“A” Group: Standard Functions
Configur
ing Dr
iv
e
P
a
ra
meters
3–10
NOTE:
The base frequency must be less than or equal to the maximum frequency (ensure that
A003
≤
A004).
A203 Base frequency setting,
2nd motor
Settable from 30 Hz to the
maximum frequency
✘ ✘
50.
60.
60.
Hz
>A203 2F-BASE
F 0060Hz
A004 Maximum frequency
setting
Settable from 30 Hz to
400 Hz
✘ ✘
50.
60.
60.
Hz
>A004 F-max
F 0060Hz
A204 Maximum frequency
setting, 2nd motor
Settable from 30 Hz to
400 Hz
✘ ✘
50.
60.
60.
Hz
>A204 2F-max