– 69 –
‡
‡
‡
‡
£
£
£
£
£
£
1
2
zzz
@
!
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
B
A
W
+
V
+
V
-
U
+
U
-
W
-
W
V
U
U coil
DC compressor
motor
W coil
V coil
Power module
R806
DC current (Id)
detection resistor
MP6501
1000
F
µ
Fig. 3-5
●
Since current flows at point
B
only when U+ transistor is ON, the current waveform at point
B
becomes
intermittent waveform as shown in Fig. 3-3. Since current at point
B
is approximately proportional to the
input current of the air conditioner, input current is controlled by using DC current (Id) detection resistor.
<Reference>
If power module is detective, self diagnosis lamps on the control P.W.B. may indicate as shown below:
●
Simplified check of power module (Lighting mode when operated with compressor leads disconnected)
(1) Disconnect connector of 3-pole (WHT, YEL, RED) lead wire connecting to compressor located at the
lower part of electric parts box.
(2) Set to compressor operation state (other than FAN mode) and press Start/stop switch of remote
control.
(3) If normal operation continues for more than 1 minute (LD303 lights), power module is considered
normal.
❈
Refer to other item (troubleshooting on page 91) for independent checking of power module.
Fig. 3-4 Power module circuit (U+ is ON, V– is ON)
Self-diagnosis
Self-diagnosis lamp
and mode
lp (peak current cut)
LD301
Abnormal low speed
rotation
LD301
Switching incomplete
LD301
Blinks 2
times
Blinks 3
times
Blinks 4
times
Table 3-1
Control P.W.B.
LD301 Red
LD302 Red
LD303 Red
Self-diagnosis lamps
}
LD301
Blinks 10
times
Switching incomplete
Содержание RAC-25CNH11
Страница 35: ... 35 CIRCUIT DIAGRAM MODEL RAS 25CNH11 ...
Страница 36: ... 37 CIRCUIT DIAGRAM MODEL RAC 25CNH11 ...
Страница 104: ... 113 PARTS LIST AND DIAGRAM MODEL RAS 25CNH11 11 2 18 8 20 19 12 63 1 4 60 3 7 14 15 6 5 16 13 88 61 17 9 62 10 ...
Страница 106: ... 115 MODEL RAC 25CNH11 55 22 59 16 26 24 23 20 21 19 13 52 58 53 56 57 2 3 51 15 14 18 4 5 9 6 8 54 17 7 11 10 12 25 ...
Страница 108: ...RAS 25CNH11 RAC 25CNH11 PM NO 0164E Printed in Malaysia HITACHI ...