Quick Start 4-7
© 2005 HMS Industrial Networks
AB7607 User manual
The EDS file must be registered with NetTool-DN before configuration can con-
tinue.
•
From the
Tools
menu, select
Install EDS Files
.
•
Enter the path, or browse to the location of the EDS file for the Anybus-
X.
•
Click
Open
.
•
Select the
Tools
menu option, then
Update
, and click on the network
name. The Anybus-X icon should be properly displayed on the network
screen.
Step 4: Put the Anybus-X in Idle Mode
The Anybus-X powers up in Idle mode, and is controlled by the EtherNet/IP scan-
ner through the output command register. Make sure that the module is in Idle
mode by verifying that the Anybus-X Status LED is flashing green (the LED is
solid green when the module is in Run mode). If the module is not in Idle mode,
place the connected Ethernet scanner in Idle or Program mode.
Step 5: Set the DeviceNet MAC ID
•
Right click on the Anybus-X icon and select
Device
.
•
Pull down the next menu and select
Change Node Address
.
•
Select or enter the desired MAC ID and click
Ok
.
Note:
The Anybus-X will automatically reset if a new MAC ID is entered.
Note:
When the MAC ID is changed, the Anybus-X’s I/O configuration is
cleared.