Model 6820 / 6820-EVS Installation Manual
LS10144-001SK-E
3-3
3.5
Wiring Specifications
Induced noise (transfer of electrical energy from one wire to another) can interfere with telephone
communication or cause false alarms. To avoid induced noise, follow these guidelines:
•
Isolate input wiring from high current output and power wiring. Do not pull one multi-conductor cable for
the entire panel. Instead, separate the wiring as follows:
•
Do not pull wires from different groups through the same conduit. If you must run them together, do so for
as short a distance as possible or use shielded cable. Connect the shield to earth ground at the panel. You
must route high and low voltages separately.
•
Route the wiring around the inside perimeter of the cabinet. It should not cross the circuit board where it
could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed
circuits. See Figure 3-1 for an example.
•
High frequency noise, such as that produced by the inductive reactance of a speaker or bell, can also be
reduced by running the wire through ferrite shield beads or by wrapping it around a ferrite toroid.
SC-
L1
SLC OUT
SLC terminals
32 VDC
150 mA
0
SC+
SC-
SLC Programming Terminal
(-)
32 VDC
150 mA
0
SC+
SLC Programming Terminal
(+)
32 VDC
150 mA
SC-
L2
SLC IN
Used for Class A installations
0
SC+
Ring
Phone Line 1 Telco Ring
N/A
0
Tip
Phone Line 1 Telco Tip
Ring
Phone Line 1 Premises Ring
Tip
Phone Line 1 Premises Tip
Ring
Phone Line 2 Telco Ring
N/A
0
Tip
Phone Line 2 Telco Tip
Ring
Phone Line 2 Premises Ring
Tip
Phone Line 2 Premises Tip
P7
Data
Network
Used for SK-NIC
24 VDC
21 mA
0
High voltage
AC power Terminals
SLC loops
In/Out Terminals
POTS reporting input/output Phone line circuits, TELCO
Notification circuits
NAC 1-6
SBUS
SBUS1 In/Out Terminals, Cellular
communication
Relay circuits
Trouble, Relay 1, Relay 2 Terminals
Table 3-1: Terminal Descriptions and Electrical Specification
Terminal Label
Description
Rating
Earth
Ground
Faults
Voltage
Current
Содержание 6820
Страница 26: ...LS10144 001SK E Before You Begin Installation 3 4 Figure 3 1 Wire Routing Example for 6820 EVS ...
Страница 87: ...LS10144 001SK E Common Communication Link 5 8 Figure 5 9 Fiber Optic Wiring Single Mode Example Class A wiring ...
Страница 119: ...LS10144 001SK E Programming Overview 8 8 Figure 8 5 Example of Zone Events Mapped to Output Groups and Patterns ...
Страница 240: ......
Страница 242: ......
Страница 244: ......
Страница 246: ......
Страница 248: ......
Страница 249: ......
Страница 250: ...Silent Knight 12 Clintonville Road Northford CT 06472 1610 203 484 7161 Fax 203 484 7118 www silentknight com ...