![Hitachi RCME-AH1 Скачать руководство пользователя страница 96](http://html.mh-extra.com/html/hitachi/rcme-ah1/rcme-ah1_service-manual_140451096.webp)
3. Servicing
Cycle components
SMGB0082 rev.1 - 07/2015
88
5
Remove the pressure differential assembly as
described in chapter
Water inlet pipe
Water outlet pipe
Pressure
differential
device
Flare nut for pres-
sure differential
device (inlet)
Flare nut for pres-
sure differential
device (outlet)
6
Remove the water inlet and water outlet pipes.
Remove the Victaulic couplings from their
attachment.
Water inlet pipe
Water outlet pipe
Victaulic couplings
7
Screw eyebolts to both sides of the condenser
to the bolts for that purpose. Fasten a textile belt
to proceed to lift the condenser.
C A U T I O N
Do not ever use chains or metallic ropes to lift the
condenser as they can damage the condenser.
8
Unscrew the 4 screw of the foot plate heat
exchanger.
9
Remove de condenser. Softly lift the condenser
and place it on a strong and stable surface.
C A U T I O N
In spite of water shut-off valves are closed, water inside the plate heat exchanger and water pipe remain.
C A U T I O N