. CONTORL LOGIC DESCRIPTION
5.4 Auto mode
This mode can be chosen with remote controller and the set temperature can be changed
between 16~30
℃
.
In auto mode, the machine will choose cooling, heating or fan-only mode according to
Δ
T (
Δ
T
=T1-Ts).
Δ
T=T1-Ts
Running mode
Δ
T > 3
℃
Cooling
-3
℃
≤
Δ
T ≤ 3
℃
Fan-only
Δ
T
<
-3
℃
Heating
Indoor fan will run at auto fan of the relevant mode. The louver operates
the
same as in relevant
mode. If the compressor keep
s
stopping for 10 minutes or the set temperature is modified, the
machine will choose mode according to
Δ
T again.
5.5 Evaporator low-temperature protection
DC-Inverter
AC will enter T2 protection if any of the following condition is satisfied.
Condition:
Cooling mode: When the indoor coil temp. T2 keeps lower than TE5 for 120
seconds, the compressor and outdoor fan will shut off. When T2 is higher than TE6, the
compressor and outdoor fan will restart up.
TE6
T2
On
Off
TE5