4. Troubleshooting
Troubleshooting by alarm code
SMGB0082 rev.1 - 07/2015
147
4
Alarm code
F1-21
~
24
Fan error detection
Fan overcurrent
Fan fin temperature increase
N O T E
Fan number is indicated by the last digit (example:
F1-21
for fan number 1........
F1-24
for fan number 4)
Alarm stop reason
1
Detection of overcurrent · power voltage drop · short circuit.
2
Temperature of the inverter rises above the tolerance value.
N O T E
Causes alarm stop with 5 occurrences in 30 minutes. Retry control is performed until the fourth one. (Only the relevant
fan stops, and restarts automatically after 10 seconds)
Retry indication
LCD: By touching "Inspection" · "No.1 Cycle", "Fan error retry" · "Fan overcurrent retry" · "Fan fin temperature retry" are
shown in "Fan Status".
PCB monitoring position
PCB
EN
(Fan module)
N O T E
Please refer to “Fan earth detection” in the previous page fro the flowchart of “Fan error detection”
In the case of “Fan fin temperature increase”
Restart operation
Please apply silicon
grease covering the entire
contact surface
Eliminate the clogging
of the air side heat
exchanger or change the
auxiliary fan
Replace the fan PCBen
Replace the fan PCBen
Yes
Yes
Yes
No
No
No
It trips immediately
There is no silicon grease
in all the surface between
the transistor module of the fan
PCBen and radiation fins
The air side heat
exchanger is clogged or
auxiliary fan do not run.
Fan PCBen
Radiaton fins
Auxiliary fan
N O T E
Please use the silicone grease available as a service part (P22760).