3. Servicing
Cycle components
SMGB0082 rev.1 - 07/2015
94
3.5.16
Replacement of the stop valve (x3)
There are 3 stop valves located along the refrigerant cycle: 2 are located close the expansion valves and 1 is located at
the filter drier, as shown in the pictures below.
To replace the stop valves, unscrew the stop valve with a spanner. Remove and replace the stop valve. Use Teflon tape to
seal the thread and avoid any leakage.
At expansion valves
At filter drier
Stop valve (x3)
3.5.17
Replacement of the thermistor (Suction, THMs)
1
Remove the insulation of the suction pipe.
2
Loosen the screw fixing the thermistor.
3
At the E-box, disconnect the CN27 contact (or
the Faston terminals 4C and 4D of multiple con-
tact QCN3)
4
Remove the thermistor.
5
When reassembling after replacing the thermis-
tor (THMd), perform the procedure in the re-
verse order than removing.
Thermistor THMs
Screw
Suction pipe