34
FireNET FN-DAC Digital Alarm Communicator I & O Manual - v 1.0
Site Number
– This is the phone number used to contact the FireNET panel for
remote access. See Section 4 of this manual for details.
Phone Number 1 – 4
– These are the phone numbers that the communicator will use
to report to the monitoring station(s). Phone Number 1 is used with Account 1, Phone
Number 2 with Account 2 and so on. Use a comma (,) for a three-second dialing
pause. Program phone numbers only for the accounts you plan to use.
NOTE:
To comply with UL and NFPA standards, the FN-DAC dialer may not be
programmed to call a telephone number that is call-forwarded to the DACR.
Dialing
– You may select Tone, Pulse or Both. If Both is selected, the FN-DAC
communicator will use DTMF (Touch Tone) dialing and Pulse dialing when making
multiple attempts to report an event.
Line Monitoring
– These options allow you to turn off the phone line monitoring on
one or both phone lines. Check the boxes to enable line monitoring.
NOTE
: UL and NFPA require that Line Monitoring be enabled for both phone lines.
Number of Rings before Answer
– Programmable ring counter for remote access to
the FireNET network. See Section 4 of this manual for more details.