Chapter 10 LCD display and operating for SJ300/L300P series
(
3
)
Trip Monitor
How to display each of trip data is following explanation.
・
Example
In case of display last time (ERR2) trip contents.
In the display example, Factor is Over.V(Over voltage trip), frequency is
35.30Hz on tripping. Inverter status is DEC(During deceleration).
Trip Monitor
1
2
Press the key to select "ERR2".
Press the key, then move the cursor to the bottom row.
Press the key to display output current on tripping.
Press the key to display PN voltage on tripping.
2
Press the key to display accumulated time on tripping during run which time
counted from when inverter is operating.
Press the key to display accumulated time on tripping of ON time
which time is counted from when inverter is turned on.
2
2
2
In the display example, output current is 22.5A on
tripping.
In the display example, PN voltage is 395V on tripping.
In the display example, accumulated time on tripping
during run is 10 hours while inverter is turned on.
In the display example, accumulated time on tripping of ON
time is 12 hours which time is counted from when inverter
is turned on.
ERR1 OC. Accel
F 0037.00Hz ACC
ERR2 Over.V
F 0035.30Hz DEC
ERR2 Over.V
F 0035.30Hz DEC
ERR2 Over.V
Iout 0022.5A DEC
ERR2 Over.V
Vpn 0395.0V DEC
ERR2 Over.V
RUN 000010hr DEC
ERR2 Over.V
ON 000012hr DEC