Table 29:
Hint menu
Headline
Explanation
Incorrect setting of SyncLostMode
There are two explanations possible:
SyncLostMode
is set to
Block
, no time source is
configured to achieve the required accuracy. Unless a
high accuracy time source is selected, the function
dependent on high time accuracy will be blocked.
SyncLostMode
is set to
BlockOnLostUTC
, but there is no
UTC capable synch source (GPS, IRIG-B) used. Unless
a UTC capable time source is selected, the function
dependent on high time accuracy will be blocked.
Sampled value substituted
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Power grids_MU0101>
Time diff: IED vs Sampled value
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Power grids_MU0101>
Frequency diff: IED vs Sampled value
<Access Point><Hardware Module Identifier><svID>
Where the Hardware Module Identifier is the same as
given in PCM600, e.g. AP1: MU1_9201 svID: <Hitachi
Power grids_MU0101>
Wrong cycle time for PMU report
Wrong cycle time on SMAI or 3PHSUM block connected
to Phasor Report block. The SMAI or 3PHSUM block
should have same cycle time as that of Phasor Report.
PMU not connected to 3ph output
The PMU phasor report input(s) must be connected to
the 3ph output of SMAI or 3PHSUM.
Invalid value set for PMU Parameters
There are two possible error conditions:
Check if the following parameters are set correctly on
PMUREPORT:1
ReportRate
or
SvcClass
or parameter
PRIMVAL:1.
FrequencySel
is not set as 50Hz / 60Hz.
Check if the following parameters are set correctly on
PMUREPORT:1
ReportRate
or
SvcClass
or
RptTimetag
or parameter PRIMVAL:1.
FrequencySel
is not set as
50Hz / 60Hz.
Invalid phase angle reference
The selected
PhaseAngleRef
corresponds to an analog
channel that is not configured. Configure a valid
reference channel.
GOOSE is configured on a disabled port
At least one of the access points configured for GOOSE
is disabled. The port can be disabled either through
changing the access point operation to off or by
unchecking the GOOSE protocol from the access point
in the Ethernet configuration in PCM600 or LHMI.
Enable GOOSE on access points:
<Access Points>, can be any of these: AP_FRONT,
AP_1, AP_2, AP_3, AP_4, AP_5, AP_6,AP_7, AP_8
LDCM not running the application image
LDCM in <slot number> is running the factory image
instead of the application image. The factory image is
older than the required FW version and does not contain
the latest updates and fixes.
Reboot the IED. If the problem persists, update the
LDCM firmware or replace the board.
LDCM rate (2M) is not supported
The <firmware version> does not support 2M mode. Set
the LDCM to 64k bit mode.
Table continues on next page
1MRK 511 403-UEN Rev. L
Section 14
Troubleshooting
Bay control REC670
221
Commissioning manual
© 2017 - 2022 Hitachi Energy. All rights reserved
Содержание REC670
Страница 1: ...Relion 670 SERIES Bay control REC670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 28: ...22 ...
Страница 54: ...48 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 90: ...84 ...
Страница 212: ...206 ...
Страница 218: ...212 ...
Страница 232: ...226 ...
Страница 240: ...234 ...
Страница 241: ...235 ...