3. Servicing
Cycle components
SMGB0082 rev.1 - 07/2015
97
3
3.5.22
Thermistor (Cooler water outlet, THMwo)
To remove the thermistor THMwo, proceed as follows:
1
Unscrew the nut of the cable gland
2
Gently pull the sensor wiring upwards.
C A U T I O N
Sensor sheath is full of sealing silicone. Use gloves
and eye goggles for protection in order to avoid
possible injuries to eyes and skin.
3
Disconnect the 1C and 1D Faston terminals at
the QCN3 connector from the rear of the E-box.
4
Replace the thermistor in reverse order than re-
moving.
N O T E
Use sealant silicone inside the sensor sheath to
protect and avoid any leakage.
Cable gland
Fitting adaptor
Sensor sheath
Sensor
Sensor wiring
3.5.23
Replacement of the solenoid valves (SVa, SVb, SVc)
1
Remove the screw with a Phillips screwdriver.
1
Gently pull the coil and remove it from the valve.
1
Remove 2 M6 screws that fixes the valve in the
compressor.
1
Replace the valve in reverse order than remov-
ing.
N O T E
Table of connections at compressor E-box
SVa
SVb
SVc
15/16
13/14
11/12
Screw
Solenoid valves
(SVa, SVb, SVc)
3.5.24
Replacement of the water inlet pipe purge
1
Remove the rear cover as explained in chapter
2
Remove the air purge from the top of the water inlet pipe
Water inlet air
purge