– 106 –
V
V
Interface relay
Coil terminal
Contact terminal
YES
YES
YES
NO
Is there DC35V output at both
ends of C67?
There are defective parts between
brown/red jumper wire and C/D
line.
Is DC 12V applied to both ends of
the control side (coil terminals) of
the interface relay?
Replace the interface relay.
Is a voltage (10V or more) generat-
ed between the connection termi-
nals of the interface relay?
Check the interface circuit.
YES
There are defective parts between
the 12V output of the switching
power supply on the control P.W.B.
and the interface relay. (Also check
the solder-touch, etc.)