Chapter 10 LCD display and operating for SJ300/L300P series
(11/15)
No.
Function name
Display
Data range
216
Alarm relay output
a/b
>C036 OUT-TM
O/C-AL NC
NO
:
NO
NC
:
NC
217
Overload advance
notice signal
output mode
>CO40 OL
Mode CRT
ON(On accel. And decel,constant speed) /
CRT(Only constant speed)
218
Overload advance
notice level
>C041 OL
LEVEL 0000.0A
0.0 - 2.0*rated current (A)
219
Frequency arrival
setting for
acceleration.
>C042 ARV
ACC 0000.00Hz
0.00 - 400.00(Hz)
220
Arrival frequency
setting for
deceleration
>C043 ARV
DEC 0000.00Hz
0.00 - 400.00(Hz)
221
PID deviation
setting level
>C044 PID
LEVEL 003.0%
0.0 - 100.0(
%
)
222
Frequency arrival
for deceleration 2.
>C045 ARV
ACC2 0000.00Hz
0.00 - 400.00(Hz)
(NOTE 1)
223
Arrival frequency
setting for
deceleration 2.
>C046 ARV
DEC2 0000.00Hz
0.00 - 400.00(Hz)
(NOTE 1)
224
Over torque level
setting
(Forward-driving)
>C055 OV-TRQ
FW-V 100%
0 – 200(
%
)
(NOTE 1)
225
Over torque level
setting
(Reverse-regenerati
ng)
>C056 OV-TRQ
RV-R 100%
0 – 200(
%
)
(NOTE 1)
226
Over torque level
setting
(Reverse-driving)
>C057 OV-TRQ
RV-V 100%
0 – 200(
%
)
(NOTE 1)
227
Over torque level
setting
(Forward-regenerati
ng)
>C058 OV-TRQ
FW-R 100%
0 – 200(
%
)
(NOTE 1)
228
Thermal warning
level setting
>C061 E-THM
WARN 080%
0 – 100(
%
)
229
Alarm code
selection
>C062 AL-CODE
SELECT OFF
OFF(invalid) / 3BIT(3bit) / 4BIT(4bit)
(NOTE 1)
230
Zero speed
detection level
setting
>C063 ZS
LEVEL 000.00Hz
0.00 - 100.00(Hz)
(NOTE 1)
231 Data
command
>C070 PARAM
SELECT REM
REM(Operator) / RS485(RS485) /
OPT1(option1) / OPT2(option2)
232
Communicating
transmission speed
>C071 RS485
BAU 4800bps
TEST(Loop-back test)
2400bps,4800bps,9600bps,19200bps
233
Communication
code
>C072 RS485
ADDRESS 01
01 - 32
234 Communication
bit
>C073 RS485
BIT 7BIT
7BIT(7bit) / 8BIT(8bit)
235
Communication
parity
>C074 RS485
PARITY NO
NO(No parity name) / EVN(even parity)
ODD(odd parity