![HomeMatic HM-LC-Sw4-DR Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/homematic/hm-lc-sw4-dr/hm-lc-sw4-dr_installation-and-operating-manual_2153739039.webp)
Installation
39
6 Installation
Refer to the relevant installation regulations
when performing installations in distribution
systems.
The circuit to the which the device and the load
will be connected has to be secured by a cable
protection switch in accordance with EN60898-
1 (tripping characteristic B or C, max. 16 A ra-
ted current, min. 6 kA interrupting rating, ener-
gy limiting class 3).
For secure operation, the device has to be ins-
talled in a power distribution panel according to
VDE 0603, DIN 43871 (low-voltage subdistribu-
tion board), DIN 18015-x. The installation must
be made on a mounting rail (DIN rail) according
to EN50022. Installation and wiring have to be
performed according to VDE 0100 (VDE 0100-
410, VDE 0100-510 etc.). Please consider the
technical connection requirements (TAB) of
your energy supplier.