6.

 

Verify the signal strength remains steady for a few minutes, then mark that mounting position.  
Disconnect the battery. 

 

STEP 4 – Mount and Wire 

 

 

For UL compliant installations, refer to the topic on 

UL Compliance

 in this manual. 

 

For Dry/Indoor use only. 

 

Unless otherwise specified, use 18AWG or larger wire. 

 

External cabinet wiring may be routed in conduit if desired. 

 

This communicator comes partially assembled with all the components mounted except the PowerBoost1 

and the Antenna.  To protect certain components on the PowerBoost1, it is shipped un-mounted but fully 
wired.  

1.

 

Remove knockouts from cabinet to accommodate the power input wires, and wiring to the control 

panel.  Then mount the cabinet securely to the wall using 4 screws or bolts.  Use mounting screws or 
bolts that are suitable for the material being anchored to. 

2.

 

Ensure the cabinet door lock is installed. 

3.

 

Carefully remove the packaging material that surrounds the PowerBoost1. 

4.

 

Mount the PowerBoost1 on the three unused standoffs.  Use the

 plastic screw

 (prevents shorting) 

to secure the upper right corner of the PowerBoost1 and the two metal screws and lock washers to 

fasten the left side of the circuit board.  Ensure the two lock washers are between the circuit board 
and the head of the two metal screws.  

3 BARS MIN.

G

Y

G

G

R

Y

7845i-GSM-025-V0

Содержание 800-04433V1

Страница 1: ... rc ci ia al l F Fi ir re e C Co om mm mu un ni ic ca at to or r I In ns st ta al ll la at ti io on n a an nd d S Se et tu up p G Gu ui id de e iPGSM COM Commercial Fire Communicator RADIO TROUBLE LOW BATT AC ON AC LOSS 800 04433V1 12 10 Rev A ...

Страница 2: ...t 2 STEP 3 Determine the Signal Strength and Select a Location 3 STEP 4 Mount and Wire 3 STEP 5 Program the Communications Module 6 STEP 6 Configure the Fire Panel 7 STEP 7 Test the System 7 iPGSM COM Trouble Detection Information 7 Dialer Capture Module Information 8 LED Board Information 8 PowerBoost1 Module Information 9 iGSM Communications Module Information 10 iPGSM COM Specifications 11 Wiri...

Страница 3: ...is reported as 04 The installer must inform the central station of this condition Operation The iPGSM COM replaces the fire panel s POTS communications path When an event occurs the fire panel goes off hook to dial the central station The iPGSM COM detects the off hook condition and provides the fire panel with a dial tone When the fire panel detects the dial tone it begins dialing the central sta...

Страница 4: ...nitoring station Communication Module s MAC ID and MAC CRC number located on outside of box and inside of the module Note The iPGSM COM comes with a SIM Subscriber Identity Module that needs to be activated 1 To activate the SIM log into the AlarmNet Direct website and choose SIM Activation Status then enter the required information Click Activate SIM 2 Setup the customer account by choosing Progr...

Страница 5: ...ute for the module to initialize 4 Position the assembly near a suitable mounting position and observe the RSSI display 5 Look for a mounting position that yields at least 3 bars lit solid Four or five bars are better 6 Verify the signal strength remains steady for a few minutes then mark that mounting position Disconnect the battery STEP 4 Mount and Wire For UL compliant installations refer to th...

Страница 6: ...ity power ground typically a cold water pipe to the cabinet s ground post Ensure all ground connections are tight 8 Connect the Ethernet cable and the Telco 1 and Telco 2 lines If you choose to use an optional Cabinet Tamper Switch if the control panel supports it mount and wire it Note The Ethernet cable Telco 1 Telco 2 lines and the optional cabinet Tamper Switch if used must be run through cond...

Страница 7: ...RSSI M0 M1 GPRS IBS 7720P PROGRAMMER PORT NOT FOR TELEPHONE SERVICE USE BATTERY ANTENNA MOUNTING ADAPTER CONDUIT WALL OUTLET BOX K14358 CABINET DOOR PowerBoost1 TO FACILITY GROUND ANTENNA NUT WASHER 50 OHM CABLE LED Display TRANSFORMER N8167 1 5 ON 2 3 4 CONDUIT FUSE not supplied BATTERY 7AH Dialer Capture Module Telco 1 Telco 2 ECP Tip 2 Ring 2 ZN EOL EOL ZN PWR GND Tip 1 Ring 1 Data Out Data In ...

Страница 8: ...Then press Y to the Exit Prog Mode prompt Upon exiting the root file is updated to log the changes made A message is displayed telling the user that this step is being executed When complete the message DONE is displayed to indicate the file was successfully uploaded Note If critical configuration changes were made such as the mode of operation the communications module will reset to ensure that t...

Страница 9: ...x then close and lock the cabinet cover 2 Refer to the fire panel s installation operation guide the testing procedure 3 Notify the monitoring station that a test will be conducted Test the system to ensure it is operating iPGSM COM Trouble Detection Information Telco 1 is used for the Fire Panel to output contact ID messages to the iPGSM COM and Telco 2 is used by the iPGSM COM to report faults t...

Страница 10: ...is lost iPGSM COM 004 V0 Dialer Capture Module Telco 1 Telco 2 ECP Tip 2 Ring 2 ZN EOL EOL ZN PWR GND Tip 1 Ring 1 Data Out Data In 12V In GND RED GREEN LED Board Information Panel Status LED Indicator RADIO TROUBLE Yellow ON when radio trouble is present Buzzer Upon loss of AC power this will beep once every 10 seconds LOW BATTERY Yellow ON when battery is low Yellow not used AC LOSS Yellow ON wh...

Страница 11: ...r more trouble conditions exist such as overload output supervision ground fault or charger failure Notes If AC power is lost and the battery voltage falls below 10v the module s output voltage will be turned off The output power is turned back on when AC power is restored You must use the DIP switch settings shown below iPGSM COM 003 V0 TROUBLE LED INDICATOR PowerBoost 1 1 5 ON 2 3 4 Confiure DIP...

Страница 12: ...per Switch GRN YEL RED ECP OFF OFF Zone NOT USED ON OFF 4204 NOT USED OFF ON 2 4204 NOT USED ON ON MODULE S RECEIVED SIGNAL STRENGTH RSSI When the Mode Switch is NOT depressed LED 1 will illuminate red The remaining LEDs indicate RSSI Received Signal Strength MODULE S OPERATION MODE When the Mode Switch IS depressed LED 1 will be OFF LEDs 2 and 3 indicate the module s communication mode with the D...

Страница 13: ... 3 4 inches Height 14 7 8 inches Depth 3 inches Transformer N8167 Primary 120VAC 60Hz 0 50A Secondary 18VAC 50VA Battery 12V 7Ah sealed lead acid type not supplied Use a Honeywell 712BNP Yuasa NP7 12 or equivalent Battery Charging Current maximum 1A Supervision The AC power backup battery IP communications and GSM communications are monitored ...

Страница 14: ...iPGSM COM Commercial Fire Communicator Installation and Setup Guide 12 NOTES ...

Страница 15: ...ROUBLE ACTIVE AC PowerBoost1 DC DC OUT DC OUT N U DC OUT OUT RX TX GND RED WHT LO BATT VIO OUTPUT 1 OUTPUT 2 N U RADIO TROUBLE 1 5 ON 2 3 4 Buzzer Buzzer AC LOSS not used CONDUIT WALL OUTLET BOX K14358 ANTENNA GRN YEL STATUS MESSAGE FAULT 7720P PROGRAMMER PORT RED BLK YEL GRN BLK RED CABINET DOOR FUSE GRA OPTIONAL CABINET TAMPER SWITCH BLK BATTERY BATTERY 7AH CONDUIT GRA AC ON To Facility Ground n...

Страница 16: ...of the FCC Rules and RSS 210 of IC Operation is subject to the following two conditions 1 This device may not cause harmful interference 2 This device must accept any interference received including interference that may cause undesired operation The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User s Manual Unauthorized ch...

Отзывы: