Using Intelligent Output Terminals
Oper
ations
a
nd Moni
tor
ing
4–36
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is
in Run Mode. The output relay contacts are
closed when the inverter is in Run Mode
(normally open logic).
NOTE:
The example circuit in the table above drives a relay coil. Note the use of a diode to
prevent the negative-going turn-off spike generated by the coil from damaging the inverter’s
output transistor.
Opt.
Code
Symbol
Function Name
Output
State
Description
00
RUN
Run signal
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Valid for
outputs:
11, 12, AL0 – AL2
Required
settings:
(none)
Notes:
•
The inverter outputs the [RUN] signal
whenever the inverter output exceeds the start
frequency specified by parameter B082
.
The
start frequency is the initial inverter output
frequency when it turns ON.
[FW, RV]
Motor
speed
Run
Signal
start freq.
B82
t
See I/O specs on page
.
Inverter output terminal circuit
12C
12A
11C
11A
24VDC
L
Example: (Default output configuration
shown—see page
.)
+
–
RUN
Содержание L300P Series
Страница 2: ......
Страница 42: ......
Страница 134: ......
Страница 195: ...Inverter System Accessories In This Chapter page Introduction 2 Component Descriptions 3 Dynamic Braking 6 5 ...
Страница 225: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 6 A ...
Страница 250: ......
Страница 251: ...Drive Parameter Settings Tables In This Appendix page Introduction 2 Parameter Settings for Keypad Entry 2 C ...
Страница 263: ...CE EMC Installation Guidelines In This Appendix page CE EMC Installation Guidelines 2 Hitachi EMC Recommendations 4 D ...
Страница 272: ......