4. Troubleshooting
Troubleshooting by alarm code
SMGB0082 rev.1 - 07/2015
148
In case of “fan overcurrent”
Restart operation
Replace the fan module
Replace the fan module
Replace the fan module
Check the surroundings of
fan module
•
Clogging of air side heat exchanger
•
Trapping of foreign bodies in the fan
•
Fan motor lock
•
Propeller fan contact
Check of the local power
source system
Check of the
wiring system
Yes
Abnormal
Not normal
Yes
Yes
Yes
Yes
No
No
No
No
No
(It can be reproduced)
(Rarely occurs)
It trips immediately
The current check of fan
motor exceeds 10A.
Turn power source OFF,
remove faston terminals
U,V,W on the fan module,
and turn DSW1-1# of the fan
module ON (Up). In that state,
reactivate power and try to
operate. Does it trip (release
zero A detection?
Voltage during operation is higher
than rated 15%
Check the
fan module
Local power source voltage is
within usage range
N O T E
Use silicone grease sealant between the PCB and aluminium fin to insure properly heat transfer. Available as spare part
(P22760).