LS10144-001SK-E
Network Management
6-6
5.
Press * to add rows, Press ENTER to edit data
Figure 6-1 Communicator Reporting (4x20 screen)
6.3
Voice Options
6.3.1
Edit Timers
1.
Enter the installer code. The panel will automatically go to the main menu.
2.
Select 6 for Network Programming.
3.
Select 7 for Voice Options.
4.
Choose Site.
5.
Select 1 for Edit Timers
6.3.1.1 Control Lockout
The Control Lockout countdown timer is set to the programmed value when an LOC gains EVS Control. The
timer starts over upon any key press at the EVS Control LOC. While the Control Lockout timer is active, an LOC
of equal priority must request EVS control. The Control Lockout timer is cleared when EVS Control is
relinquished. The Control Lockout timer does not apply to EVS Super User control.
Select Immediate/Timer/Never
Range 0-720 min/0-59 sec
6.3.1.2 Auto Reset EVS MIC Triggered Event
If the Timer is selected, the event will automatically reset after being active for the programmed time. If Event
Disabled is selected, the event will not be allowed to be activate from an LOC Station. Selecting Never will
require an emergency system reset to be performed to reset the event.
Select Never/Timer/Event Disabled, Range from 1-240 min
Содержание 6820
Страница 26: ...LS10144 001SK E Before You Begin Installation 3 4 Figure 3 1 Wire Routing Example for 6820 EVS ...
Страница 87: ...LS10144 001SK E Common Communication Link 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 119: ...LS10144 001SK E Programming Overview 8 8 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns ...
Страница 240: ......
Страница 242: ......
Страница 244: ......
Страница 246: ......
Страница 248: ......
Страница 249: ......
Страница 250: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com ...