Section 9
Establishing connection and
verifying the IEEE C37.118/1344
communication
9.1
Overview
GUID-EFD77C28-6F7C-4277-8C7E-30E78CC8EFAD v3
The IED can support synchrophasor data communication via IEEE C37.118 and/or IEEE1344 with
maximum 8 TCP clients and 6 UDP client groups, simultaneously.
The rear OEM ports are used for IEEE C37.118/1344 communication. The same ports can also be
used for substation bus (IEC 61850-8-1) communication and process bus (IEC/UCA 61850-9-2LE)
communication where applicable.
In order to establish a connection between PMU and a TCP/UDP client (PDC client), an Ethernet
communication link (e.g. optical fiber) shall be available and the required parameters on both PMU
and the TCP/UDP client shall be set. For the purpose of this section, an Open PDC tool (PMU
Connection Tester) installed on a PC is used as the TCP/UDP client.
9.2
Setting the PMU station communication (PMU Report)
GUID-B8DCD7BA-AEBA-4977-89D4-2F18ECE34A2F v1
1.
Check the settings for the PMU Report parameters by navigating to:
Main menu /
Configuration /Communication /Station communication /phasor measurement /PMU
Report /PMUREPORT:1
1.1. Make sure that the operation of at least one PMU instance (e.g. PMU1) is
On
.
1.2. Enable sending the frequency data by setting the parameter
SendFreqInfo
to
On
.
2.
Check the operation of the required phasor channels (PHASORREPORT) by navigating to:
Main menu /Configuration /Communication /Station communication /phasor
measurement /PMU Report /PHASORREPORT:x
.
9.3
Setting the PMU station communication (PMU
configuration)
GUID-B4BA9F74-5E28-42FC-8F33-0BC98D5AE6B0 v3
To enable IEEE C37.118/1344 communication, the corresponding OEM ports must be activated. The
galvanic Ethernet front port and the rear optical ports can be used for IEEE C37.118/1344
communication.
Front port is not available in the IED’s with blank front panel. By default, AP1 is
available for engineering.
To enable IEEE C37.118/1344 synchrophasor communication:
1.
Enable communication for by navigating to:
Main menu /Configuration /Communication /
Ethernet configuration
.
1MRK 511 403-UEN Rev. L
Section 9
Establishing connection and verifying the IEEE C37.118/1344 communication
Bay control REC670
61
Commissioning manual
© 2017 - 2022 Hitachi Energy. All rights reserved
Содержание REC670
Страница 1: ...Relion 670 SERIES Bay control REC670 Version 2 2 IEC Commissioning manual ...
Страница 2: ......
Страница 28: ...22 ...
Страница 54: ...48 ...
Страница 60: ...54 ...
Страница 66: ...60 ...
Страница 90: ...84 ...
Страница 212: ...206 ...
Страница 218: ...212 ...
Страница 232: ...226 ...
Страница 240: ...234 ...
Страница 241: ...235 ...