.TROUBLESHOOTING
Fault
code
Fault
d
escription
Possible
r
eason
s for
a
bnormality
How to
d
eal
w
ith
R
emarks
46 IPM and control board
communication fault
1.
The cable between the control
board and the driver board
is
connect
ed
loose
ly
;
2.
The cable between the control
board and the driver board
fail
s
;
3.
The driver board fail
s
;
4.
The control board fail
s
.
1.Reconnect the cable between
the control board and the
driver board;
2.Replace the communication
cable between the control
board and the driver board;
3.Replace the driver board;
4.Replace the control board.
47
Too high d
ischarge
temperature
fault
1.
2.
The refrigerant of the unit is not
enough;
The refrigerant of the unit is not
enough due to
that the
installation pipe
is longer
;
3.
Throttling service
fails
;
4.
The outdoor ambient temperature
is too high
.
1.
Check the welding point to
confirm whether the unit has
leakage
point, and then add
some
refrigerant
;
2.
Add some refrigerant refer
ring
to
the installation user manual;
3.
Replace the throttling service
(such as capillary, expansion
valve)
;
4.
Normal protection.
48
T
he outdoor DC
fan motor fault
(upper fan motor)
1.
The
connecting
wiring of the up
DC fan motor
is
loose;
2.
The cord of the up
per
DC fan
motor
fails;
3.
The up
per
DC fan motor
fails
;
4.
The drive circuit of the up
per
DC
fan
motor fail
s
;
5.
The outdoor fan has been
blocked.
1.
Reconnect the wiring of the up
DC fan motor;
2.
Replace the up
per
DC fan motor;
3.
Replace the up
per
DC fan motor;
4.
Replace the driver board of the
fan motor;
5.
Check the outdoor fan and
ensure
the outdoor fan can run
normally.
49
T
he outdoor DC
fan motor fault
(down fan motor)
1.
2.
The
connecting
wiring of the
down DC fan
motor
is
loose;
The cord of the down DC fan
motor
fails
;
3.
The down DC fan motor
fails
;
4.
The drive circuit of the down DC
fan motor fail
s
;
5.
The outdoor fan has been
blocked.
1. Reconnect the wiring of the
down DC fan motor;
2. Replace the down DC fan
motor;
3. Replace the down DC fan
motor;
4. Replace the driver board of
the fan motor;
5. Check the outdoor fan and
ensure the outdoor fan can run
normally.
91
The unit turn off due to
the IPM
board over heating
fault
1.
2.
The outdoor ambient
temp.
is too
high;
The speed of the out fan motor is
too low if the fan motor is AC fan
motor;
3.
The outdoor unit
is not
installed
in
accordance with the
standard
s
;
4.
The supply power is too low.
1.
2.
Normal protection;
Check the fan capacitor, and
replace the fan capacitor if it
fail
s
;
3. Reinstall the outdoor unit
refer
ring
to the installation
user
manual;
4.Normal protection.
96
Lacking of
refrigerant
The refrigerant of the unit is not
enough
.
Discharge the refrigerant and
charge the refrigerant
refer
ring
to the rating label
.
97
4-way valve
commutation failure
fault
1.
The
connecting
wiring of the 4-
way valve coil
is
loose;
2.
The 4-way valve coil fail
s
;
3.
The 4-way valve
fail
s
;
4.
The driver board of the 4-way
valve
fails.
1. Reconnect the wiring of the
4-way valve;
2. Replace the 4-way valve coil;
3. Replace the 4-way valve;
4.Replace the driver board of the
4-way valve.
23