Check the boxes for the report groups you wish to send using the selected account. It
is possible to send alarm events to one monitoring station, while all other events are
reported to a different monitoring station. See Section 2.5.3 for additional information
on report groups.
Protocol
– Select the desired central station reporting format, Contact ID or SIA. For a
detailed reporting summary, please see Appendix A.
Backup Report
– Check this box to enable backup reporting. You must also select
the events that you want to be reported to the backup destination, as shown above.
Backup Report is only available on Account 2 (backup to Account 1) and 4 (backup to
Account 3).
NOTE:
To comply with UL and NFPA standards, the dialer must be programmed for
backup reporting. To accomplish this, program a phone number for Phone Number 1
and Phone Number 2, and an account number for Account Number 1 and Account
Number 2. Both phone numbers must be different.
Programming the Panel
– After all programming is complete, save the project file and
then download it to the panel or network.