2. Control Functions
Control functions on the module
SMGB0082 rev.1 - 07/2015
32
Pulse input type 1
a. Signal aspect and basic sequence
For wiring
'&9
$
%
&
'
Terminal
board
Run/stop switch (to be
prepared locally)
Section arranged as a local work
Alarm output (DC24V, less than 0.8A)
Relay coil for DC24V, etc. (to be prepared
locally) (The relay coil is powered on in
case of alarm) Please do not connect a
LED or a relay of internal diode type.
Time chart
Switch
Please keep more
than 5 minutes
More than
200ms
More than
200ms
ON
OFF
Run
Stop
Chiller
unit
N O T E
Pulse input indicates an ON input of the same switch when changing the status of the chiller unit, as shown in the
diagram above.