LS10144-001SK-E
Programming
9-14
SWITCH
(cont.)
FIRE SUPER-
VISORY
Latching
Use this switch type for tamper monitoring of sprinklers and other
fire protection devices. If a contact closes, a sprinkler supervisory
event will be generated. Supervisory switches can be latching or
non-latching.
Non Latching
FIRE DRILL
System-level, non latching switch. This switch is an alternative way
of causing a fire drill. It has the same operation as the fire drill option
available from the annunciator. When the switch is activated, a fire
drill begins; when the switch is de-activated, the fire drill ends.
SILENCE
This system-level switch is an alternative way to silence the fire
system. It has the same effect as pressing the Silence key.
RESET
This system-level switch is an alternative way to reset the fire
system. It has the same effect as pressing the Reset key.
P.A.S. ACK
Positive acknowledge switch. This switch must be used in zones
programmed as Positive Alarm Sequence (see 9.3.1.2 ).
If an acknowledge switch closes when an alarm or trouble condition
is not already in progress, a trouble will occur.
You must use a UL listed normally open, momentary switch type.
The switch must be rated at 5V, 100 mA (minimum) and be used
with an EOL resistor for supervision.
ZONE AUX1
Latching
Use these switch types if you want to monitor special zone-level
conditions (such as dry contact from a remote power supply).
Non Latching
ZONE AUX2
Latching
Non Latching
SYSTEM AUX1
Latching
Use these switch types if you want to monitor special system-wide
conditions (such as dry contact from a remote power supply).
Non Latching
SYSTEM AUX2
Latching
Non Latching
DETECTOR
Used to monitor conventional 4-wire detectors, a contact closure will
generate a detector alarm event.
FIRE TAMPER
Latching
Performs identically to a supervisory switch, but will be indicated as
a tamper switch on the LCD annunciator.
Non Latching
MANUAL
RELEASE
Manual release switch
INTERLOCK
Interlock release switch input.
STATUS POINT
EVS INPUT
Latching
User also has EVS Event Number 1-8 option for EVS INPUT.
Only available when an EVS-VCM is installed in the system.
Non Latching
EVS TAMPER
Latching
Non Latching
EVS SUPER-
VISORY
Latching
Non Latching
CO DETECT
SWITCH
CO Detector Switch
CO
SUPERVISORY
DETECT SWITCH
Latching
CO Supervisory Detector Switch
Non Latching
Table 9-4 Point Programming for 6815
Type
Selection
Function
Latching Option
Comments
Содержание 6820
Страница 26: ...LS10144 001SK E Before You Begin Installation 3 4 Figure 3 1 Wire Routing Example for 6820 EVS ...
Страница 87: ...LS10144 001SK E Common Communication Link 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 119: ...LS10144 001SK E Programming Overview 8 8 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns ...
Страница 240: ......
Страница 242: ......
Страница 244: ......
Страница 246: ......
Страница 248: ......
Страница 249: ......
Страница 250: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com ...