About the Anybus Communicator for Modbus-RTU
1-4
Configuration Switches
The configuration switches determines the basic communication settings
for the Modbus interface. Normally, these switches are covered by a plas-
tic hatch. When removing the hatch, avoid touching the circuit boards and
components. If tools are used to open the hatch, be cautious.
Note that these settings cannot be changed during runtime, i.e. the gate-
way must be restarted in order for any changes to have effect.
Node Address
Baudrate Configuration
Parity & Stop Bits
Physical Interface
Node Address
Sw. 1 Sw. 2 Sw. 3 Sw. 4 Sw. 5 Sw. 6 Sw. 7
(reserved)
OFF OFF OFF OFF OFF OFF OFF
1
OFF OFF OFF OFF OFF OFF ON
2
OFF OFF OFF OFF OFF ON
OF
...
...
...
...
...
...
...
...
126
ON
ON
ON
ON
ON
ON
OFF
127
ON
ON
ON
ON
ON
ON
ON
Baudrate
Sw. 8
Sw. 1
Sw. 2
(reserved)
OFF
OFF
OFF
1200 bps
OFF
OFF
ON
2400 bps
OFF
ON
OFF
4800 bps
OFF
ON
ON
9600 bps
ON
OFF
OFF
19200 bps (standard)
ON
OFF
ON
38400 bps
ON
ON
OFF
57600 bps
ON
ON
ON
Parity
Sw. 3
Sw. 4
(reserved)
OFF
OFF
No parity, 2 stop bits
OFF
ON
Even parity, 1 stop bit
ON
OFF
Odd parity, 1 stop bit
ON
ON
Interface Type
Sw. 5
RS-485
OFF
RS-232
ON