Configuration 3-7
© 2005 HMS Industrial Networks
AB7607 User manual
Note:
The Anybus-X will automatically reset after the Ethernet configuration is
downloaded from BWConfig.
Setting the IP Address with the Configuration Switch
If DHCP/BootP is not enabled or a server is not found and the Configuration
Switch is non zero, on power up the value of the switch is used to form an the IP
Address. The switch represents the binary value of the last byte in the 4 byte IP
address. In this case it is
n
.
IP address:
192.168.1.
n
Subnet mask:
255.255.255.0
Gateway address:
0.0.0.0 (No gateway set)
This is a private address and can only be used on a local intranet. In such a case a
Web Browser such as Microsoft’s Internet Explorer can be used to access the
Anybus-X’s web page which allows changing the IP Address, Subnet mask, and
GateWay address settings.
Note:
A non-zero DIP switch setting will override any other Ethernet configura-
tion that is done.
Network Duplex
The duplex setting that the module will use to
communicate on the Ethernet network.
If the network duplex is set to Auto, the mod-
ule will auto-negotiate duplex.
Half, Full, or
Auto
Modbus Timeout
The Modbus Timeout option provides a means
to detect the loss of the Modbus Scanner from
the Ethernet network. If the option is enabled,
and no Modbus requests are received within
the configured timeout period, the module
Run/Idle status will be set to Idle.
0-65000ms
Parameter
Description
Allowable
Range
Table 3-1 Ethernet Network Configuration Parameters