– 94 –
CHECKING THE INDOOR/OUTDOOR UNIT ELECTRICAL PARTS AND REFRIGERATING CYCLE
[ MODEL RAS-25CNH11 / RAC-25CNH11 ]
Does the timer or dehumidifying lamp on
the indoor unit blink?
Set to room temperature 16
°
C in the
cooling mode or to 32
°
C in the heating
mode, and press the start/stop button.
Does the operation lamp on the indoor unit
start to light or blink?
Is the compressor in the outdoor unit
operating?
Remove the decorative cover and electrical
parts cover and check the pin voltages of
CN3 (brown and red wires).
Pin
5
: +35 V, pin
3
: 0V
See "Troubleshooting when the timer lamp
blinks".
Check the outdoor electrical parts.
Timer
lamp
Dehumidifying
lamp
No
No
Yes
Yes
No
Is approx. 35V DC being generated? Is the
polarity correct?
Remove the outdoor unit cover
and electrical parts cover, and
check self-diagnosis lamp LD301.
Does LD301 blink one time?
* Repeats 0.25-second on and
2-second off.
Check to see whether the F-
cable is connected incorrectly
or disconnected.
Set the service switch on the
outdoor unit to "cooling". Does
the compressor operate? (After
checking, be sure to return the
service switch to "normal".)
See Outdoor unit self-
diagnosis lamp lighting mode.
Check the refrigerating cycle.
Check the outdoor electrical parts.
Check the indoor electrical parts.
Blinking other
than one-time
One-time blinking
Yes
No
Normal
D101
+
–
A
B
C
D
Service switch
LD301
LD302
LD303
Yes
No
Содержание RAC-25CNH11
Страница 35: ... 35 CIRCUIT DIAGRAM MODEL RAS 25CNH11 ...
Страница 36: ... 37 CIRCUIT DIAGRAM MODEL RAC 25CNH11 ...
Страница 104: ... 113 PARTS LIST AND DIAGRAM MODEL RAS 25CNH11 11 2 18 8 20 19 12 63 1 4 60 3 7 14 15 6 5 16 13 88 61 17 9 62 10 ...
Страница 106: ... 115 MODEL RAC 25CNH11 55 22 59 16 26 24 23 20 21 19 13 52 58 53 56 57 2 3 51 15 14 18 4 5 9 6 8 54 17 7 11 10 12 25 ...
Страница 108: ...RAS 25CNH11 RAC 25CNH11 PM NO 0164E Printed in Malaysia HITACHI ...