13
FireNET FN-DAC Digital Alarm Communicator I & O Manual - v 1.0
Figure 2.2.3 – J5 PC port on FireNET front display board
Figure 2.2.4 – Maintain a minimum.25” separation between low voltage wiring (Power Limited)
and high voltage wiring (Non-Power Limited) in the FireNET enclosure! High voltage wiring
locations are circled above (telephone lines and AC power input). The telephone line
connections must be toward the top of the enclosure.
Power Limited
Wiring –
- Ribbon Cables
- Power to FN-DAC
Non-Power Limited
Wiring –
2) AC Power
Non-Power Limited
Wiring –
1) Telephone Lines
firealarmresources.com