Chapter 10 LCD display and operating for SJ300/L300P series
110
Instantaneous
power
failure/under-voltag
e
retry time selection
>b005 IPS
RETRY 16
16(16 times) / FREE(free)
111
Open-phase
selection
>b006 PH-FAIL
SELECT OFF
OFF(invalid) / ON(valid)
112
Frequency setting to
match
>b007 IPS
F 0000.00Hz
0.00 – 400.00 Hz
113
Electronic thermal
level
>b012 E-THM
LEVEL 0000.0A
0.2*constant current-1.20*constant current(A)
114
Electronic thermal
level (2
nd
motor)
>b212 2E-THM
LEVEL 0000.0A
0.2*constant current-1.20*constant current(A)
115
Electronic thermal
level (3
rd
motor)
>b312 3E-THM
LEVEL 0000.0A
0.2*constant current-1.20*constant current(A)
(NOTE 1)
116
1
st
electronic
thermal
characteristic
selection
>b013 E-THM
CHAR SUB
SUB(reduced characteristic) / CRT(constant
torque characteristic) / FREE(free setting)
117
2
nd
electronic
thermal
characteristic
selection
>b213 2E-THM
CHAR SUB
SUB(reduced characteristic) / CRT(constant
torque characteristic) / FREE(free setting)
(NOTE 1) SJ300 series only .
(6/15)
No.
Function name
Display
Data range
118
3
rd
electronic
thermal
characteristic
selection
>b313 3E-THM
CHAR SUB
SUB(reduced characteristic) / CRT(constant
torque characteristic) / FREE(free setting)
(NOTE 1)
119
Free electronic ther-
mal frequency 1
>b015 E-THM
F1 0000Hz
0 - 400 (Hz)
120
Free electronic ther-
mal current 1
>b016 E-THM
A1 0000.0A
0.0 - 1000.0(A)
121
Free electronic ther-
mal frequency 2
>b017 E-THM
F2 0000Hz
0 - 400 (Hz)
122
Free electronic ther-
mal current 2
>b018 E-THM
A2 0000.0A
0.0 - 1000.0(A)
123
Free electronic ther-
mal frequency 3
>b019 E-THM
F3 0000Hz
0 - 400 (Hz)
124
Free electronic ther-
mal current 3
>b020 E-THM
A3 0000.0A
0.0 - 1000.0(A)
125
Overload restriction
selection
>b021 OLOAD
1MODE ON
OFF(invalid) / ON(enabled on acceleration /
constant speed) / CRT(enabled on constant
speed) / R-OFF(enabled on acceleration /
constant speed(speed increasing at
regenerating mode))
126
Overload restriction
level
>b022 OLOAD
1LEVEL 0000.0A
0.5* rated current-2.00* rated current(A)
(NOTE 2)
127
Overload restriction
limit constant
>b023 OLOAD
1CONST 01.00
0.10 - 30.00(s)
128
Overload restriction
selection 2
>b024 OLOAD
2MODE ON
OFF(invalid) / ON(enabled on acceleration /
constant speed) / CRT(enabled on constant
speed) / R-OFF(enabled on acceleration /
constant speed(speed increasing at
regenerating mode))