4. Troubleshooting
Troubleshooting by alarm code
SMGB0082 rev.1 - 07/2015
151
4
Alarm code
F1-81
~
84
Abnormality in current detection circuit
N O T E
Fan number is indicated by the last digit (example:
F1-81
for fan number 1........
F1-84
for fan number 4)
Alarm stop reason
•
Fan motor is started operation, but the current value is less than 1.5A
•
Fan motor is started operation, but according the fan position (inverter control) the current value is less than 4.0A
Retry indication
LCD: Fan Current Sensor Abnormality
Retry code
No indication
PCB monitoring position
PCB
EN
(Fan module)
Replace the fan module
Check fan motor
No
Yes
Yes
No
Restart.
Fan motor operates
Fan motor coil is
disconnected