Chapter 10 LCD display and operating for SJ300/L300P series
(
4
)
Function mode
(1/15)
No.
Function name
Display
Data range
1
Frequency setting
selection
>A001 F-SET
SELECT REM
TRM(terminal)/REM(operator)/RS485(RS485
)/OP1(option 1)/OP2(option 2)
2
Operation setting
selection
>A002 F/R
SELECT REM
TRM(terminal)/REM(operator)/RS485(RS485
)/OP1(option 1)/OP2(option 2)
3 Base
frequency
>A003 F-BASE
F 0060Hz
30. – Maximum frequency Hz
4
Base frequency, 2
nd
motor
>A203 2F-BASE
F 0060Hz
30. –2
nd
Maximum frequency Hz
5
Base frequency, 3
rd
motor
>A303 3F-BASE
F 0060Hz
30.- 3
rd
Maximum frequency Hz
(NOTE 1 )
6 Maximum
frequency
>A004 F-max
F 0060Hz
30 - 400 Hz
7
Maximum frequency
2
nd
motor
>A204 2F-max
F 0060Hz
30 - 400 Hz
8
Maximum frequency
3
rd
motor
>A304 3F-max
F 0060Hz
30 - 400 Hz
(NOTE 1 )
9
AT terminal
selection
>A005 AT
SELECT O/OI
O/OI(Changing of O and OI with AT terminal)/
O/O2(Changing of O and O2 with AT terminal)
10 O2
selection
>A006 O2
SELECT O2
O2(Single) /
O/OI-P(auxillary speed of O, OI) [no
reversible] /O/OI-PM(auxillary speed of O, Oi)
[reversible]
11 O
start
>A011 INPUT-O
EXS 0000.00Hz
0.00 - 400.00 Hz
12 O
end
>A012 INPUT-O
EXE 0000.00Hz
0.00 - 400.00 Hz
13 O
start
rate
>A013 INPUT-O
EX%S 000%
0 - 100
%
14 O
end
rate
>A014 INPUT-O
EX%E 100%
0 - 100
%
15 O
start
selection
>A015 INPUT-O
LEVEL 0Hz
O-EXS(external starting frequency) /
0Hz(0Hz)
16 O, OI, O2 sampling
>A016 INPUT
F-SAMP 08
1 - 30 times
17
Multi-speed
selection
>A019 SPEED
SELECT BINARY
BINARY(range is to 16 stage speed with 4
terminals)/
BIT(range is to 8 stage speed with 7 terminals)
18 Multi-speed
0
>A020 SPEED
FS 0000.00Hz
0.00
,
Starting frequency– maximum
frequency(Hz)
19
Multi-speed 0, 2
nd
motor
>A220 SPEED
2FS 0000.00Hz
0.00
,
Starting frequency– 2
nd
maximum
frequency(Hz)
20
Multi-speed 0, 3
rd
motor
>A320 SPEED
3FS 0000.00Hz
0.00
,
Starting frequency– 3
rd
maximum
frequency(Hz) (NOTE 1 )
21 Multi-speed
1
>A021 SPEED
01S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
22 Multi-speed
2
>A022 SPEED
02S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)
23 Multi-speed
3
>A023 SPEED
03S 0000.00Hz
0.00
,
Starting frequency-maximum
frequency(Hz)